Model TY720
16.8 K-factor Pendent Sprinkler
Electronic Control
Page 1 of 2 AUGUST 2018 TFP325
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Model TY720 Pendent
Sprinkler is an electronically controlled
sprinkler having a nominal K-factor of
16.8 (Ref. Figure 1).
The TY720 sprinkler is designed as an
integral component of the Electronic
Sprinkler System for Storage Applica-
tions, a performance-based system
addressing high-challenging high pile
storage fire hazards. For more informa-
tion about the sprinkler system and the
system components, refer to technical
data sheet TFP360.
In place of a traditional heat-sensitive
glass bulb or solder element, the TY720
sprinkler features an electronic linear
actuator and tensile link with hook and
strut arrangement holding a button and
seal against the waterway. A Simplex
Sprinkler Control Heat Sensor paired
with the TY720 sprinkler is connected
directly to the actuator and is in con-
tinuous communication with a Simplex
4100ES Suppression Release Panel.
The panel software algorithm analyzes
information from heat sensors in mul-
tiple locations and selects the optimal
response in a fire event. A voltage is
then sent from an algorithm-selected
heat sensor to its companion TY720
sprinkler, operating the actuator and
breaking the tensile link, allowing
waterflow from the sprinkler.
NOTICE
The TY720 Sprinkler described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa-
tion, in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY720
Technical
Data
Approvals
UL Listed
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 in. NPT
Discharge Coefficient
K=16.8 GPM/psi½(241,9 LPM/bar½)
Finish
Natural Brass
Physical Characteristics
Frame .............................Brass
Deflector. . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
Compression Screw . . . . . . . . . . Stainless Steel
Hook.............................MONEL
Strut . . . . . . . . . . . . . . . . . . . . . . . . . . . . .MONEL
Tensile Link . . . . . . . . . . . . . . . . . . . . . . . Copper
Button.............................Brass
Sealing Assembly . Beryllium Nickel w/TEFLON
Ejection Spring. . . . . . . . . . . . . . . . . . . INCONEL
Electrical Actuator . . . . . . . . . . . . . . . . . . . Brass
Electrical Actuator Housing.....ABS/PC Resin
Temperature Rating
Temperature rating is determined by
the panel and heat sensor paired with
the TY720 sprinkler.
For more information, refer to the Elec-
tronic Sprinkler System for Storage
Applications data sheet (document
number TFP360).
Installation
Install the Model TY720 Pendent Sprin-
kler in accordance with this section.
General Instructions
Avoid damage to the actuator and
tensile link during installation. Grasp
the sprinkler only by the protec-
tor and frame wrench flats when
hand-tightening.
A leak-tight 3/4 in. NPT sprinkler joint
should be obtained by applying pipe-
thread sealant to the sprinkler threads
and wrench-tightening using only the
W-Type 21 Sprinkler Wrench (Ref.
Figure 2).
Sprinkler Installation
Install the Model TY720 Pendent Sprin-
kler only in the pendent position in
accordance with the following:
Step 1. Apply pipe-thread sealant to
sprinkler threads.
Step 2. Hand-tighten sprinkler into
sprinkler fitting. Do not apply force to
the actuator and tensile link, handle
only by the protector and frame wrench
flats.
Step 3. Apply W-Type 21 Sprinkler
Wrench to sprinkler by fully seating
wrench recess on sprinkler wrench flats
(Ref. Figure 1).
Step 4. Wrench-tighten sprinkler to
obtain leak-tight joint either 1 to 1-1/2
turns beyond hand-tightened or by
applying a minimum-to-maximum
torque of 10 to 20 lb-ft (13,4 to 26,8
N∙m).
TFP325
Page 2 of 2
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL and INCONEL are registered trademarks of Special Metals Corporation;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
dures section of the Simplex 4100ES
Fire Alarm System Operator’s Manual
(Simplex document number 579-197).
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies
Specify: Model TY720, K=16.8, Elec-
tronic Control, Pendent Sprinkler,
natural brass, P/N 58-461-1-000
Sprinkler Wrench
Specify: W-Type 21 Sprinkler Wrench,
P/N 56-001-0-686
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, strik-
ing, wrench twist/slippage, or the like,
must be replaced. Also, replace any
sprinkler that has a damaged actuator,
tensile link or other operative parts.
(Ref. Installation Section.)
The owner is responsible for the
inspection, testing, and mainte-
nance of their fire protection system
and devices in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association (e.g., NFPA
25), in addition to the standards of any
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Suppression Release Panel
For information about the inspection,
test and maintenance (ITM) of the
Simplex 4100ES Suppression Release
Panel, see the System Test Proce-
NOTICE
Higher levels of torque may distort
sprinkler inlet with consequent leakage
or impairment of sprinkler.
Care and
Maintenance
TY720 Sprinklers must be maintained
and serviced in accordance with this
section.
Submit 10 samples or 1% of the total
number of installed sprinklers, which-
ever is greater, to UL for testing 5 years
after manufacturing, then again at 10
years and followed by annual testing
after the 10th year. Sampling can be
from mock-installations not connected
to the fire protection sprinkler system
but are located in the same orienta-
tion and environment as the system
sprinklers.
Components:
WRENCH
FLATS
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
Tensile Link
Compression
Ejection Spring
-
3
Screw
Button
Assembly
Sealing
-
Strut
-
-
-
-
-
Hook
9
5
6
7
4
8
-
10 Electrical
Actuator
Deector
-
2
Frame
-
1
2
3
4
6
10
1
8
5
7
9
1-7/8" (47,6 mm)
3/4" NPT
3-9/16"
(90,5 mm)
WRENCH
RECESS
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
FIGURE 1
MODEL TY720 ELECTRONIC CONTROL,
PENDENT SPRINKLER, 16.8 K-FACTOR
FIGURE 2
W-TYPE 21
SPRINKLER WRENCH

Other Johnson Controls Irrigation System manuals

Johnson Controls tyco TY2235 User manual

Johnson Controls

Johnson Controls tyco TY2235 User manual

Johnson Controls tyco LD User manual

Johnson Controls

Johnson Controls tyco LD User manual

Johnson Controls tyco AQUAMIST ULF AM28 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM28 User manual

Johnson Controls tyco CC2 User manual

Johnson Controls

Johnson Controls tyco CC2 User manual

Johnson Controls tyco DS-1 Series User manual

Johnson Controls

Johnson Controls tyco DS-1 Series User manual

Johnson Controls tyco RFII-MRI Series User manual

Johnson Controls

Johnson Controls tyco RFII-MRI Series User manual

Johnson Controls tyco LFII Series Guide

Johnson Controls

Johnson Controls tyco LFII Series Guide

Johnson Controls tyco EC-25 User manual

Johnson Controls

Johnson Controls tyco EC-25 User manual

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls tyco RAVEN User manual

Johnson Controls

Johnson Controls tyco RAVEN User manual

Johnson Controls tyco CHEC User manual

Johnson Controls

Johnson Controls tyco CHEC User manual

Johnson Controls Tyco EC-11 Series User manual

Johnson Controls

Johnson Controls Tyco EC-11 Series User manual

Johnson Controls tyco CC3 User manual

Johnson Controls

Johnson Controls tyco CC3 User manual

Johnson Controls Tyco RFIII User manual

Johnson Controls

Johnson Controls Tyco RFIII User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco TFP700 User manual

Johnson Controls

Johnson Controls tyco TFP700 User manual

Johnson Controls tyco TY-L Series User manual

Johnson Controls

Johnson Controls tyco TY-L Series User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco ULTRA K17 User manual

Johnson Controls

Johnson Controls tyco ULTRA K17 User manual

Johnson Controls tyco AQUAMIST ULF AM29 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM29 User manual

Johnson Controls SABROE SVER User manual

Johnson Controls

Johnson Controls SABROE SVER User manual

Johnson Controls tyco AQUAMIST ULF AM34 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM34 User manual

Johnson Controls CDS-2000 User manual

Johnson Controls

Johnson Controls CDS-2000 User manual

Johnson Controls tyco EC-5 Series User manual

Johnson Controls

Johnson Controls tyco EC-5 Series User manual

Popular Irrigation System manuals by other brands

Reliable SWC Bulletin

Reliable

Reliable SWC Bulletin

Tyco rapid response LFII Series quick start guide

Tyco

Tyco rapid response LFII Series quick start guide

Tyco EC-25 Operation instructions

Tyco

Tyco EC-25 Operation instructions

RedMax DA-EX850 Operator's manual

RedMax

RedMax DA-EX850 Operator's manual

Reliable G4A-300 quick start guide

Reliable

Reliable G4A-300 quick start guide

Toro TWRS user guide

Toro

Toro TWRS user guide

VONROC PS505XX Original instructions

VONROC

VONROC PS505XX Original instructions

TOOLCRAFT 1561112 operating instructions

TOOLCRAFT

TOOLCRAFT 1561112 operating instructions

Reliable F1S5-FSLO instruction manual

Reliable

Reliable F1S5-FSLO instruction manual

GEM F687 manual

GEM

GEM F687 manual

Hunter Institutional Series I-90 manual

Hunter

Hunter Institutional Series I-90 manual

GW Sprinkler Loflow K15 Series manual

GW Sprinkler

GW Sprinkler Loflow K15 Series manual

Tyco Fire Product CENTRAL 3 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL 3 instruction manual

Eden 94110EDAMZ quick start guide

Eden

Eden 94110EDAMZ quick start guide

DIG GE2050 installation instructions

DIG

DIG GE2050 installation instructions

Tyco Fire Product CENTRAL Royal Flush GB4-EC instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL Royal Flush GB4-EC instruction manual

Tyco ESFR-1 General description

Tyco

Tyco ESFR-1 General description

Task Force Tips MASTER FOAM INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Task Force Tips

Task Force Tips MASTER FOAM INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.