manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Johnson Controls
  6. •
  7. Irrigation System
  8. •
  9. Johnson Controls tyco TY-FRL Series User manual

Johnson Controls tyco TY-FRL Series User manual

Series TY-FRL – 5.6 K-factor
Horizontal Sidewall Sprinkler
Quick Response, Standard Coverage
Page 1 of 4 AUGUST 2018 TFP140
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
TYCO Series TY-FRL 5.6K Horizon-
tal Sidewall Sprinklers (HSW), Quick
Response, Standard Coverage are sol-
der-type spray sprinklers designed for
use in light and ordinary hazard com-
mercial occupancies such as banks,
hotels, shopping malls, offices, etc.
They are designed for installation along
a wall or the side of a beam and just
beneath a smooth ceiling. Horizontal
sidewall sprinklers are commonly used
instead of pendent or upright sprin-
klers due to aesthetics or building con-
struction considerations, where piping
across the ceiling is not desirable.
NOTICE
The Series TY-FRL Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association (NFPA), in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers (SINs)
TY3321 – HSW 5.6K, 1/2 in. NPT
TY3321 is a re-designation for Star SIN
S1878 and Gem SIN G8946.
Technical
Data
Approvals
UL and C-UL Listed
FM and NYC Approved
(Refer to Table A for complete approval
information.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6 gpm/psi½(80,6 lpm/bar½)
Temperature Ratings
Refer to Table A
Finishes
Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Link Assembly. . . . . . . . . . . . . . . . . . . . . . Nickel
Ejection Spring . . . . . . . . . . . . . . . . . . INCONEL
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TEFLON
Operation
The fusible link (heat collector) assem-
bly is comprised of two halves that
are joined together by a thin layer of
solder. When the rated temperature is
reached, the solder melts and the two
link halves separate, allowing the sprin-
kler to operate.
Design
Criteria
TYCO Series TY-FRL 5.6K HSW Sprin-
klers, Quick Response, Standard
Coverage are intended for fire pro-
tection systems designed in accor-
dance with the standard installation
rules recognized by the applicable
listing or approval agency (e.g., UL
Listing is based on NFPA 13 require-
ments); however, the minimum dis-
tance between sprinklers to prevent
cold soldering is 8 ft (2,4 m). The
Series TY-FRL HSW Sprinklers
must be installed with a deflector-
to-ceiling distance of 4 in. to 6 in.
(100 mm to 150 mm). To meet this
requirement the centerline of the
sprinkler waterway must be located
4-5/16 in. to 6-5/16 in. (110 mm to
160 mm) below the ceiling. Installation
of the Series TY-FRL HSW Sprinklers
in recessed escutcheons will void all
manufacturer’s warranties, as well as
possibly void the sprinkler’s approvals
and/or listings.
TFP140
Page 2 of 4
Installation
TYCO Series TY-FRL 5.6K HSW Sprin-
klers, Quick Response, Standard Cov-
erage must be installed in accordance
with this section.
General Instructions
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained with a torque of 7 to
14 lb-ft. (9,5 to 19,0 N·m). A maximum
of 21 lb-ft. (28,5 N·m) of torque may be
used to install sprinklers with 1/2 NPT
connections. Higher levels of torque
may distort the sprinkler inlet and
cause leakage or impairment of the
sprinkler.
Do not attempt to make-up for insuf-
ficient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
Horizontal Sidewall Sprinklers
Note: The Series TY-FRL HSW Sprin-
klers must be installed with their cen-
terline of waterway parallel to the
ceiling and perpendicular to the back
wall surface. The word “TOP” on the
deflector must face upwards toward
the ceiling.
Step 1. After installing an escutcheon
(as applicable) over the sprinkler pipe
threads and with pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 2. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
9 Sprinkler Wrench (Ref. Figure 2).
With reference to Figure 1, the W-Type
9 Sprinkler Wrench is to be applied to
the wrench area.
K
FACTOR SPRINKLER
TYPE TEMPERATURE
RATING FRAME
COLOR CODE
SPRINKLER FINISH
NATURAL
BRASS CHROME
PLATED
5.6
1/2 in. NPT
HORIZONTAL
SIDEWALL
(TY3321)
165°F (74°C) Unpainted
1, 2, 3, 4
212°F (100°C) White
Notes:
1. UL Listed for light or ordinary hazard occupancies as Quick Response sprinklers
2. C-UL Listed for light or ordinary hazard occupancies as Quick Response sprinklers
3. FM Approved for light hazard occupancies Quick Response sprinklers
4. Approved by the City of New York under MEA 112-04-E
WRENCH
RECESS
2
1
4
7
63
5
8
ISO 7-1 can be provided on
Pipe thread connections per
Temperature rating is indicatedButton
Strut
Deector
Frame
Assembly
Link
Hook
Ejection
Spring
Seal on Deector
special request
*
**
*
**
*
WATERWAY
OF SPRINKLER
CENTERLINE
SURFACE
PLATE SEATING
WALL
TOP
(15,9 mm)
5/8"
NOMINAL
5/16" (7,9 mm)
DEFLECTOR
BOSS
(41,3 mm)
DEFLECTOR
1-5/8"
3.5°
2-11/16"
(68,3 mm)
7/16" (11,1 mm)
NOMINAL MAKE-IN
(50,8 mm)
2"
WRENCH
AREA
6
34527
WRENCH
FLANGES
1/2" NPT
81
-
-
-
-
--
-
-
FIGURE 1
QUICK RESPONSE
SERIES TY-FRL (TY3321) HORIZONTAL SIDEWALL SPRINKLER
5.6 K-FACTOR, 1/2 INCH NPT
FIGURE 2
W-T YPE 9
SPRINKLER WRENCH
TABLE A
LABORATORY LISTINGS AND APPROVALS
TFP140
Page 3 of 4
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: Series TY-FRL 5.6K Quick
Response Horizontal Sidewall Sprin-
klers, SIN TY3321, (specify) temperature
rating, (specify) finish, P/N (specify from
Table B)
Sprinkler Wrench
Specify: W-Type 9 Sprinkler Wrench,
P/N 56-000-1-849
Care and
Maintenance
TYCO Series TY-FRL 5.6K HSW Sprin-
klers, Quick Response, Standard Cov-
erage must be maintained and serviced
in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied or over-heated sprinklers must be
replaced.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprinklers
damaged by dropping, striking, wrench
twist/slippage, or the like, must be re
placed.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
P/N 58 — XXX — X — XXX
SPRINKLER
FINISH
1NATURAL
BRASS
9CHROME
PL ATED
SIN
946 5.6K HSW (1/2 in. NPT) TY3321
TEMPERATURE
RATING
165 165°F ( 74°C)
212 212°F (100°C)
TABLE B
SERIES TY-FRL HORIZONTAL SIDEWALL SPRINKLERS, QUICK RESPONSE
PART NUMBER SELECTION
TFP140
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL and INCONEL are registered trademarks of Special Metals Corporation;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

This manual suits for next models

1

Other Johnson Controls Irrigation System manuals

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco TY-L Series User manual

Johnson Controls

Johnson Controls tyco TY-L Series User manual

Johnson Controls tyco CHEC User manual

Johnson Controls

Johnson Controls tyco CHEC User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls tyco RAVEN User manual

Johnson Controls

Johnson Controls tyco RAVEN User manual

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls C-9500 User manual

Johnson Controls

Johnson Controls C-9500 User manual

Johnson Controls tyco TY4334 Operating and maintenance instructions

Johnson Controls

Johnson Controls tyco TY4334 Operating and maintenance instructions

Johnson Controls tyco DS-1 Series User manual

Johnson Controls

Johnson Controls tyco DS-1 Series User manual

Johnson Controls tyco CC3 User manual

Johnson Controls

Johnson Controls tyco CC3 User manual

Johnson Controls tyco DS-1 Series User manual

Johnson Controls

Johnson Controls tyco DS-1 Series User manual

Johnson Controls JWS-3 User manual

Johnson Controls

Johnson Controls JWS-3 User manual

Johnson Controls tyco CC3 User manual

Johnson Controls

Johnson Controls tyco CC3 User manual

Johnson Controls TY5811 User manual

Johnson Controls

Johnson Controls TY5811 User manual

Johnson Controls Tyco ULF AM6 User manual

Johnson Controls

Johnson Controls Tyco ULF AM6 User manual

Johnson Controls tyco DSB-2 User manual

Johnson Controls

Johnson Controls tyco DSB-2 User manual

Johnson Controls tyco WS User manual

Johnson Controls

Johnson Controls tyco WS User manual

Johnson Controls tyco AQUAMIST ULF AM15 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM15 User manual

Johnson Controls tyco ESFR-25 User manual

Johnson Controls

Johnson Controls tyco ESFR-25 User manual

Johnson Controls tyco TY3334 User manual

Johnson Controls

Johnson Controls tyco TY3334 User manual

Popular Irrigation System manuals by other brands

Tyco G2 manual

Tyco

Tyco G2 manual

Tyco Fire Product STAR S160E manual

Tyco Fire Product

Tyco Fire Product STAR S160E manual

Tyco K17-231 manual

Tyco

Tyco K17-231 manual

claber POP-UP 90 user manual

claber

claber POP-UP 90 user manual

Coopers Pk 6 G346 Instructions for use

Coopers

Coopers Pk 6 G346 Instructions for use

Tyco ESFR-34 manual

Tyco

Tyco ESFR-34 manual

Mondo Verde IRA03 quick start guide

Mondo Verde

Mondo Verde IRA03 quick start guide

Reliable G5-56 Dry instruction manual

Reliable

Reliable G5-56 Dry instruction manual

Tyco F08 FIP Operator's manual

Tyco

Tyco F08 FIP Operator's manual

Globe GL Series quick start guide

Globe

Globe GL Series quick start guide

Brandson Equipment 304257/20191212NB128 user manual

Brandson Equipment

Brandson Equipment 304257/20191212NB128 user manual

Autopot 80Pot XL Set-up guidelines

Autopot

Autopot 80Pot XL Set-up guidelines

Solem LoRa LR-BST-25 installation guide

Solem

Solem LoRa LR-BST-25 installation guide

Hunter I-25 Installation

Hunter

Hunter I-25 Installation

Hunter PRO-C Hydrawise Software/App Owner's Manual

Hunter

Hunter PRO-C Hydrawise Software/App Owner's Manual

Orbit 56448 instructions

Orbit

Orbit 56448 instructions

Tyco Fire Product CENTRAL ELO-231TM instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231TM instruction manual

AQUAvalve 6Pot XL Set-up guidelines

AQUAvalve

AQUAvalve 6Pot XL Set-up guidelines

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.