that is not securely attached, indicates
the sprinkler is positioned at a distance
from the mounting surface greater than
is described if Figure 3. A Cover Plate
Assembly fully engaged on the sprin-
kler body while the retainer flange is
not in contact with the wall indicates
the sprinkler is positioned at a distance
from the mounting surface lesser than
described in Figure 3. If either condi-
tion is encountered when attempting
to install the Cover Plate Assembly, the
sprinkler fitting must me repositioned.
Care and
Maintenance
The Series LFII Concealed Horizontal
Sidewall Sprinkler must be maintained
and serviced in accordance with this
section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION, for example, NFPA 25,
in addition to the standards of any
authorities having jurisdiction. Contact
the installing contractor or sprinkler
manufacturer regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
When properly installed, there is a
nominal 5/32 in. (4,0 mm) air gap
between the lip and the Cover Plate
and the wall, as shown in Figure 3.
This air gap is necessary for the proper
operation of the sprinkler. If the wall
is to be repainted after installation of
the sprinkler, care must be exercised
to ensure that the new paint does not
seal off any of the air gap.
Factory painted cover plates must not
be repainted. They should be replaced
if necessary, by factory painted units.
Non-factory applies paints may
adversely delay or prevent sprinkler
operation in the event of a fire.
If removal of the Cover Plate is neces-
sary relative to the enclosure, be con-
scious not to be too forceful, where
separation may result.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other- wise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced.
If a sprinkler must be removed, do not
reinstall it or a replacement without
reinstalling the Cover Plate Assembly.
If a Cover Plate Assembly becomes
dislodged during service, replace it
immediately.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied or over heated sprinklers must be
replaced.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced.
If a sprinkler must be removed, do not
reinstall it or a replacement without
reinstalling the Cover Plate Assembly.
If a Cover Plate Assembly becomes
dislodged during service, replace it
immediately.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assembly
Specify: Series LFII (TY2324), K=4.2,
Residential Horizontal Sidewall Sprin-
kler, without Cover Plate Assembly,
P/N 50-520 -1-160
Note: Sprinkler and Cover Plates are
separately ordered. See below for
Cover Plate ordering information.
Cover Plate Assembly
(Separately Ordered)
Specify: Series LFII Concealed Sprin-
kler Cover Plate Assembly, (specify
finish), P/N (specify):
Ivo r y ( R A L10 15 ) . . . . . . . . . . . . . . .56-204-0 -135
Beige (RAL1001) . . . . . . . . . . . . . . 56-204-2-135
Pure White (RAL9010)* . . . . . . . . . 56-204-3-135
Signal White (RAL9003)** . . . . . . .56-204-4-135
Grey White (RAL9002) . . . . . . . . . . 56-204-5-135
Brown (RAL8028). . . . . . . . . . . . . .56-204-6-135
Black (RAL9005) . . . . . . . . . . . . . . 56 -204-7-135
Brushed Brass ................56-204-8-135
Brushed Chrome . . . . . . . . . . . . . .56-204-9-135
Custom Paint .................56-204-X-135
*Eastern Hemisphere sales only
**Previously known as Bright White
Note: All Custom Cover Plates are
painted using SHERWIN-WILLIAMS
Interior Latex Paint. Contact Johnson
Controls Customer Service with any
questions related to custom orders.
Sprinkler Wrench
Specify: W-Type 37 Sprinkler Wrench,
P/N 56-320-1-015
Pipe Guide Bracket
Pipe Guide Bracket accessory for
sprinkler installation adjacent to
framing member such as 2 x 4 within
wall structure, includes mounting
screws.
Specify: Pipe Guide Bracket,
P/ N 91- 52 0 -115