
INSTALLATION
1. Remove the four #10 hex head screws from
the back of the enclosure and attach mounting
brackets to enclosure.
2. Select the proper location for the Control
Panel and hang enclosure on a flat vertical
surface or other support, using hardware
suitable for the purpose.
3. Prepare the necessary conduit runs, terminate
them at both ends and pull in the conductors
as specified by the installation layout.
4. If external bonding is required, install a
bonding lug at bottom of enclosure and bond
installation according to code requirements.
5. The enclosure must be grounded as required
by NEC, Article 680 and any applicable
local codes.For Canadian installations, the
transformer supply circuit must be protected
by a ground fault circuit interrupter.
6. If this enclosure is used for direct connection
of underwater lights, refer to 1999 NEC 680-
21(b), 2002 NEC 680-24(b) or CEC 68-060,
062 and 066 for further details.
7. Make sure that all unused transformer taps
(leads) are separately insulated.
8. Use the tables at the top of page 3 as a guide
to determine the correct wire size.
9. Check voltage at lamp terminals after
installation. It should be 12+0.3 volts.
10. Install front panel over wiring compartment.
The control is now ready for programming,
see OPERATION section on Page 3.
2
8"
21 1/4"
4 3/8"
4 3/4"
20 7/8"
12 7/8"
Figure 1
Risk of injury or property damage!
Do not install or operate this equipment and other associated equipment without basic safety
precautions.
Read and follow the safety instructions listed below and other basic safety precautions before
installation or operation of this control and other associated equipment.
1. This control must be installed by a qualified person, according to the national and local electrical
codes.
2. Install this control not less than 5 feet (3 meters in Canada) from inside edge of pool and 1 foot
(30cm) above ground.
3. USE COPPER CONDUCTORS ONLY rated 90˚C minimum.
4. Do not exceed maximum ratings of individual components, wiring devices and current carrying
capacity of conductors.
5. For control grounding, bonding, installing and the wiring of underwater lights, refer to Article 680
of the National Electrical Code or Article 68 of the Canadian Electrical Code.
6. The control should not operate any equipment which would cause bodily injury or property
damage should it be activated unexpectedly.
CAUTION