M9204-Bxx-2(Z) Series On/Off Electric Spring Return Actuators Installation Guide
11
Technical specifications
M9204-Bxx-2(Z) Series On/Off Electric Spring Return Actuators (Part 1 of 2 )
Power
requirements
-BGx-2 models AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety
Extra-Low Voltage (SELV) (Europe), 5 VA running, 1.6 VA holding position
DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe),
2.8 W running, 0.8 W holding position
Minimum transformer size: 6 VA per actuator
-BUx-2 models AC 100 to 240 V (AC 85 V to 264 V) at 50/60 Hz: 0.06 A running, 0.02 A
holding position
-BUx-2Z models AC 100 to 240 V (AC 85 V to 264 V) at 50/60 Hz: 0.08 A running, 0.02 A
holding position
Auxiliary switch
rating
-xxB models One single-pole, double-throw (SPDT), double-insulated switch with silver
contacts:
AC 24 V, 50 VA pilot duty
AC 120 V, 5.8 A resistive, 1/4 hp, 275 VA pilot duty
AC 240 V, 5.0 A resistive, 1/4 hp, 275 VA pilot duty
Spring return Direction is selectable with mounting position of actuator:
Actuator side A is away from damper or valve: CCW spring return
Actuator side B is away from damper or valve: CW spring return
Rated torque Power on (running) 35 lb·in. (4 N·m) all operating temperatures
Power off (spring
returning)
35 lb·in. (4 N·m) all operating temperatures
Rotation range Maximum full stroke: 95°
Adjustable stop: 35 to 95° maximum position
Rotation time
for 90 degrees of
travel
Power on (running)
-Bxx-2 models
53 to 71 seconds for 0 to 35 lb·in. (4 N·m) load, at room temperature
60 seconds nominal at full rated load (0.25 rpm)
Power on (running)
-BUx-2Z models
24 to 28 seconds for 0 to 35 lb·in. (4 N·m) load, at room temperature
27 seconds nominal at full rated load (0.5 rpm)
Power off (spring
returning)
19 to 23 seconds for 0 to 35 lb·in. (4 N·m) load, at room temperature
22 seconds nominal at full rated load
28 seconds maximum with 35 lb·in. (4 N·m) load at -22°F (-30°C)
Life cycles 60,000 full-stroke cycles with 35 lb·in. (4 N·m) load
Audible noise
rating
Power on (running)
-Bxx-2 models
<36 dBA at 35 lb·in. (4 N·m) load, at a distance of 39-13/32 in. (1 m)
Power on (running)
-BUx-2Z models
<45 dBA at 35 lb·in. (4 N·m) load, at a distance of 39-13/32 in. (1 m)
Power on (holding) <20 dBA at a distance of 39-13/32 in. (1 m)
Power off (spring
returning)
<51 dBA at 35 lb·in. (4 N·m) load, at a distance of 39-13/32 in. (1 m)
Electrical
connections
Actuator
(all models)
48 in. (1.2 m) UL 758 type AWM halogen-free cable with 18 AWG (0.85 mm²)
conductors and 0.25 in. (6 mm) ferrule ends
Auxiliary switch
(-xxB models)
48 in. (1.2 m) UL 758 type AWM halogen-free cable with 18 AWG (0.85 mm²)
conductors and 0.25 in. (6 mm) ferrule ends
Conduit connections Integral 1/2 in. (13 mm) threaded conduit connector(s)
Mechanical
connections
Round shafts Range of sizes: 1/4 to 1/2 in. (6 to 12 mm)
Square shafts Range of sizes: 1/4 to 5/16 in. (6 to 8 mm)
Enclosure rating NEMA 2 (IP54) for all mounting orientations
Ambient conditions Standard operating -22 to 140°F (-30 to 60°C); 90% RH maximum, noncondensing
Storage -40 to 185°F (-40 to 85°C); 95% RH maximum, noncondensing