
ZZ 1019/1E
5
6.3 CONDENSATE
6.3.1 When firing , the unit may produce condensate which must be drained away. A JDT1 kit, which externally drains
the condensate away from the flue terminal is available for horizontal flued applications. Vertical flued
applications require the fitment of an in-line condensate trap within 0.5 m of the unit, in the first vertical flue run,
and before any bends in the flue run. Such a trap, with a 32 mm male drainage connection, is available for this
purpose.
6.3.2 Condensate from vertical flued applications must be drained away using 32 mm or 20 mm internal diameter, rigid
plastic pipe, connected to the condensate drain using KUTERLITE 700 or similar straight coupling. The pipe
should be installed in such a manner, that it forms a continuous downward slope away from the unit at a minimum
3oangle (6 mm per 100 mm, or, 0.75 in per foot run), and that the risk of mechanical damage and interior
interference is minimised. The pipe is to be protected against frost damage.
6.4 ELECTRICAL
6.4.1 Mains: The heater is supplied with mains cable (PVC sheathed, high temperature resistant, 3 core [Brown-
Blue-Green/Yellow], 6A, 0.75mm2), connected to a terminal block and exiting from the heater at the bottom right
hand rear. The cable is suitable for a 230V 50Hz single phase supply and must be protected by a 5A fuse, and an
earth wire must be connected. This cable must only be replaced by either the maunfacturer or a recognised and
qalified service engineer.A double pole switch or fused spur box should also be used. All wiring conform to I.E.E.
regulations, (current edition).
6.4.2 Thermostat: A Thermostat is provided with the appliance. The Thermostat wiring is to be connected to
terminals 6 and 7 on the air heater control panel, (marked ‘THERMOSTAT’), polarity being unimportant. It should
be located where there is free air circulation, and approximately 1.5m (5ft) from the floor. The following
locations should be avoided.
a. In a room where temperature is greatly affected by the sun or any other heat source (e.g. radiant fire, wall
light fitting or TV set).
b. Near an outside door or windows, or on an outside wall.
c. Where it can be affected by warm air ducts, diffusers, waste pipes or the heater itself.
d. Where it can be subject to vibration.
6.4.3 Time Control: If an external time control (not supplied) is to be fitted, connect the live supply to terminal 3,
the neutral to terminal 4, and the time-switch output to terminal 5. If no time control is fitted, link terminal 3
and 5.
6.5 GAS (see BS 5864 and BS 6891)
6.5.1 An independent gas supply pipe from the gas meter is to be preferred wherever possible. However, when this is
not possible, the pipe must be capable of taking the complete input of the heater and all other gas appliances being
served by this same pipe. This supply should be suitably sized to conform to British Standards requirements of no
more than 1.0 mbar (0.4 in. wg.) pressure drop (see table of discharge in BS 6891).
6.5.2 The 1/2in union gas cock (supplied) must be fitted externally in the gas inlet of the heater for easy isolation during
servicing. The gas pipe should be fitted and installed as to be durable, substantial and gas tight. Gas entry to the air
heater may be through the left hand side, right hand side front, or rear, to an Rc1/2(1/2in B.S.P. internal (taper)
thread).
7. COMMISSIONING
7.1 Ensure the following:
7.1.1 Gas and Electrical supplies are OFF.
7.1.2 Filter, fan and fan compartments are free from obstructions.
7.1.3 All registers or grilles are open and conform to design specifications.
7.1.4 Return, relief and ventilation air installations are adequate.
7.1.5 Adhesive label is removed from the centre of the combustion air fan to expose the motor cooling slots.
7.2 Turn ON the gas supply to the heater.
7.3 Test for gas soundness at supply, Multifunctional control and the Main burner using proprietary detection fluid, sealing
any leaks found, and purge the whole gas pipe as described in BS 6891.
7.4 Set the Thermostat to its maximum setting.
7.5 Ensure that the time control (if fitted) is in an ON position.
7.6 Switch on the electrical supply to the heater. The combustion air fan will start up immediately; after a minimum of 30
seconds, the burner will automatically ignite and the green ‘BURNER ON’ indicator will illuminate.
12
ZZ 1019/1E
BURNERNOTOPERATING
Check that the time control is on and Thermostat is calling for heat.
Check mains electrical supply.
Link terminals 3 & 5 (shorts out clock).
Disconnect Thermostat at terminals 6 & 7.
Noresponse Burner lights
Linkterminals 15&16. Reinstate connections at 6 & 7.
Check wiring to, or replace
Thermostat.
Noresponse Burner lights
Checkterminal 14for 230volts. Replace fandelay/limit
control.
No230 volts 230volts detected
CheckICU terminal5 for230 volts. Check wiring to, or replace
multifunctionalcontrol.
No230 volts 230volts detected
CheckICU terminal8 for230 volts. Checkwiring.
No230 volts 230volts detected
Check terminal C4 for230volts. Replace Ignition Control
Unit.
No230 volts 230volts detected
Check terminal C3 for 230 volts. Check wiring.
No230 volts 230volts detected
Checkterminal 5for 230volts Replace Control Module.
No230 volts 230volts detected
Check 3.15 A fuse, if OK check 230 volt Check wiring and Air Heating
input at terminal 1 Switch.
AirHeatingSwitchand
WiringOK
Replace Ignition Control unit
or Pressure switch
BURNERON,BUTAIRCIRCULATIONFANNOTRUNNING
Check for 230 volts at fan terminals 11 & 12
No230 voltsdetected 230voltsdetected
Switchto ‘SummerAirflow’. Switchto ‘SummerAirflow’.
230volts detected
Replace air circulation fan.
Aircirculation fanruns Aircirculationfandoes
Replacefan delay/limit control. notrun
Replace Fan Speed Transformer
BURNERONCONTINUOUSLY
(ROOMTEMPERATURETOOHIGH)
Setthe Air HeatingSwitch to‘Summer Airflow’
Burnerremainsalight Burner goesout
Disconnect solenoid plug at Replace Thermostat.
multifunctionalcontrol.
Burnerremainsalight
Replace multifunctional control.
AIRCIRCULATIONFANCONTINUESTORUNORCYCLES
WHENBURNERISNOTON
Check that Air Heating switch is not set to ‘Summer Airflow’.
Disconnect Thermostat and link terminals 6 & 7.
Disconnect the fan delay/limit control.
Aircirculation fanstops Air circulationfan continuesto run
Replacefan delay/limit ReplaceControl module
control
AIRCIRCULATIONFANON,BUTBURNERCYCLESBEFORE
REQUIREDCOMFORTLEVELISREACHED
Disconnect Thermostat at terminals 6 & 7.
Burnercontinuestocycle Burnerremains on
Check air filter, return air path Thermostat defective.
and outlets for restrictions.
Burnercontinuestocycle
Link terminals 15 & 16 to bypass limit control.
Burnercontinuestocycle Burnerrunsand room
Replace Thermostat. temperaturerises
Check temperature rise.
Less than 60 degrees C Morethan 60degreesC
Replace fan delay/overheat (limit) Replace Thermostat
control.
PRESSURESWITCHDEFECTIVE