Johnson Controls tyco TY-FRB Series User manual

Series TY-FRB – 5.6 K-factor
Conventional (Old Style) Sprinklers
Quick Response
Page 1 of 4 AUGUST 2018 TFP667
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Series TY-FRB, 5.6 K-fac-
tor, Conventional Sprinklers, Quick
Response described in this technical
data sheet are quick response, stan-
dard coverage, decorative 3 mm glass
bulb type spray sprinklers. These sprin-
klers are intended to be installed either
pendent or upright, and in either posi-
tion, they produce a spherical water
discharge pattern with approximately
50% of the discharge directed upwards
and approximately 50% of the dis-
charge directed downwards.
Conventional sprinklers are generally
used with Ordinary and Extra High
Hazard Class Systems, as defined by
the automatic sprinkler system instal-
lation rules of the country and author-
ity having jurisdiction. The NATIONAL
FIRE PROTECTION ASSOCIATION
(NFPA) permits the use of “Old Style
Sprinklers” where special construction
features require a unique water distri-
bution; for the protection of fur vaults;
or, the replacement of similar sprinklers
that had been installed prior to 1955.
NOTICE
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the appli-
cable standards of the NATIONAL
FIRE PROTECTION ASSOCIATION, in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers (SINs)
TY363
TY3630 (LPCB Approved only)
Technical
Data
Approvals
UL and C-UL Listed
VdS Approved
LPCB Approved (TY3630 only)
Sprinklers with Polyester Finish are UL
and C-UL Listed as Corrosion-Resistant
Sprinklers.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6 GPM/psi½(80,6 LPM/bar½)
Temperature Ratings
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
Finishes
Sprinkler: Refer to Table A.
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper
Sealing Assembly ...Stainless Steel w/TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-fac-
tor, Conventional Sprinklers, Quick
Response are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing
or Approval agency (e.g., UL Listing is
based on NFPA 13 requirements). The
Series TY-FRB Conventional Sprinklers
are only for non-recessed applications.
TFP667
Page 2 of 4
Installation
The TYCO Series TY-FRB, 5.6 K-fac-
tor, Conventional Sprinklers, Quick
Response must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) to 3/32 in.
(2,4 mm) for the 286°F (141°C) tempera-
ture ratings.
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained with a torque of 7 to
14 lb-ft (9,5 to 19,0 N∙m). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Step 1. With pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 2. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 2).
With reference to Figure 1, the W-Type
6 Sprinkler Wrench is to be applied to
the wrench flats.
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-fac-
tor, Conventional Sprinklers, Quick
Response must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. Refer to the Instal-
lation section for additional information.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of the
NATIONAL FIRE PROTECTION ASSO-
CIATION (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
CROSS SECTION
SHOWN UPRIGHT
SHOWN
PENDENT
6
-Deector
5
-
4
-
Compression
Screw
Bulb
Components:
-
2
3
-
1
-
Button
Sealing
Assembly
Frame
1-3/8"
(34,9 mm)
2"
(50,8 mm)
WRENCH
FLATS
7/16" (11,1 mm)
NOMINAL
MAKE-IN
ESCUTCHEON PLATE
SEATING SURFACE
1/2"
NPT
2
1
3
*
Temperature
rating is indicated
on Deector.
*4
5
6
*
**
Pipe thread
connections per
ISO 7-1 can be
provided on
special request.
**
WRENCH RECESS
(USE ONLY
END "A")
FIGURE 1
SERIES TY-FRB CONVENTIONAL SPRINKLERS (TY363 & TY3630)
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
FIGURE 2
W-T YPE 6
SPRINKLER WRENCH
TFP667
Page 3 of 4
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and
Part Number (P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: Series TY-FRB Conventional
Sprinkler, (specify) SIN, K=5.6, Quick
Response, (specify) temperature
rating), (specify) finish, P/N (specify,
refer to Table A)
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Notes:
* Use sufx “I” for ISO 7-1 connection (e.g., 77-373-4-175-I)
** LPCB Approved Series TY-B Conventional Sprinkler as-
semblies only: Use sufx “L” for LPCB Approved assemblies
(e.g., 77-373-4-175-L or 77-373-4-175-IL for LPCB Approved
and ISO 7-1 connection)
*** Eastern Hemisphere sales only
SPRINKLER
FINISH
1NATURAL
BRASS
3PURE WHITE (RAL9010)***
POLYESTER
4SIGNAL WHITE (RAL9003)
POLYESTER
9CHROME
PL ATED
TEMPERATURE
RATINGS
135 135°F (57°C)
155 155°F (68°C)
175 175°F (79°C)
200 200°F (93°C)
286 286°F (141°C)
P/N* 77 – XXX – X – XXX
SIN
373 5.6K CONVENTIONAL TY363
373 5.6K CONVENTIONAL TY3630**
TABLE A
PART NUMBER SELECTION
SERIES TY-FRB CONVENTIONAL SPRINKLERS
TFP667
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Other manuals for tyco TY-FRB Series

3

This manual suits for next models

2

Other Johnson Controls Irrigation System manuals

Johnson Controls Tyco EC-8 Series User manual

Johnson Controls

Johnson Controls Tyco EC-8 Series User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco LD User manual

Johnson Controls

Johnson Controls tyco LD User manual

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls SABROE NS-HPAC User manual

Johnson Controls

Johnson Controls SABROE NS-HPAC User manual

Johnson Controls tyco TY2235 User manual

Johnson Controls

Johnson Controls tyco TY2235 User manual

Johnson Controls tyco DS-1 Series User manual

Johnson Controls

Johnson Controls tyco DS-1 Series User manual

Johnson Controls tyco TY3596 User manual

Johnson Controls

Johnson Controls tyco TY3596 User manual

Johnson Controls tyco TY-L Series User manual

Johnson Controls

Johnson Controls tyco TY-L Series User manual

Johnson Controls tyco TY720 User manual

Johnson Controls

Johnson Controls tyco TY720 User manual

Johnson Controls tyco AQUAMIST ULF AM15 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM15 User manual

Johnson Controls Tyco EC-11 Series User manual

Johnson Controls

Johnson Controls Tyco EC-11 Series User manual

Johnson Controls JWS-3 User manual

Johnson Controls

Johnson Controls JWS-3 User manual

Johnson Controls tyco TY2334 User manual

Johnson Controls

Johnson Controls tyco TY2334 User manual

Johnson Controls tyco CC2 User manual

Johnson Controls

Johnson Controls tyco CC2 User manual

Johnson Controls tyco TY4334 Operating and maintenance instructions

Johnson Controls

Johnson Controls tyco TY4334 Operating and maintenance instructions

Johnson Controls tyco CC3 User manual

Johnson Controls

Johnson Controls tyco CC3 User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco ESFR-25 User manual

Johnson Controls

Johnson Controls tyco ESFR-25 User manual

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls tyco DS-1 Series User manual

Johnson Controls

Johnson Controls tyco DS-1 Series User manual

Johnson Controls tyco AQUAMIST ULF AM34 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM34 User manual

Johnson Controls tyco RFII-MRI Series User manual

Johnson Controls

Johnson Controls tyco RFII-MRI Series User manual

Johnson Controls tyco EC-5 Series User manual

Johnson Controls

Johnson Controls tyco EC-5 Series User manual

Popular Irrigation System manuals by other brands

Rain Bird RSD-BEx user guide

Rain Bird

Rain Bird RSD-BEx user guide

Reliable F3-80 Dry Pendent manual

Reliable

Reliable F3-80 Dry Pendent manual

Tyco TY-B Series quick start guide

Tyco

Tyco TY-B Series quick start guide

Reliable G quick start guide

Reliable

Reliable G quick start guide

Reliable DH56 Dry installation instructions

Reliable

Reliable DH56 Dry installation instructions

Renkforce Easy Trio operating instructions

Renkforce

Renkforce Easy Trio operating instructions

Tyco LFII Series quick start guide

Tyco

Tyco LFII Series quick start guide

Viking MICROMATIC VK202 Technical data

Viking

Viking MICROMATIC VK202 Technical data

Viking VK500 Technical data

Viking

Viking VK500 Technical data

Viking VK506 Technical data

Viking

Viking VK506 Technical data

Reliable F1FR56-300 QREC Series Bulletin

Reliable

Reliable F1FR56-300 QREC Series Bulletin

Tyco TY-B Series quick start guide

Tyco

Tyco TY-B Series quick start guide

AMT MiniACE Instructions for use

AMT

AMT MiniACE Instructions for use

Netafim D-Net 8550 user manual

Netafim

Netafim D-Net 8550 user manual

Viking HORIZON MIRAGE B-1 Technical data

Viking

Viking HORIZON MIRAGE B-1 Technical data

Eden 94134EDAMZ manual

Eden

Eden 94134EDAMZ manual

Toro Super 800 Series installation instructions

Toro

Toro Super 800 Series installation instructions

Tyco Rapidresponse LFII Series quick start guide

Tyco

Tyco Rapidresponse LFII Series quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.