
TFP223
Page 3 of 4
Installation
The Series EC-8 Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm).
A leak tight 3/4 in. NPT sprinkler joint
should be obtained with a torque of
10 ft-lb to 20 ft-lb (13,4 N·m to 26,8
N·m). Higher levels of torque may
distort the sprinkler inlet with conse-
quent leakage or impairment of the
sprinkler.
Do not attempt to compensate for
insufcient adjustment of an escutch-
eon plate by under-or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler tting to suit.
Step 1. The sprinkler must be installed
with the deector parallel to the mount-
ing surface. Pendent sprinklers must
be installed in the pendent position.
Step 2. After installing the style 30 or
40 mounting plate (or other escutch-
eon, as applicable) over the sprinkler
pipe threads, and with pipe thread
sealant applied to the pipe threads,
hand tighten the sprinkler into the
sprinkler tting.
Step 3. Wrench tighten pendent sprin-
klers using only the W-Type 3 (End A)
Sprinkler Wrench. Wrench tighten the
recessed pendent sprinklers using
only the W-Type 23 Sprinkler Wrench.
The wrench recess of the applicable
sprinkler wrench as shown in Figures
4 and 5 is to be applied to the sprinkler
wrench ats as shown in Figure 1.
Care and
Maintenance
The Series EC-8 Sprinklers must be
maintained and serviced in accordance
with this section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system that
it controls, permission to shut down the
affected re protection systems must
be obtained from the proper authorities
and all personnel who may be affected
by this action must be notied.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. For informa-
tion about replacing a sprinkler, see the
Installation Section.)
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant coated sprin-
klers, after the installation has been
completed, to verify the integrity of
the corrosion resistant coating. There-
after, annual inspections according
to NFPA 25 should sufce; however,
Area Style 135°F (57°C) 155°F (68°C)
16 x 16 Pendent QR QR
16 x 16 Style 30 Recessed QR QR
16 x 16 Style 40 Recessed QR QR
18 x 18 Pendent QR QR
18 x 18 Style 30 Recessed QR SR
18 x 18 Style 40 Recessed QR SR
20 x 20 Pendent QR SR
20 x 20 Style 30 Recessed QR SR
20 x 20 Style 40 Recessed SR SR
NOTES
• QR: Quick Response
Area Style 135°F (57°C) 155°F (68°C)
16 x 16 Pendent QR QR
16 x 16 Style 30 Recessed QR N/A
16 x 16 Style 40 Recessed N/A N/A
18 x 18 Pendent QR QR
18 x 18 Style 30 Recessed QR N/A
18 x 18 Style 40 Recessed N/A N/A
20 x 20 Pendent QR QR
20 x 20 Style 30 Recessed QR N/A
20 x 20 Style 40 Recessed N/A N/A
NOTES
• QR: Quick Response
• SR: Standard Response
Description Area gpm psi
TY4232 (K=8.0)
Pendent
16 x 16 26 10.6
18 x 18 33 17.0
20 x 20 40 25.0
NOTES
• 1 ft = 0.3048 m
• 1 gpm = 3.785 Lpm
• 1 psi = 0.06895 bar
• 1 gpm/ft2= 40.74 mm/min
TABLE B
SENSITIVITY RATING FOR UL AND C-UL LISTING
OF SERIES EC-8 SPRINKLERS
TABLE C
SENSITIVITY RATING FOR FM APPROVAL
OF SERIES EC-8 SPRINKLERS
TABLE D
FLOW CRITERIA FOR UL AND C-UL LISTING
OF SERIES EC-8 SPRINKLERS