TESTING & MAINTENANCE
Table A: IPS Diagnostic Codes
STATUS INDICATION
RED
GREEN
OFF
FLASHING GREEN
FLASHING RED/GREEN
FLASHING RED (ONCE PER 0.5 SEC.)
FLASHING RED (ONCE PER 6 SEC.)
TWO RED FLASHES
THREE RED FLASHES
CONDITION
BATTERY IS CHARGING
BATTERY IS FULLY CHARGED
EMERGENCY MODE
UNIT IS PERFORMING A TEST
INSUFFICIENT CHARGE
BATTERY MAY BE MISSING
BATTERY FAILURE
LOAD FAILURE
ELECTRONICS FAILURE
FOUR RED FLASHES TEMPERATURE OUT OF RANGE
WIRING DIAGRAM
ILBDW S AND SLTEST WITH IPS TEST ACCESSORY
ILBDW-IPS.EPS
AC (NORMAL)
DRIVER
LED
LOAD
UNSWITCHED 24/7 POWER
NEUTRAL
BLACK (120-277V, 50/60HZ)
IPS TEST
ACCESSORY
(”SLTEST” MODELS)
LOCATION OF IPS TEST ACCESSORY VARIES
ACCORDING TO MODEL. FOR “SLTEST” MODELS
THE IPS TEST ACCESSORY IS PRE-CONNECTED
BY THE FACTORY, NO ADDITIONAL CONNECTIONS
ARE NEEDED.
IPS TEST
ACCESSORY
(”S” MODELS)
PVC
CONDUIT
1
1
1
WHITE
GREEN
GROUND
WHITE/RED WHITE
RED (+) LED OUTPUT (+)
LED OUTPUT (-)
BLUE (-) LED INPUT (-)
VIOLET/WHITE (+) LED INPUT (+)
ILBDW
EMERGENCY DRIVER
Refer to the diagram below for the appropriate wiring of the LED load and driver. Install in accordance with the National Electrical
Code and local regulations. For additional wiring diagrams consult Customer Service.
Automatic Testing
The ILBDW is designed to automatically test the emergency
function for 60 seconds each month, and
90 minutes every 12 months.
Self-testing works in conjunction with the IPS assembly. Any
detected failures will be indicated by ashing of the three-color
LED. See Table A for diagnosis.
Manual Testing
Manual testing of the ILBDW can be performed by pressing
and releasing the IPS test button. Only initiate a manual test
when the IPS status indicator light is GREEN (see Table A).
Manual testing lasts 60 seconds and may be cancelled at any
time during the test duration by pressing and holding
the IPS.
Load Calibration
To ensure proper operation, Load Calibration is required whenever the LED load connected to the ILBDW is changed. Note:
Load Calibration happens automatically 48 hours after the ILBDW is rst installed. If after installation, the connected LED
load is changed, Load Calibration will need to be performed. This will happen automatically 48 hours after the ILBDW is
re-initialized (see Maintenance section below). To manually initiate Load Calibration earlier, press and hold the IPS button for
20 seconds. After 20 seconds, the LED load will turn o. Release the IPS button. The LED load should turn back on and the IPS
will begin FLASHING GREEN to indicate that the 60-second Load Calibration is commencing. Any failures detected during Load
Calibration will be indicated on the IPS (see Table A).
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Consult Customer Service or visit www.iotaengineering.com for current warranty information.
Maintenance
When performing maintenance on the ILBDW or the emergency luminaire, the ILBDW battery circuit must be completely pow-
ered down by performing the following steps:
1) Disconnect AC power. The ILBDW will enter EMERGENCY MODE.
2) Disconnect the battery circuit through one of the following methods:
Method 1: This can only be performed within the rst 30 seconds of EMERGENCY Mode - Press and hold the IPS button for
approximately ve seconds until the LED Module shuts o.
Method 2 (“S” Models Only): Unplug the IPS
Once all power sources are disconnected from the ILBDW and emergency luminaire, proceed with required maintenance.
When maintenance is complete, reconnect the IPS (if unplugged from Method 2 above) and restore AC power to the emer-
gency luminaire. The AC Activate circuitry will detect the presence of AC power and automatically re-activate the ILBDW battery
charging circuit.