Quick Start Commissioning Guide VFD66xxx-2 Series
Issue Date July 15, 2011
© 2011 Johnson Controls, Inc. 1
Part No. 24-10511-112, Rev. —www.johnsoncontrols.com
VFD66 Series Condenser Fan Speed Controls
Electrical Connections
Optional
Ground
Connection
Fuses
FIG:trmnl_cnnctns
Ground Connection
Terminals (For Power
and Motor Ground) Supply
Ground
TB2
L3/T
L2/S
L1/R
T1/U
T2/V
T3/W
Mains Supply
Figure 1: VFD66xxx-2
Power Terminal Connections
A: Alarm
B: Alarm
1: +5V Output
2: Analog Input 1
3: Analog Input 2
FIG:cntrl_cnnctns
TB1 4: 0V Common
Figure 2: VFD66xxx-2
Control Connections
Manual Operation
Operating the VFD66 Control from the Keypad
VFD66xxx-1 Setup
The speed is controlled with P1 (P2 is not used).
J2 = On, J3 = On, and J7 = On or Off.
VFD66xxx-2 Setup
Set parameter 05 to PAd (manual input mode).
Press the green button on the keyboard to run;
press the red button to stop.
Use the up arrow key to increase the speed; use
the down arrow key to decrease the speed.
Note: If you cycle the power, the VFD66xxx-2 stops
and you must press the green button again.
2VFD66 Series Condenser Fan Speed Controls Quick Start Commissioning Guide
Operating the VFD66 Control with a P35 Pressure Transducer or Any 0 to 5 VDC Signal
VFD66xxx-1 Setup
J2 = On, J3 = Off, and J7 = On.
P1 = minimum speed.
P2 = minimum speed maintain (stop or hold).
VFD66xxx-2 Setup
Set parameter 05 to Std (standard input mode;
factory default setting).
Set parameter 65 to 5V (factory default setting).
Set parameter 67 for the desired minimum speed
(factory default setting is 0 Hz).
Set parameter 64 for either stop (factory default
setting; motor stops below the minimum speed
setting) or HOLd (motor idles), to obtain the
desired action at the minimum speed point.
Operating the VFD66 Control with a C450 Control Module or Any 0 to 10 VDC Signal
VFD66xxx-1 Setup
J2 = On, J3 = Off, and J7 = Off. VFD66xxx-2 Setup
Set parameter 05 to Std (factory default setting).
Set parameter 65 to 10V.
Set parameter 67 for the desired minimum speed
(factory default setting is 0 Hz).
Set parameter 64 for either stop (factory default
setting) or HOLd, to obtain the desired action at
the minimum speed point.
Operating the VFD66 Control with a Ratiometric P499 Series Electronic Pressure Transducer
VFD66xxx-1 Setup
J2 = Off, J3 = On or Off, and J7 = On or Off.
P1 = setpoint.
P2 = proportional band.
VFD66xxx-2 Setup
Set parameter 05 to EPt (electronic pressure
transducer input mode).
Set parameter 65 to 5V (factory default setting) for
ratiometric sensors; set parameter 65 to 10V for
0 to 10 VDC sensors.
Set parameter 61 for the desired setpoint. This
setting is calculated using the following equation:
)
Max.Pressure Rating ofSensor
(
10 + 80 x Desired Pressure Setpoint
Example: If a 0 to 500 psig sensor is used and the
desired setpoint is 275 psig, then the setting for
parameter 61 is 10 + (80 x 275/500) or 54.
Set parameter 62 for the desired proportional band
of the control. This setting is calculated using the
following equation:
]
Max.Pressure Rating of Sensor
[
80 x (Pressure Setpoint – Min. Req. Pressure)
Example: If a 0 to 750 psig sensor with a setpoint
of 500 psig and a minimum required pressure of
410 psig is used, then the setting for parameter 62
is 80 x [(500 –410)/750] or 9.6.
VFD66 Series Condenser Fan Speed Controls Quick Start Commissioning Guide 3
Changing Acceleration and Deceleration Parameters on the VFD66 Control
VFD66xxx-1 Setup
If J4 = On, then the acceleration and deceleration
rate is 5 seconds (this value is in seconds/60Hz).
If J4 = Off, then the acceleration and deceleration
rate is 30 seconds (this value is in
seconds/60 Hz).
VFD66xxx-2 Setup
Set parameter 03 for acceleration
(in seconds/100 Hz). This setting is calculated
using the following equation:
60
Desired Acceleration Rate x 100
Example: A setting of 8.3 (in seconds/100 Hz)
equals a 5 second acceleration rate from
0 to 60 Hz.
Set parameter 04 for deceleration
(in seconds/100 Hz). This setting is calculated
using the following equation:
60
Desired Deceleration Rate x 100
Example: A setting of 50 (in seconds/100 Hz)
equals a 30 second deceleration rate from
0 to 60 Hz.
Note: The settings for the acceleration and
deceleration parameters are adjustable from
0 to 3,200 seconds (this range is in seconds/100 Hz).
Selecting Single or Dual Sensors (High Signal Select) on the VFD66 Control
VFD66xxx-1 Setup
If J8 = On, then dual sensors are configured with
high signal select.
If J8 = Off, then single sensor is configured.
VFD66xxx-2 Setup
Set parameter 63 to 1InP (factory default setting)
for single sensor configuration.
Set parameter 63 to 2InP for dual sensor
configuration with high signal select.
Setting the Motor Rated Frequency on the VFD66 Control
VFD66xxx-1 Setup
If J9 = On, then the motor rated frequency is
50 Hz.
If J9 = Off, then the motor rated frequency is
60 Hz.
VFD66xxx-2 Setup
Set parameter 39 to the motor rated frequency
(factory default setting is 60 Hz).
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Johnson Controls/PENN® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2011 Johnson Controls, Inc.

Other manuals for VFD66 Series

3

This manual suits for next models

2

Other Johnson Controls Controllers manuals

Johnson Controls M9220-Bxx-3 User manual

Johnson Controls

Johnson Controls M9220-Bxx-3 User manual

Johnson Controls P77 Series User manual

Johnson Controls

Johnson Controls P77 Series User manual

Johnson Controls TEC3620 Series User manual

Johnson Controls

Johnson Controls TEC3620 Series User manual

Johnson Controls MP8 20 Series User manual

Johnson Controls

Johnson Controls MP8 20 Series User manual

Johnson Controls EDA-8100 Assembly instructions

Johnson Controls

Johnson Controls EDA-8100 Assembly instructions

Johnson Controls FW-08 User manual

Johnson Controls

Johnson Controls FW-08 User manual

Johnson Controls M9308-A Z Series User manual

Johnson Controls

Johnson Controls M9308-A Z Series User manual

Johnson Controls PENN ACT2 Service manual

Johnson Controls

Johnson Controls PENN ACT2 Service manual

Johnson Controls LN Series User manual

Johnson Controls

Johnson Controls LN Series User manual

Johnson Controls VA9104-AGA-1S User manual

Johnson Controls

Johnson Controls VA9104-AGA-1S User manual

Johnson Controls MR12DR230-1C User manual

Johnson Controls

Johnson Controls MR12DR230-1C User manual

Johnson Controls PENN P70 Series Manual

Johnson Controls

Johnson Controls PENN P70 Series Manual

Johnson Controls TEC3000 Series User manual

Johnson Controls

Johnson Controls TEC3000 Series User manual

Johnson Controls VA-8052 User manual

Johnson Controls

Johnson Controls VA-8052 User manual

Johnson Controls DWUNI User manual

Johnson Controls

Johnson Controls DWUNI User manual

Johnson Controls EDA-8102 Assembly instructions

Johnson Controls

Johnson Controls EDA-8102 Assembly instructions

Johnson Controls M9203-AG-2 Series User manual

Johnson Controls

Johnson Controls M9203-AG-2 Series User manual

Johnson Controls VMA18 Series User manual

Johnson Controls

Johnson Controls VMA18 Series User manual

Johnson Controls VMA1930 User manual

Johnson Controls

Johnson Controls VMA1930 User manual

Johnson Controls FX-PCV1656 User manual

Johnson Controls

Johnson Controls FX-PCV1656 User manual

Johnson Controls BMMS-1P Original operating instructions

Johnson Controls

Johnson Controls BMMS-1P Original operating instructions

Johnson Controls VMA18 Series User manual

Johnson Controls

Johnson Controls VMA18 Series User manual

Johnson Controls FEC1611 User manual

Johnson Controls

Johnson Controls FEC1611 User manual

Johnson Controls PENN ACT2 Service manual

Johnson Controls

Johnson Controls PENN ACT2 Service manual

Popular Controllers manuals by other brands

Emerson Fisher 1066 instruction manual

Emerson

Emerson Fisher 1066 instruction manual

EWS ES2030 CV instruction manual

EWS

EWS ES2030 CV instruction manual

Danfoss ECL Comfort 301 quick guide

Danfoss

Danfoss ECL Comfort 301 quick guide

Chziri ZJR1 Series user manual

Chziri

Chziri ZJR1 Series user manual

Honeywell WEB-600E manual

Honeywell

Honeywell WEB-600E manual

DROPSA ADVANCED LUBRICATION CONTROLLER INSTRUCTION AND PRODUCT DATA SHEET

DROPSA

DROPSA ADVANCED LUBRICATION CONTROLLER INSTRUCTION AND PRODUCT DATA SHEET

Siemens REV13 series instruction manual

Siemens

Siemens REV13 series instruction manual

Flowserve Limitorque LTQ008 User instructions

Flowserve

Flowserve Limitorque LTQ008 User instructions

BIFFI ALGAS-QA Series Instruction and operation manual

BIFFI

BIFFI ALGAS-QA Series Instruction and operation manual

Rinnai MC-100V Operation & installation manual

Rinnai

Rinnai MC-100V Operation & installation manual

Timewave PK-232 MBX operating manual

Timewave

Timewave PK-232 MBX operating manual

Rane DC24 Operator's manual

Rane

Rane DC24 Operator's manual

GE PACSystems* RX3i user manual

GE

GE PACSystems* RX3i user manual

HTW HTW-KJR86A1E Installation and operation manual

HTW

HTW HTW-KJR86A1E Installation and operation manual

UIrobot UIM241 Series user manual

UIrobot

UIrobot UIM241 Series user manual

Mitsubishi AL2 Series Programming manual

Mitsubishi

Mitsubishi AL2 Series Programming manual

Panasonic AKHRP900P - CAMERA CONTROLLER HC Service manual

Panasonic

Panasonic AKHRP900P - CAMERA CONTROLLER HC Service manual

Siemens SIPART DR22 manual

Siemens

Siemens SIPART DR22 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.