
TFP260
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Care and
Maintenance
The TYCO Series RFII, 5.6 K-factor,
Royal Flush Concealed Pendent Sprin-
klers, (TY3532) must be maintained
and serviced in accordance with this
section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protec-
tion system from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the Cover Plate/Retainer
Assembly can delay sprinkler opera-
tion in a fire situation.
When properly installed, there is a
nominal 3/32 in. (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This
air gap is necessary for proper oper-
ation of the sprinkler. If the ceiling
requires repainting after sprinkler instal-
lation, ensure that the new paint does
not seal off any of the air gap.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Replace sprinklers that are leaking or
exhibiting visible signs of corrosion.
Never repaint, plate, coat, or otherwise
alter automatic sprinklers after they
leave the factory. Never repaint fac-
tory-painted Cover Plates. If neces-
sary, replace them with factory-painted
units. Non-factory applied paint can
adversely delay or prevent sprinkler
operation in the event of a fire.
Replace modified or over-heated
sprinklers.
Exercise care to avoid damage to
the sprinklers before, during, and
after installation. Replace sprinklers
damaged by dropping, striking, wrench
twisting, wrench slipping, or the like.
Also, replace any sprinkler that has
a cracked bulb or that has lost liquid
from its bulb. Refer to the Installation
Section.
If you must remove a sprinkler, do not
reinstall it or a replacement without
reinstalling the Cover Plate/Retainer
Assembly. If a Cover Plate/Retainer
Assembly becomes dislodged during
service, replace it immediately.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION - for example, NFPA 25 -
in addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler systems should
be inspected, tested, and maintained
by a qualified Inspection Service in
accordance with local requirements
and/or national code.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P/N).
Sprinkler/Support Cup Assembly
Specify: Series RFII Royal Flush Con-
cealed Pendent Sprinkler, TY3532,
(specify) temperature rating, P/N
(specify):
155°F (68°C)
TY3532...................... 51-794-1-155
200°F (93°C)
TY3532......................51-794-1-200
Separately Ordered Cover Plate/
Retainer Assembly
Specify: (temperature rating, listed
below) Series RFII Concealed Cover
Plate with (finish), P/N (specify):
139°F (59°C)(a)
Grey White (RAL9002) . . . . . . . . . . 56-792-0-135
Brass .......................56-792
-
1-135
Pure White(c) (RAL9010). . . . . . . . . 56-792-3-135
Signal White (RAL9003)
. . . . .
56-792-4-135
Jet Black (RAL9005) . . . . . . . . . . . 56-792-6-135
Chrome......................56-792-9-135
Custom......................56-792-X-135
165°F ( 74°C) (b)
Grey White (RAL9002) . . . . . . . . . . 56-792-0-165
Brass .......................56-792-1-165
Pure White(c) (RAL9010 ). . . . . . . . . 56 -792-3-165
Signal White (RAL9003). . . . . . . . . 56 -792- 4-165
Jet Black (RAL9005) . . . . . . . . . . . 56-792-6-165
Chrome......................56-792-9-165
Custom......................58-792-X-165
a. For use with 155°F (68°C) sprinklers
b. For use with 200°F (93°C) sprinklers
c. Eastern Hemisphere sales only
Sprinkler Wrench
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075