  9. Johnson Controls TCGF24 User manual

Johnson Controls TCGF24 User manual

This manual suits for next models

6

Other Johnson Controls Air Conditioner manuals

Johnson Controls Y Seroes Manual

Johnson Controls

Johnson Controls Y Seroes Manual

Johnson Controls York FREE MATCH EK Series User manual

Johnson Controls

Johnson Controls York FREE MATCH EK Series User manual

Johnson Controls PCE4 Series User manual

Johnson Controls

Johnson Controls PCE4 Series User manual

Johnson Controls Duct R-410A Quick start guide

Johnson Controls

Johnson Controls Duct R-410A Quick start guide

Johnson Controls YORK YH9FXC18BAH-FX User manual

Johnson Controls

Johnson Controls YORK YH9FXC18BAH-FX User manual

Johnson Controls HIC4008B21S User manual

Johnson Controls

Johnson Controls HIC4008B21S User manual

Johnson Controls SINGLE PHASE Guide

Johnson Controls

Johnson Controls SINGLE PHASE Guide

Johnson Controls J ZH Series User manual

Johnson Controls

Johnson Controls J ZH Series User manual

Johnson Controls M Series User manual

Johnson Controls

Johnson Controls M Series User manual

Johnson Controls J ZT Series User manual

Johnson Controls

Johnson Controls J ZT Series User manual

Johnson Controls TempMaster ZD Series User manual

Johnson Controls

Johnson Controls TempMaster ZD Series User manual

Johnson Controls ZD Series User manual

Johnson Controls

Johnson Controls ZD Series User manual

Johnson Controls York ZD Series User manual

Johnson Controls

Johnson Controls York ZD Series User manual

Johnson Controls YFK Series User manual

Johnson Controls

Johnson Controls YFK Series User manual

Johnson Controls YJHJXH024BARR-FX User manual

Johnson Controls

Johnson Controls YJHJXH024BARR-FX User manual

Johnson Controls York YH9FZC24BAH-AFX User manual

Johnson Controls

Johnson Controls York YH9FZC24BAH-AFX User manual

Johnson Controls 13 SEER - GCGD User manual

Johnson Controls

Johnson Controls 13 SEER - GCGD User manual

Johnson Controls GCGD18S User manual

Johnson Controls

Johnson Controls GCGD18S User manual

Johnson Controls York YH9FYC24BAH-A-X User manual

Johnson Controls

Johnson Controls York YH9FYC24BAH-A-X User manual

Johnson Controls 18 SEER CZH Series User manual

Johnson Controls

Johnson Controls 18 SEER CZH Series User manual

Johnson Controls CSV Series User manual

Johnson Controls

Johnson Controls CSV Series User manual

Johnson Controls 341426-BIM-A-0108 User manual

Johnson Controls

Johnson Controls 341426-BIM-A-0108 User manual

Johnson Controls RAC13L Guide

Johnson Controls

Johnson Controls RAC13L Guide

Johnson Controls YORK D4IC 360 User manual

Johnson Controls

Johnson Controls YORK D4IC 360 User manual

Popular Air Conditioner manuals by other brands

Fujitsu ASYG 09 LLCA installation manual

Fujitsu

Fujitsu ASYG 09 LLCA installation manual

York HVHC 07-12DS Installation & owner's manual

York

York HVHC 07-12DS Installation & owner's manual

Carrier Fan Coil 42B Installation, operation and maintenance manual

Carrier

Carrier Fan Coil 42B Installation, operation and maintenance manual

intensity IDUFCI60KC-3 installation manual

intensity

intensity IDUFCI60KC-3 installation manual

Frigidaire FAC064K7A2 Factory parts catalog

Frigidaire

Frigidaire FAC064K7A2 Factory parts catalog

Sanyo KS2432 instruction manual

Sanyo

Sanyo KS2432 instruction manual

LG MultiV Series installation manual

LG

LG MultiV Series installation manual

CLIMAVENETA a-CHD U-2T 606+2209 OPERATING AND INSTALLATION Manual

CLIMAVENETA

CLIMAVENETA a-CHD U-2T 606+2209 OPERATING AND INSTALLATION Manual

Midea EWK06CW5 user manual

Midea

Midea EWK06CW5 user manual

Pioneer FAB Series installation manual

Pioneer

Pioneer FAB Series installation manual

SPT WA-1511S user manual

SPT

SPT WA-1511S user manual

Mitsubishi Electric Mr.Slim MSZ-A24NA operating instructions

Mitsubishi Electric

Mitsubishi Electric Mr.Slim MSZ-A24NA operating instructions

Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Mitsubishi Electric

Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Panasonic CS-S18HKQ Service manual

Panasonic

Panasonic CS-S18HKQ Service manual

Panasonic CS-E15NKE3 operating instructions

Panasonic

Panasonic CS-E15NKE3 operating instructions

Gree GWH18TC-K3DNA1B/I Service manual

Gree

Gree GWH18TC-K3DNA1B/I Service manual

Friedrich ZoneAire Compact P08SA owner's manual

Friedrich

Friedrich ZoneAire Compact P08SA owner's manual

Daikin R32 Split Series installation manual

Daikin

Daikin R32 Split Series installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Johnson Controls Unitary Products 362564-UTD-B-0708
TABULAR DATA SHEET
Outdoor Split System Air Conditioner 2 Thru 5 Tons
MODELS: TCGF24* THRU 60
14.5 SEER – R-410A, 1 PHASE
All dimensions are in inches. They are subject to change
without notice. Certified dimensions will be provided upon
request.
Physical and Electrical Data
MODEL TCGF24S41S1 TCGF30S41S1 TCGF36S41S1 TCGF42S41S1 TCGF48S41S1 TCGF60S41S1
Unit Supply Voltage 208-230V, 1φ, 60Hz
Normal Voltage Range 1
1.Rated in accordance with ARI Standard 110, utilization range “A”.
187 to 252
Minimum Circuit Ampacity 16.8 18.4 19.1 23.9 27.9 35.9
Max. Overcurrent Device Amps 2
2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
25 30 30 40 45 60
Min. Overcurrent Device Amps 3
3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
20 20 20 25 30 40
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll
Compressor
Amps Rated Load 12.8 14.1 14.1 17.9 21.1 27.5
Locked Rotor 58 73 77 112 115 135
Crankcase Heater No No No No No No
Fan Motor Amps Rated Load .8 .8 1.5 1.5 1.5 1.5
Fan Diameter Inches 22 22 22 24 24 24
Fan Motor Rated HP 1/8 1/8 1/4 1/4 1/4 1/4
Nominal RPM 1075 1075 850 850 850 850
Nominal CFM 2750 2800 3200 3600 3600 3700
Coil Face Area Sq. Ft. 13.1 17.4 17.4 20.0 21.4 24.0
Rows Deep 1 1 1 1 1 1
Fin / Inches 23 23 23 23 23 23
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line Set OD (Field Installed) 3/4 3/4 3/4 7/8 7/8 1 1/8
Unit Charge (Lbs. - Oz.) 4
4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
3 - 2 3 - 7 3 - 10 4 - 4 4 - 9 5 - 9
Charge Per Foot, Oz. 0.62 0.62 0.62 0.67 0.67 0.75
Operating Weight Lbs. 128 130 145 172 180 199
B
C
A
Unit
Model
Dimensions
(Inches) Refrigerant Connection
Service Valve Size
A1
1. Including Fan Guard.
B C Liquid Vapor
24 28 29 29
3/8”
3/4”30 36 29 29
36 36 29 29
42 34 33.6 33.6 7/8”
48 36 33.6 33.6
60 40 33.6 33.6 7/8”2
2. Adapter fitting required for 1-1/8” line set.
362564-UTD-B-0708
2Johnson Controls Unitary Products
R-410A SYSTEM CHARGING PROCEDURE
Additional R-410A Charge / Orifice Size for Various Matched Systems
Outdoor Unit TCGF24S41S1 TCGF30S41S1 TCGF36S41S1 TCGF42S41S1 TCGF48S41S1 TCGF60S41S1
Required Orifice or TXV 11TVM902 1TVM903 1TVM903 1TVM903 1TVM905 1TVM906
Factory Charge, lbs-oz 3 - 2 3 - 7 3 - 10 4 - 4 4 - 9 5 - 9
Indoor Coil2,3,4 Additional Charge, Oz
FC/MC/PC24A3X 5 –––––
FC/MC/PC24B3X 5 –––––
FC/MC/PC30A3X 12 2 ––––
FC/MC/PC30B3X 12 2 ––––
FC/MC/PC32A3X 16 10 ––––
FC/MC/PC35B3X 16 10 ––––
FC/MC/PC35C3X 16 10 ––––
FC/MC/PC36A3X 8 4 ––––
FC/MC/PC36B3X 8 4 8 –––
FC/MC/PC36C3X 8 4 1 –––
FC/MC/PC37A3X 24 19 15 –––
FC/MC/PC43B3X 24 19 15 5 ––
FC/MC/PC43C3X 24 19 15 5 ––
FC/MC/PC48C3X 40 32 15 17 16 –
FC/MC/PC48D3X 40 32 27 17 16 –
FC/MC/PC60D3X –––17 16 0
FC/MC62D3X –––25 26 18
UC24A3X 8 –––––
UC24B3X 8 –––––
UC30A3X 8 4 ––––
UC30B3X 8 4 ––––
UC36A3X ––––––
UC36B3X ––––––
UC36C3X ––––––
UC42B3X ––––––
UC42C3X ––––––
UC48C3X ––––––
UC48D3X ––––––
UC60C3X ––12 –––
UC60D3X ––12 –––
HC18A3X ––––––
HC30A3X 10 –––––
HC36B3X 16 11 8 –––
HC42C3X 25 19 15 6 ––
HC60D3X –––0 0 0
HD24*3X 16 –––––
HD36*3X 18 –––––
HD48*3X 51 42 36 24 25 –
HD60*3X ––––24 –
AHP18B3X ––––––
AHP24B3X 3 –––––
AHP30B3X 16 ––––
AHP36C3X –19 15 –––
362564-UTD-B-0708
Johnson Controls Unitary Products 3
R-410A SYSTEM CHARGING PROCEDURE
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-
connecting line tubing.
2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.
3. Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electri-
cal Data Table.
4. For TXV match charge weight needs to be weighed in for specififc coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaporator + adder for line set.
AHP42C3X ––––––
AHP/SHP60D3X ––––1 –
AV24B3X 3 –––––
AV36C3X 25 19 15 –––
AV/SV48D3X ––9 0 1 –
AV/SV60D3X –––0 1 0
F4FP024 0 –––––
F4FP030 3 0 ––––
F4FP036 –8 5 –––
F4FP040 –12 8 –––
F4FP042 ––8 0 ––
F4FP045 ––9 2 ––
F5FP048 ––20 10 11 –
F5FP060 ––20 10 11 –
F4FV060 ––9 10 1 –
FOOTNOTES:
1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
2. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
3. A TXV kit must be used with these coils to obtain system performance. Note: If a TXV is factory installed on the coil, it must be replaced
with the listed TXV
4. Refer to Technical Guide for actual system performance and matches.
Additional R-410A Charge / Orifice Size for Various Matched Systems (Continued)
Outdoor Unit TCGF24S41S1 TCGF30S41S1 TCGF36S41S1 TCGF42S41S1 TCGF48S41S1 TCGF60S41S1
Required Orifice or TXV 11TVM902 1TVM903 1TVM903 1TVM903 1TVM905 1TVM906
Factory Charge, lbs-oz 3 - 2 3 - 7 3 - 10 4 - 4 4 - 9 5 - 9
Indoor Coil2,3,4 Additional Charge, Oz
See Cautionbelow
See Cautionbelow
See Cautionbelow
See Cautionbelow
See Cautionbelow
See Cautionbelow
See Cautionbelow
See Cautionbelow
See Cautionbelow
If the F*FP Air Handler used has a with a factory installed R-22 TXV it MUST BE CHANGED OUT to a R-410A TXV or a orifice for proper operation.
If the TXV is not changed out system damage will occur.
Subject to change without notice. Printed in U.S.A. 362564-UTD-B-0708
Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 362564-UTD-A-0608
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069