manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Johnson Controls
  6. •
  7. Irrigation System
  8. •
  9. Johnson Controls tyco ESFR-34 User manual

Johnson Controls tyco ESFR-34 User manual

Model ESFR-34
33.6 K-factor Pendent Sprinklers
Early Suppression, Fast Response
Page 1 of 4 DECEMBER 2019 TFP338
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
Technical
Data
Approvals
FM Approved
Finish
Natural Brass
Physical Characteristics
Frame � � � � � � � � � � � � � � � � � � � � � � � � � � � � �Brass
Deflector � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze
Compression Screw � � � � � � � � � � Stainless Steel
Hook � � � � � � � � � � � � � � � � � � � � � � � � � � � � MONEL
Strut� � � � � � � � � � � � � � � � � � � � � � � � � � � � � MONEL
Link Assembly� � � � � � � � � � � � � � � � Solder, Nickel
Button ��������������������� Stainless Steel
Sealing Assembly ��Beryllium Nickel w/TEFLON
Additional Technical Data
See Table A for additional technical data�
Operation
The fusible link assembly is com-
prised of two link halves that are joined
together by a thin layer of solder� When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water�
NOTICE
The Model ESFR-34 Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of FM Global, in addi-
tion to the standards of any authorities
having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
In all cases, the appropriate FM instal-
lation standard, or other applicable
standard, must be referenced to ensure
applicability and to obtain complete
installation guidelines. The general
guidelines in this technical data sheet
are not intended to provide complete
installation criteria.
Sprinkler
Identification
Number
See Table A for sprinkler identification
number�
General
Description
TYCO Model ESFR-34 Pendent Sprin-
klers are Early Suppression, Fast
Response Sprinklers having a nominal
K-factor of 33�6 (See Figure 1)� They are
suppression-mode sprinklers that are
especially advantageous as a means of
eliminating the use of in-rack sprinklers
when protecting high-piled storage�
The Model ESFR-34 Sprinklers are pri-
marily used for ceiling-only sprinkler
protection of (but not limited to) the
following storage applications:
• most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
• uncartoned (exposed) expanded
plastics in accordance with FM
Global standards
• some storage arrangements of
rubber tires, roll paper, flammable
liquids, and aerosols
For more specific criteria, refer to Table
B as well as the applicable design
standard�
The Model ESFR-34 can protect a
storage arrangement of 50 ft (15,2 m)
with a ceiling height of 55 ft (16,8 m)
without requiring in-rack sprinklers�
In addition, it can be installed with a
maximum centerline of thermal sensing
element-to-ceiling distance of 17 in�
(432 mm)�
TFP338
Page 2 of 4
Design
Criteria
The following general guidelines pro-
vided for the TYCO Model ESFR-34
Pendent Sprinklers can be used for a
quick reference�
FM Global Property Loss Prevention
Data Sheet 2-0, “Installation Guide-
lines for Automatic Sprinklers”, pro-
vides the installation guidelines for
the TYCO K33�6 sprinkler under the
heading of Storage Sprinkler, whereas
FM Global Property Loss Prevention
Data Sheet 8-9, “Storage of Class 1,
2, 3, 4 and Plastic Commodities”, pro-
vides its design guidelines� In all cases,
the appropriate FM Global installation
standard must be referenced to ensure
applicability and cannot be substituted
by other codes or standards� Table B
provides a summary of the design
and installation guidelines provided in
Data Sheets 2-0 and 8-9; they are not
intended to provide complete installa-
tion criteria�
In addition to this technical data sheet,
the following Technical Data Sheets
describe other TYCO ESFR Sprinklers:
• TFP312
Model ESFR-25 (TY9226)
K=25�2 Pendent Sprinkler
• TFP315
Model ESFR-17 (TY7226)
K=16.8 Pendent Sprinkler
• TFP316
Model ESFR-17 (TY7126)
K=16.8 Upright Sprinkler
• TFP317
Model ESFR-17 (TY7223)
K=16.8 Pendent Sprinkler
• TFP318
Model ESFR-1 (TY6226)
K=14.0 Pendent Sprinkler
• TFP319
Model ESFR-14 (TY6236)
K=14.0 Pendent Sprinkler
• TFP320
Model ESFR-17 (TY7229)
K=16.8 Dry Pendent Sprinkler
• TFP321
Model ESFR-22 (TY8223)
K=22.4 Pendent Sprinkler
Roof Construction
Refer to FM 2-0, Section 2�2
TABLE A
MODEL ESFR-34 PENDENT SPRINKLER
TECHNICAL DATA
Item Description
Sprinkler Identication Number (SIN) TY9286
K-factor, gpm/psi½(lpm/bar½)33�6 gpm/psi½(480 lpm/bar½)
Thread Size 1 1/4 in� NPT or ISO 7-R 1 1/4
Sprinkler Orientation Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
2
6
4
3
1
5
7
8
-
-
-
-
-
-
-
-
Deector
Hook
Compression
Assembly
Components:
Link
Frame
Screw
Strut
Assembly
Button
Assembly
Sealing
WRENCH
FLATS
CENTERLINE
OF THERMAL
ELEMENT
TEMPERATURE
RATING
5/8"
(15,9 mm)
NOMINAL
MAKE-IN
4-3/16"
(106,4 mm)
1-1/4" NPT
1
8
7
5
4
3
2
6
2-1/4"
(57,2 mm)
2-1/16"
(52,4 mm)
FIGURE 1
MODEL ESFR-34 (TY9286) EARLY SUPPRESSION, FAST RESPONSE
PENDENT SPRINKLER 33.6 K-FACTOR
TFP338
Page 3 of 4
TABLE B
MODEL ESFR-34 PENDENT SPRINKLERS
FM GLOBAL COMMODITY SELECTION AND DESIGN CRITERIA
Description Specification
Sprinkler Type QR Storage (ESFR)
Temperature Rating ºF (ºC) 165°F (74°C) and 212°F (100°C)
Response Type QR
Sprinkler Position Pendent, frame arms aligned with pipe, deectors parallel to oor
System Type Wet
Maximum Area of Coverage 100 ft2(9,3 m2)
Minimum Area of Coverage 64 ft2(5,9 m2)
Maximum Slope Ceiling Up to 10°
Maximum Spacing For buildings up to 30 ft (9,1 m): 12 ft (3,7 m)
For buildings over 30 ft (9,1 m): 10 ft (3,0 m)
Minimum Spacing 8 ft (2,4 m)
Deector Distance from Walls Minimum of 4 in. (100 mm) from walls but no more than
1/2 the allowable distance permitted between sprinklers
Deector to Top of Storage Minimum of 36 in. (914 mm)
Centerline of Thermal Sensing
Element to Ceiling Distance
Min. Distance: Refer to FM 2-0, Section 2.2
Max. Distance: 17 in. (432 mm)
Maximum Ceiling Height 55 ft (16,8 m)
Maximum Storage Height 50 ft (15,2 m)
Storage Arrangement Palletized, solid piled, open frame; single row or double row
Commodity Class I - IV, Cartoned unexpanded plastic
Sprinkler System Design Total of 9 operating sprinklers (3 sprinklers on the most remote 3 lines) with a minimum
pressure of 55 psi (3.8 bar) available at the most remote sprinkler
Obstruction Criteria Refer to FM 2-0 Section 2.2
Minimum Aisle Width 6 ft (1,8 m)
Hose Stream Allowance and
Water Supply Duration 250 gpm for 60 minutes (950 lpm for 60 minutes)
TFP338
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL is a registered trademarks of Special Metals Corporation;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Installation
TYCO Model ESFR-34 Pendent Sprin-
klers must be installed in accordance
with this section�
General Instructions
Damage to the fusible Link Assem-
bly during installation can be avoided
by handling the sprinkler by the frame
arms only (that is, do not apply pres-
sure to the fusible Link Assembly),
and by using the appropriate sprinkler
wrench� Failure to do so can lead to an
unstable link assembly and premature
activation of the sprinkler� Damaged
sprinklers must be replaced�
A leak-tight 1 1/4 in� NPT sprinkler
joint should be obtained by applying a
minimum-to-maximum torque of 30 to
40 lb-ft (40,7 to 54,2 N∙m)� Higher levels
of torque can distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler�
Note: Install the Model ESFR-34
Pendent Sprinkler in the pendent posi-
tion (See Figure 2).
Step 1. With pipe-thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting� Do not apply pres-
sure to the Link Assembly, and handle
the Model ESFR-34 Pendent Sprinkler
only by the Frame arms�
Step 2. Use only the W-Type 26 Sprin-
kler Wrench (See Figure 2) to install
the Model ESFR-34 Pendent Sprinkler�
Fully engage (seat) the wrench recess
on the sprinkler wrench flats (See
Figure 1) and wrench-tighten�
Step 3. After installation, inspect the
Link Assembly of each Model ESFR-34
Pendent Sprinkler for damage� In par-
ticular, verify that the Link Assembly
and Hook are positioned as illustrated
in Figures 1 and 2, and that the Link
Assembly is not bent, creased, or
forced out of normal position in any
way� Replace damaged sprinklers�
Care and
Maintenance
TYCO Model ESFR-34 Pendent Sprin-
klers must be maintained and serviced
in accordance with this section�
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action�
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced�
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory�
Modified sprinklers must be replaced�
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush�
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation� Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced�
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(for example, NFPA 25), in addition to
the standards of any authorities having
jurisdiction� Contact the installing con-
tractor or product manufacturer with
any questions�
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes�
Limited
Warranty
For warranty terms and conditions, visit
www�tyco-fire�com�
Ordering
Procedure
Contact your local distributor for avail-
ability� When placing an order, indicate
the full product name and Part Number
(P/N)�
Sprinkler Assemblies with
1 1/4 Inch NPT Thread Connection
Specify: Model ESFR-34 (TY9286),
K=33�6, Early Suppression, Fast
Response Pendent Sprinkler with
1 1/4 in� NPT thread connection,
(specify) temperature rating, Natural
Brass, P/N (specify):
165° F ( 74° C ) ������������������ 51-681-1-165
212°F (100°C) ����������������� 51-681-1-212
Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connections
Specify: Model ESFR-34 (TY9286),
K=33�6, Early Suppression, Fast
Response Pendent Sprinkler with
ISO 7-R 1 1/4 thread connection,
(specify) temperature rating, Natural
Brass, P/N (specify):
165° F ( 74° C ) ������������������51-682-1-165
212°F (100°C) �����������������51-682-1-212
Sprinkler Wrench
Specify: W-Type 26 Sprinkler Wrench,
P/N 56-341-1-001
"SPRINKLER
SIDE"
TOWARDS
SPRINKLER
WRENCH
RECESS
FIGURE 2
W-TYPE 26
SPRINKLER WRENCH

This manual suits for next models

1

Other Johnson Controls Irrigation System manuals

Johnson Controls tyco ESFR-25 User manual

Johnson Controls

Johnson Controls tyco ESFR-25 User manual

Johnson Controls Tyco TY3201 User manual

Johnson Controls

Johnson Controls Tyco TY3201 User manual

Johnson Controls JWS-3 User manual

Johnson Controls

Johnson Controls JWS-3 User manual

Johnson Controls tyco CHEC User manual

Johnson Controls

Johnson Controls tyco CHEC User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco TFP700 User manual

Johnson Controls

Johnson Controls tyco TFP700 User manual

Johnson Controls tyco CC2 User manual

Johnson Controls

Johnson Controls tyco CC2 User manual

Johnson Controls tyco RFII-MRI Series User manual

Johnson Controls

Johnson Controls tyco RFII-MRI Series User manual

Johnson Controls tyco TY720 User manual

Johnson Controls

Johnson Controls tyco TY720 User manual

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls tyco EC-25 User manual

Johnson Controls

Johnson Controls tyco EC-25 User manual

Johnson Controls tyco EC-8C Series User manual

Johnson Controls

Johnson Controls tyco EC-8C Series User manual

Johnson Controls SABROE SVER User manual

Johnson Controls

Johnson Controls SABROE SVER User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls tyco TY2335 User manual

Johnson Controls

Johnson Controls tyco TY2335 User manual

Johnson Controls tyco CWS User manual

Johnson Controls

Johnson Controls tyco CWS User manual

Johnson Controls tyco ESFR-25 User manual

Johnson Controls

Johnson Controls tyco ESFR-25 User manual

Johnson Controls tyco EC-5 Series User manual

Johnson Controls

Johnson Controls tyco EC-5 Series User manual

Johnson Controls tyco DSB-2 User manual

Johnson Controls

Johnson Controls tyco DSB-2 User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco RAVEN User manual

Johnson Controls

Johnson Controls tyco RAVEN User manual

Johnson Controls TY5811 User manual

Johnson Controls

Johnson Controls TY5811 User manual

Johnson Controls tyco RFII Series User manual

Johnson Controls

Johnson Controls tyco RFII Series User manual

Popular Irrigation System manuals by other brands

Tyco TY-FRB Series manual

Tyco

Tyco TY-FRB Series manual

Tyco ESFR-17 quick start guide

Tyco

Tyco ESFR-17 quick start guide

Nelson RainTrain2 instruction manual

Nelson

Nelson RainTrain2 instruction manual

Tyco RFII-MRI Series manual

Tyco

Tyco RFII-MRI Series manual

Tyco rapid response LFII Series General description

Tyco

Tyco rapid response LFII Series General description

Havahart Spray Away owner's manual

Havahart

Havahart Spray Away owner's manual

Tyco ESFR-1 quick start guide

Tyco

Tyco ESFR-1 quick start guide

Nelson PC-S3000 quick start guide

Nelson

Nelson PC-S3000 quick start guide

Hunter I-80 installation instructions

Hunter

Hunter I-80 installation instructions

Westfalia Sprinkler instruction manual

Westfalia

Westfalia Sprinkler instruction manual

Eden 96998EDAMZ quick start guide

Eden

Eden 96998EDAMZ quick start guide

Gardena OS 140 Operator's manual

Gardena

Gardena OS 140 Operator's manual

claber 8053 instruction manual

claber

claber 8053 instruction manual

Tyco CCU Rack General Overview and Operation Manual

Tyco

Tyco CCU Rack General Overview and Operation Manual

Eden 99989EDAMZ quick start guide

Eden

Eden 99989EDAMZ quick start guide

Rain Bird 11000 Series Operation & maintenance manual

Rain Bird

Rain Bird 11000 Series Operation & maintenance manual

Tyco ESFR-17 quick start guide

Tyco

Tyco ESFR-17 quick start guide

Tyco Fire Product Gem F916 instruction manual

Tyco Fire Product

Tyco Fire Product Gem F916 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.