COMPRESSOR UNIT OIL
DO NOT MIX OILS of different
brands, manufacturers, or types.
Mixing of oils may cause excessive
oil foaming, nuisance oil level cutouts, oil pressure loss,
gas or oil leakage and catastrophic compressor failure.
NOTE: The Frick oil charge shipped with the unit is the
best suited lubricant for the conditions specied at
the time of purchase. If there is any doubt due to the
refrigerant, operating pressures, or temperatures, refer
to Frick Oil publication 160-802 spc for guidance.
Johnson Controls-Frick.
EVACUATION
CHARGING REFRIGERANT
TechnicalData
Never leave the unit unattended
during the rst 60 minutes following
start-up.
DRAINING REFRIGERANT
Check that the vessel is large enough
to hold the entire charge without
being overlled and that it is made
for the particular refrigerant used. DO NOT charge the
vessel beyond 90% liquid volume .
Open
SYSTEM PUMPDOWN