Johnson Controls METASYS Series Assembly instructions

Installation Sheet
Issue Date 0495
©1995 Johnson Controls, Inc. 1
Part No. 24-7534-2
●flat-head screwdriver
●needle-nose pliers
●drill
The ZT unit measures 6.88 x 7.31 x 1.52 inch (175 x 186 x 39 mm), and
weighs 1.25 lb (0.57 kg). A coiled, 6-pin telephone-type cord is included.
The cord is 17 inches long and stretches to 5 feet. The ZT contains a
5-year lithium battery, factory installed.
The Wall Mount Base with ZT measures 6.94 x 7.44 x 2.00
(176 x189 x 51 mm).
The Utility Mount Base with ZT measures 6.94 x 7.44 x 6.00
(176 x 189 x 152 mm) when mounted on the ENC100.
Installation of the Zone Terminal must meet the following standards:
●Ambient operating conditions: 32 to 122°F (0 to 50°C)
●10 to 90% non-condensing relative humidity
●86°F (30°C) maximum dew point
Notes: Do not mount the Zone Terminal on a vibrating surface.
The atmosphere must be free of corrosive chemical vapors that
may damage electronic equipment.
●Use mild soap and water with a soft cloth to wipe surfaces of the ZT
clean.
●Do not immerse the ZT unit in water.
●Wipe clean with pure isopropyl alcohol, if surface becomes
excessively dirty.
Zone Terminal
Tools Needed
Physical
Dimensions
Environmental
Information
Cleaning of ZT
Surfaces

2Zone Terminal Installation Sheet
Before you mount the ZT or connect it to a controller, the clear plastic
insert that describes the displayed values must be in place.
1. To open the ZT, lay the ZT flat and press the white tab on the top of
the ZT while pulling the front cover towards you.
2. Align the insert to the lower left front of the ZT.
3. Press the pieces back together.
INSERT3A
View
from
here.
Figure 1: Template Installation
Prior to final connection, the ZT must be downloaded using the ZT PRO
software tool which is part of the HVAC PRO Rev. 3.0 or later. Refer to
the HVAC PRO for Windows User’s Manual, Zone Terminal section.
If the ZT is connected 50 feet or less from the controller, install 24 AWG
(6-conductor) telephone cable between the controller and the ZT.
If the ZT is connected up to 500 feet from the controller, install 18 AWG
wire. The ZT requires 24 VAC, Common, and Zone Bus. The Zone Bus
and Common should be twisted pair.
The ZT can be connected directly to the:
●Air Handling Unit (AHU)
●Function Module Kit (FMK)
●Relay Kit (RLY) through a CBLCON-0
●Actuator (M100C)
●Zone Sensor (TE-6400)
●Humidity Sensor (HE-6400)
Figure 2 shows you where to locate the telephone-style plugs in these
components.
Installing the
Inserts
Connecting the
Zone Terminal
Wiring
Considerations

Zone Terminal Installation Sheet 3
Figure 2: Connecting the Zone Terminal
FMK 102
AHU103
Controller
Remote
RLY100/50
conect2
M100C
TE-6400
CBLCON-0

4Zone Terminal Installation Sheet
Other remote connections include permanently connecting to a UNT or
VAV using the CBLCON-0 and TE-6400 Zone Sensor (Figure 3).
88
66
6
2 4
VAC
COM
ZONE
BUS
1 2 3 4 5 6 7 8
1 2 3 4 5 6
B INAR Y IN
ANA LOG INPUTS B INAR Y OUTPUTS
BINARY INPUT
A N AL OG INP U TS
1 2 3 4 5 6 1 2 3 4
ANA LOG INPUTS
COMMON
+15 VDC
TO
ZONE
STAT
B IN AR Y OU TP U T
2 4V A C
1 2 3 4 5 6
+15 VDC
2 4V AC
TRACS
24 V A C
1 2 3 4 5 6
COMMON
COMMON
COM MON
0-10V DC
ANA L OG
OUT PUT
CONCT2
Connect ZT here.
Switch must
be in
normal position.
Connect
STAT here.
Connect VAV/UNT
here.
Green LED
Red LED
Figure 3: Connecting Remote ZT to UNT/VAV with
CBLCON-0 and Zone Sensor

Zone Terminal Installation Sheet 5
The Zone Terminal can be connected directly to a VAV/UNT through a
Zone Sensor without the use of the CBLCON-0 (Figure 4). This is a
portable application.
BINARYINANALOGINPUTSBINARYOUTPUTSANA OUT
BINARYIN
ANALOGINPUTS
123456 1 234
ANALOGINPUTS
COMMON
BINARYCOM
+15VDC
COM
PWR
IN
24V
AC
BINARYOUTPUT
24VACTOLOADS
12345612
0-10VDC
ANALOG
OUTPUT
ANALOG
OUTPUT
COMMON
OFF
AS-UNT101-0
TE-6400
Zone Terminal
VAV/UNT
CONCT3J
Figure 4: Remote Connect ZT to VAV/UNT through the
Zone Sensor
!
CAUTION: The ZT must be plugged into a 6-pin telephone-type
jack. Plugging the ZT into an 8-pin jack destroys the
8-pin receptacle and prevents the ZT from powering
up.

6Zone Terminal Installation Sheet
For optimum viewing, mount the top of the ZT 65 inches from the floor.
Before attaching the Enclosure Kit (ENC100-0) to the wall, remove the
top or bottom rectangular knockouts with a needle-nose pliers, depending
on the end through which the wires will run.
KNOCKOUT
Knock wire
passage out
on top or
bottom.
Figure 5: Remove Knockouts
Physical
Installation of
Wall Mountings
and Bases
Enclosure Kit
and Base
Installation

Zone Terminal Installation Sheet 7
Attach the Enclosure Kit (ENC100-0) to a flat surface or wall for direct
connection of the ZT to an application specific controller. Pull wire
through before attaching standoffs and screws for the plastic base.
MT&BASE
Figure 6: Attaching the Enclosure Kit and Utility Mounting Base

8Zone Terminal Installation Sheet
Attach the base, pulling the telephone jack type cord through the opening
as shown below. Plug the cord into the back of the ZT, and snap the ZT
into position.
ENCMTBAS
Figure 7: Connecting and Mounting the ZT

Zone Terminal Installation Sheet 9
For office or other types of remote connections, attach the Wall Mount to
a flat surface or wall. Use three screws and plastic anchors (not
provided). For easy reading, mount the ZT at least 65 inches from the
floor to the top of the ZT.
1. Position the Zone Terminal Wall Mounting Base on the wall.
2. Mark the three mounting hole locations and remove the base.
3. Drill three holes for No. 6 anchors (not included) and install the
anchors for mounting the base.
4. Thread the ZTU cable through the access hole in the back of the base.
5. Secure the Wall Mounting Base to the wall with three No. 6 screws.
6. Plug the ZTU cable in the back of the ZTU, and snap the ZTU into
the base.
WALMTZT
Figure 8: Attaching ZT and Wall Mount
Wall Mount
Installation

10 Zone Terminal Installation Sheet
Using the wall mounting base, follow the instructions below to mount the
Zone Terminal on a UPM.
Zone
Terminal
Mounted on
the Outside
ztcontr
METASYS
AHU103
N2
Zone
Bus
ALARM
Figure 9: Mounting the Zone Terminal on a UPM
1. Position the Zone Terminal Wall Mounting Base flush on the cover at
eye level (approximately 65 inches from the floor to top of ZT).
2. Mark mounting holes.
3. Mark cable hole.
4. Drill three size 3/32 inch pilot holes for mounting the base.
5. Drill 5/8 to 1 inch hole for cable.
6. Mount the base to the UPM cover using three No. 6 thread forming or
sheet metal screws. Use a No. 6 x 3/4 inch screw for the top hole and
two No. 6 x 1/2 inch screws for the bottom screws.
Mounting the ZTU
Externally on the
UPM

Zone Terminal Installation Sheet 11
The Panel Unit in Poteau, Oklahoma has a bracket available for mounting
the ZT behind a window that allows control equipment to be mounted
behind the ZT, thereby maximizing the use of the UPM. Contact the
Panel Unit for more information.
Johnson Controls Panel Unit wires and configures units, complete with
accessories, to your specifications. The ZTU internal mounting bracket is
also available. Contact:
Panel Unit -- Poteau
3100 North Broadway
P.O. Box 1088
Poteau, OK 74953
(918) 647-2195
FAX: (918) 647-4895 (Customer Service)
BottomViewofUPM
ALARM
ztin2
ZT
UNT
Figure 10: Bracket for Mounting the ZTU Internally in the UPM
Mounting the ZT
Behind a Window
Enclosure in the
UPM

12 Zone Terminal Installation Sheet
Use a large flat-head screwdriver and insert it in the bottom where the ZT
and mounting base come together. Gently pry the ZT out of the mounting
base. As you push the screwdriver in, the ZT slides up and then out.
REMOVAL
Figure 11: Removing Mounted ZT
Removing a
Mounted ZT
Controls Group
507 E. Michigan Street
P.O. Box 423 Issue Date 0495
Milwaukee, WI 53201 Printed in U.S.A
Other Johnson Controls Touch Terminal manuals

Johnson Controls
Johnson Controls FlexSys MIT3-CN User manual

Johnson Controls
Johnson Controls METASYS Zone Terminal Assembly instructions

Johnson Controls
Johnson Controls FlexSys Elan-06R-180 User manual

Johnson Controls
Johnson Controls METASYS User manual

Johnson Controls
Johnson Controls TVS User manual
Popular Touch Terminal manuals by other brands

Chase
Chase iPP 320 PIN Pad Quick reference guide

Mitsubishi Electric
Mitsubishi Electric GT2708-STBA manual

Siemens
Siemens VT9324-4TD30 operating instructions

VeriFone
VeriFone OMNI 3300 operating guide

Schmalz
Schmalz SCTMc operating instructions

Custom Audio Electronics
Custom Audio Electronics SILK Android Short guide