jablotron JA-81M User manual

The JA-81M wireless magnetic door detector & universal transmitter 1 MHQ53800_PTS
The JA-81M wireless magnetic door detector & universal transmitter
The JA-81M is a component of Jablotron’s Oasis 80 alarm system. It is
designed to detect the opening of doors, windows etc. It can also be
extended by a normally closed / normally open sensor.
It is also designed to detect the handling of roller blinds. This is
achieved by detecting ratchet-wheel movements. Small movements are
filtered out so that wind blasts do not cause false alarms.
The battery-powered detector communicates via OASIS radio protocol.
MG OFF
MG ON
tamper
switch
external
sensors
Reaction
mag. sensor
ON/OFF
INSTANT
DELAY
IN 2
IN 1
GND
TMP
1k
LITHIUM
3,6V AA
Installation
Installation shall only be undertaken by technicians holding a certificate
issued by an authorized distributor.
This detector reacts to the removal of its magnet unit. The electronics
should be installed onto the non-moving part of windows or doors, and the
magnet onto the moving part. The detector should be installed vertically.
Avoid locating it directly on a metal frame as metal influences the
functioning of the magnetic sensor and radio communication. If the door
or window is made of metal, we recommend installing the detector unit
away from the metal and wiring up an external wired magnetic sensor
which is connected to the detector. See the following instructions:
1. Open the detector cover by pressing the tab in.
2. Screw the rear cover to the solid part of the door/window.
3. Attach the magnet to the moving part of the window. Its distance
from the detector should not exceed 5mm when the door/window is
closed. The lower edge of the magnet should be aligned with the
lower edge of the detector. Only a single magnet can be installed,
either on the left side or the right side of the detector.
4. Leave the battery disconnected and the cover open and then
follow the control panel or receiver manual. The basics of
enrollment are:
1. Enter enrollment mode on the control panel by keying in “1” in
Service mode.
2. Install a battery into the detector to activate enrollment.
3. Exit enrollment mode by pressing “#”
After installing a battery into the detector, allow up to 30 seconds for
stabilisation. During this period the LED is continuously lit.
To enroll a detector after having already connected a battery, first
disconnect the battery, and press and release the tamper sensor to
discharge any remaining charge to ready the device for enrolment.
DIP switches
MG ON / MG OFF Allows the internal magnetic sensor inside the
detector to be disabled when the detector is only to be used with external
sensors wired to its terminals.
INS / DEL DEL provides entrance & exit delays for detectors installed in
a building entrance. INS allows the detector to instantly trigger alarm
activation if the control panel is armed. This DIP switch (INS/DEL) only
has an effect if the detector has a natural reaction assigned to its
address in the Oasis control panel. It also has no effect when used with a
UC-8x or AC-8x receiver.
Opening the cover makes the detector react with a tamper signal.
Open / closed status detection
The detector is factory-set to indicate both opening and closing so that the
control panel knows the status of doors/windows. If a pulse mode is
desired to indicate only opening, keep the tamper switch pressed while
installing the battery. Not pressing the tamper switch gives open and closed
status signals.
Wiring up the external sensor
External sensors can be wired to the detector. It is possible to protect
more doors / windows or to wire in other types of wired detectors. The
inputs IN2 and TMP react when disconnected from the GND common
terminal. The IN1 input can be used either as a NC input or a balanced
loop input (EOL resistor 1k). The function is detected automatically.
IN1 If the IN1 terminal is disconnected from GND it sends the same
signal to the control panel as if the magnet had been removed from the
detector. The internal magnetic sensor can be disabled by the DIP switch
if desired.
IN 1
IN 2
Wiring example for NC contacts
The balanced loop feature can be used when the connection of a
detector with a NO output is needed. The resistor is then shorted out by
the closing contact and the detector is triggered.
Overflow
detector
IN 1
IN 2
1k
Wiring example for NO contact
IN2 The IN2 input terminal receives signals from the ratchet-wheel.
Alarm signals are then only transmitted when the ratchet contact is
opened at least three times within 10 seconds. This filters out
disconnections caused by accidental ratchet-wheel shifts, which are due
to wind blasts. When the IN2 input is opened for more than 1 sec a
tamper signal is sent.
ALARM
t < 5s
Ratchet-wheel function scheme
TMP The TMP terminal sends a tamper signal to the control panel if
disconnected from GND.
Note: If any of these two inputs is not used, it must be shorted to the GND
terminal.
The maximum length of the cable for external detector is 3 meters.
The JA-81M wireless magnetic door detector & universal transmitter 2 MHQ53800_PTS
Testing the detector
15 minutes after closing the detector cover, the LED indicates detector
triggering. The strength and quality of detector signals can be measured
by the control panel in Service mode.
Battery replacement
The detector monitors its battery voltage and if too low, a transmission is
sent to the control panel to inform the installer or user. The detector
continues to function and shows each triggering of the detector with a flash
of its LED. Battery replacement should not be delayed by more than two
weeks. This should be done by a qualified technician with the control panel
in Service mode.
Expired batteries should not be thrown into the garbage, but disposed of
according to local regulations.
Removing the detector from the system
If a detector is removed, the control panel announces the removal. The
detector has to be deleted in the control panel before intentional removal.
Technical parameters
Voltage Lithium battery type LS(T)14500 (3.6V AA)
Typical battery lifetime approx. 3 years for 20 daily activations maximum
Communication band 868 MHz, Oasis protocol
Communication range approx. 300m (open area)
Typical sensitivity range of the built-in magnetic sensor 45 / 25mm
Inputs for external sensors IN2 and TMP = normally closed loops
IN1 normally closed or balanced loop (1k resistor)
The maximum length of the cable for external detectors 3 meters
Dimensions 110 x 31 x 26 mm
magnet: 56 x 16 x 15 mm
Operational environment according to EN 50131-1 II. Indoor general
Operational temperature range -10 to +40 °C
EN 50131-1,CLC/TS 50131-2-6, EN 50131-5-3 classification: grade 2
Complies with ETSI EN 300220, EN50130-4, EN55022, and EN 60950-1
Can be operated according to ERC REC 70-03
Jablotron Ltd. hereby declares that the JA-80M is in compliance with the essential
requirements and other relevant provisions of Directive 1999/5/EC
CAUTION: Changes or modifications not expressly approved by Jablotron could void
the user´s authority to operate the equipment. The original of the conformity
assessment can be found at www.jablotron.com, Technical Support section
Note: Although this product does not contain any harmful materials we suggest you
return the product to the dealeror directly to the producer after use.

Other jablotron Security Sensor manuals

jablotron JA-158P User manual

jablotron

jablotron JA-158P User manual

jablotron JA-180S User manual

jablotron

jablotron JA-180S User manual

jablotron JA-160PC User manual

jablotron

jablotron JA-160PC User manual

jablotron JA-120PW User manual

jablotron

jablotron JA-120PW User manual

jablotron JA-159P User manual

jablotron

jablotron JA-159P User manual

jablotron JA-83M User manual

jablotron

jablotron JA-83M User manual

jablotron JA-151P-WW User manual

jablotron

jablotron JA-151P-WW User manual

jablotron JA-152P User manual

jablotron

jablotron JA-152P User manual

jablotron JA-157P User manual

jablotron

jablotron JA-157P User manual

jablotron JA-158P User manual

jablotron

jablotron JA-158P User manual

jablotron JA-151P-WW User manual

jablotron

jablotron JA-151P-WW User manual

jablotron JA-151TH User manual

jablotron

jablotron JA-151TH User manual

jablotron LARGO JS-20 User manual

jablotron

jablotron LARGO JS-20 User manual

jablotron JA-160PC User manual

jablotron

jablotron JA-160PC User manual

jablotron JB-EXT-TH-R User manual

jablotron

jablotron JB-EXT-TH-R User manual

jablotron JA-120PC User manual

jablotron

jablotron JA-120PC User manual

jablotron JA-158P User manual

jablotron

jablotron JA-158P User manual

jablotron JA-80S User manual

jablotron

jablotron JA-80S User manual

jablotron JA-89P User manual

jablotron

jablotron JA-89P User manual

jablotron JA-80IR User manual

jablotron

jablotron JA-80IR User manual

jablotron JA-150P PET User manual

jablotron

jablotron JA-150P PET User manual

jablotron JA-15P User manual

jablotron

jablotron JA-15P User manual

jablotron JA-60V User manual

jablotron

jablotron JA-60V User manual

jablotron JA-160PC User manual

jablotron

jablotron JA-160PC User manual

Popular Security Sensor manuals by other brands

Inficon T-Guard2 Translation of the original operating instructions

Inficon

Inficon T-Guard2 Translation of the original operating instructions

INTERTECHNO PIR-6000 operating instructions

INTERTECHNO

INTERTECHNO PIR-6000 operating instructions

BEA LZR-MICROSCAN T manual

BEA

BEA LZR-MICROSCAN T manual

Velodyne HD HDL-64E S2 User's manual and programming guide

Velodyne

Velodyne HD HDL-64E S2 User's manual and programming guide

Autronica AutroFlame X33AF PL instructions

Autronica

Autronica AutroFlame X33AF PL instructions

MSA SOLARIS operating manual

MSA

MSA SOLARIS operating manual

Bosch PROFESSIONAL wallSCANNER D-TECT 100 concrete operating instructions

Bosch

Bosch PROFESSIONAL wallSCANNER D-TECT 100 concrete operating instructions

Airthings Corentium Pro manual

Airthings

Airthings Corentium Pro manual

Nucleonix PCM 738A instruction manual

Nucleonix

Nucleonix PCM 738A instruction manual

Arlec am120 Installation & operating instructions

Arlec

Arlec am120 Installation & operating instructions

Velleman VTTEST18 user manual

Velleman

Velleman VTTEST18 user manual

V2 SENSIVA-XS instruction manual

V2

V2 SENSIVA-XS instruction manual

EZ-ON 101M2 installation instructions

EZ-ON

EZ-ON 101M2 installation instructions

IR-Tec DP-150A installation instructions

IR-Tec

IR-Tec DP-150A installation instructions

Alarmcom ADC-IS-300-LP installation guide

Alarmcom

Alarmcom ADC-IS-300-LP installation guide

Heath Zenith 5596 manual

Heath Zenith

Heath Zenith 5596 manual

B-Link PKP-1500-LI user manual

B-Link

B-Link PKP-1500-LI user manual

Elmo HERCOLA user manual

Elmo

Elmo HERCOLA user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.