When used in accordance with
NFPA 13, smoke vents and draft cur-
tains are not required as specified in the
2015 edition of the International Building
Code (IBC) and International Fire Code
(IFC) for CMSA sprinklers with an RTI of
50 or less and a design of 12 or fewer
sprinklers.
Construction Type
In accordance with NFPA 13 for
Extended Coverage Sprinklers for High
Piled Storage.
Obstruction Criteria
Follow Sections 8.8.5.1, “Extended
Coverage Obstruction Guidelines for
Sprinkler Discharge Pattern Develop-
ment”; 8.12.5.2 and 8.12.5.3, “ESFR
Obstruction Criteria,” for obstructions
that prevent the pattern from reaching
the hazard below.
Exception: When using Model EC-25
EC-25 Upright Sprinkler, any con-
tinuous obstruction 4 in. (100 mm) or
less shall be permitted to be ignored
in accordance with NFPA 13, section
21.5.3.2.3.
Deflector Distance below Ceiling
Follow NFPA 13, Section 8.8.4 for
allowed deflector distances below
ceiling.
Clearance to Storage
Minimum 36 in. (0,9 m) from the deflec-
tor to the top of storage required.
Maximum Distance
between Sprinklers
14 ft (4,3 m)
Minimum Distance
between Sprinklers
10 ft (3,0 m)
Installation
The TYCO Model EC-25 Extended
Coverage 25.2K Upright Sprinklers are
to be installed in accordance with this
section.
Damage to the fusible Link Assembly
during installation can be avoided by
handling the sprinkler using only the
frame arms and the appropriate sprin-
kler wrench. Do not grip or apply any
force to the fusible Link Assembly.
Damaged sprinklers must be replaced
immediately.
A leak-tight 1 in. NPT sprinkler joint
should be obtained by applying a
minimum-to-maximum torque of
20 to 30 lb-ft (26,8 to 40,2 N∙m). Higher
levels of torque may distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler.
Note: Install the Model EC-25 Upright
Sprinkler in the upright position.
Step 1. With pipe thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply any
force to the Link Assembly, and handle
the Model EC-25 Upright Sprinkler only
by the Frame arms.
Step 3. Wrench-tighten the Model
EC-25 Upright Sprinkler using only the
W-Type 1 Sprinkler Wrench (Ref. Figure
2) and by fully engaging (seating) the
wrench on the sprinkler wrench flats.
Step 4. After installation, inspect the
Link Assembly of each Model EC-25
Upright Sprinkler for damage. In par-
ticular, verify that the Link Assembly
and Hook are positioned as illustrated
in Figure 1, and that the Link Assembly
has not been bent, creased, or forced
out of its normal position in any way.
Damaged sprinklers must be replaced
immediately.
Care and
Maintenance
The TYCO Model EC-25 Extended Cov-
erage 25.2K Upright Sprinklers must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this decision.
Inspection, testing, and maintenance
must be performed as indicated below
and in accordance with the local
requirements and/or national codes.
Any impairment must be immediately
corrected.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of any
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product description and part
number (P/N).
Sprinkler Assemblies
Specify: Model EC-25 Extended Cover-
age 25.2K Upright Sprinklers (TY9128),
(specify temperature rating), with
Natural Brass finish, P/N (specify):
165° F (74°C) .............. P/N 58-450-1-165
212°F (100°C) ............ P/N 58-450-1-214
Special Order
Sprinkler Assemblies with
ISO 7-R 1 Thread Connection
Specify: Model EC-25 Extended Cover-
age 25.2K Upright Sprinklers (TY9128)
with ISO 7-R 1 thread connection,
(specify temperature rating), with
Natural Brass finish, P/N (specify):
165° F (74°C) ...............P/N 58-451-1-165
212°F (100°C) .............P/N 58-451-1-214
Sprinkler Wrench
Specify W-Type 1 Sprinkler Wrench,
P/N 56-872-1-025
"FITTING SIDE"
FITTING
TOWARDS SPRINKLER
RECESS
WRENCH
FIGURE 2
W-TYPE 1
SPRINKLER WRENCH