IV Produkt’s continuous product development may give rise to specification changes without prior notice.
Product sheet
Operation and MaintenanceFlexomix MIE-EF
2015-01-071 (2)
Humidifier fitting (code MIE-EF)
The fitting is selected together with an evaporative
humidifier (code EFEF) with cold humidifying surfaces
that can also be used for evaporative cooling.
The fitting consists of a humidifier block, water
reservoir, water distribution system and housing front
section for integration into the standard module (code
EMM).
•
The water reservoir is made from stainless steel.
Spraybars and pipe parts are made from PVC
plastic.
• The humidifier is made from a specially
impregnated composite material.
• Two different versions of the humidifier are
available:
circulating water or direct water.
A droplet eliminator is also available.
• The humidifier is available with two different
humidification rates:
max. 85% (FA6-85) or max. 95% FA6-95).
• A pump is included as standard for humidifiers
using circulating water.
For further information on humidifiers, see Munters
FA6, product sheet at ivprodukt.se.
Accessories for fitting
• Mounted damper motor (code KJST-04)
• Water trap (code MIET-CL-04)
Integral attenuation (dB)
Octave band
intermediate
frequency (Hz) 63 125 250 500 1,000 2,000 4,000 8,000
EFEF
85% 3 2 2 3 5 6 12 15
95% 3 2 3 3 5 7 13 16
Technical data, sizes 150–950
Configuration MIE-EF
Sizes 150–600
Sizes 740–950
Configuration humidifier
Circulating water Direct water
Water consumption
Circulating water
The total water consumption is determined by the
amount of evaporated and bled-off water respectively.
To calculate the water consumption, see Munters FA6
Technical manual at ivprodukt.se.
Direct water
Total water consumption (T) for direct water:
Size
Configuration
FA6-85 FA6-95
150 6.3 6.3
190 8.0 8.0
240 8.5 8.5
300, 360 10.0 10.0
480, 600 12.0 12.0
740 15.0 15.0
750 12.0 12.0
850 15.0 15.0
950 12.0 12.0