JUMO LOGOSCREEN es User manual

11.07/00416051
Paperless Recorder
for secure acquisition of
FDA-compliant
measurement data
B 70.6560.2.3
PROFIBUS DP
Interface Description
es


Contents
1 Introduction 5
1.1 Preface .......................................................................................................... 5
1.2 Typographical conventions ......................................................................... 6
1.2.1 Warnings ...................................................................................................... 6
1.2.2 Note signs .................................................................................................... 6
2 Profibus description 7
2.1 Profibus types ............................................................................................... 7
2.2 RS485 transmission technology ................................................................. 8
2.3 PROFIBUS DP ............................................................................................. 11
3 Configuring a PROFIBUS system 13
3.1 GSD files ...................................................................................................... 13
3.2 Configuration procedure ........................................................................... 14
3.3 The GSD generator .................................................................................... 15
3.3.1 General ...................................................................................................... 15
3.3.2 Operation ................................................................................................... 15
3.3.3 Example report ......................................................................................... 17
3.4 Connection example .................................................................................. 19
3.4.1 RECORDER ............................................................................................... 19
3.4.2 GSD generator ........................................................................................... 19
3.4.3 PLC configuration ...................................................................................... 20
4 Data format of the recorder 23
5 Device-specific data 25
5.1 Paperless recorder LOGOSCREEN .......................................................... 26
5.2 System requirements ................................................................................. 26
5.3 Connection diagram .................................................................................. 26
5.4 Setting the slave address .......................................................................... 27
5.5 Diagnostic and status messages .............................................................. 27
5.6 Acyclic data ................................................................................................ 27
5.7 PLC data in 16-bit format .......................................................................... 32

Contents
5.8 Bit-by-bit coding of binary signals ........................................................... 34
5.9 External inputs and faults in the data exchange ..................................... 35
5.10 Paperless recorders LOGOSCREEN es and cf ........................................ 36
5.10.1 System requirements ................................................................................. 36
5.10.2 Connections for LOGOSCREEN es and cf ................................................ 36
5.10.3 Setting the slave address .......................................................................... 37
5.10.4 Diagnosis and status messages ................................................................ 37
5.10.5 Acyclic data transmission .......................................................................... 37
5.10.6 Extension of the address range for LOGOSCREEN es and cf .................. 38
5.10.7 Process data .............................................................................................. 39
5.10.8 PLC data in 16-bit format .......................................................................... 46
5.10.9 Bit-wise coded binary logic signals ........................................................... 48
5.10.10External inputs and faults in the data exchange ....................................... 49

5
1 Introduction
1.1 Preface
Please read this manual before starting up the interface. Keep the manual in a
place which is accessible to all users at all times.
Please assist us to improve this manual.
Your suggestions will be welcome.
HIf any difficulties should arise during commissioning, you are asked
not to carry out any unauthorized manipulations. You could endan-
ger your rights under the instrument warranty!
Please contact the nearest subsidiary or the main factory in such a
case.
EWhen returning chassis, modules or components, the regulations
of EN 100 015 “Protection of electrostatically sensitive compo-
nents” must be observed. Use only the appropriate ESD packag-
ing for transport.
Please note that we cannot accept any liability for damage caused
by ESD (electrostatic discharge).
B

1 Introduction
6
1.2 Typographical conventions
1.2.1 Warnings
The signs for Danger and Caution are used in this manual under the following
conditions:
V
Danger
This symbol is used where there may be danger to personnel if the instruc-
tions are disregarded or not followed accurately!
ACaution
This symbol is used where there may be damage to equipment or data if the
instructions are disregarded or not followed accurately!
E
Caution
This symbol is used if precautions must be taken when handling electrostati-
cally sensitive components.
1.2.2 Note signs
HNote
This symbol is used to draw your special attention to a remark.
vReference
This symbol refers to additional information in other manuals, chapters or
sections.
abc1Footnote
Footnotes are notes which refer to certain points in the text.
Footnotes consist of two parts:
Marking in the text and the footnote text.
The marking in the text is arranged as continuous superscript numbers.
h
Handling instructions
This symbol marks the description of a required action.
The individual steps are indicated by an asterisk, e. g.
hPress the hkey
hConfirm with E

7
2 Profibus description
PROFIBUS is a manufacturer-independent, open fieldbus standard for a wide
range of applications in manufacturing, process and building automation.
Manufacturer independence and openness are ensured by the international
standard EN 50 170.
Using PROFIBUS, devices from different manufacturers can communicate
without any special interface adjustments. PROFIBUS can be employed for
both high-speed time-critical data transmission and extensive, complex com-
munication tasks. The PROFIBUS family consists of three versions.
2.1 Profibus types
The PROFIBUS family
PROFIBUS DP This PROFIBUS version, which is optimized for high speed and low connec-
tion costs, has been especially designed for communication between auto-
mation control systems (PLC) and distributed field devices (typical access
time: < 10msec). PROFIBUS DP can be used to replace conventional, parallel
signal transmission with 24V or 0/4—20mA.
DPV0: cyclic data transfer:
--> is supported by the recorder.
DPV1: cyclic and acyclic data transfer:
--> is not supported by the recorder.
DPV2: slave-to-slave communication takes place in addition to cyclic and
acyclic data transfer:
--> is not supported by the recorder.
PROFIBUS-PA PROFIBUS-PA has been specifically designed for process engineering. It per-
mits the linking of sensors and actuators to a common bus cable, even in haz-
ardous areas. PROFIBUS-PA enables the data communication and energy
supply for devices in two-wire technology according to the international IEC
1158-2 standard.
PROFIBUS-FMS This is the universal solution for communication tasks at cell level (typical ac-
cess time: approx. 100msec). The powerful FMS services open up a wide
range of applications and provide a high degree of flexibility. FMS is also suit-
able for extensive communication tasks.

2 Profibus description
8
2.2 RS485 transmission technology
Transmission takes place according to the RS485 standard. It covers all areas
in which a high transmission speed and simple, cost-effective installation are
required. A shielded twisted copper cable with one conductor pair is used.
The bus structure permits addition and removal of stations or step-by-step
commissioning of the system without affecting the other stations. Later expan-
sions have no influence on the stations which are already in operation.
Transmission speeds between 9.6 kbit/sec and 12 Mbit/sec are available. One
uniform transmission speed is selected for all devices on the bus when the
system is commissioned.
Basic features of the RS485 transmission technology
Installation
tips All devices are connected in a bus structure (line). Up to 32 stations (master or
slaves) can be linked up in one segment.
The bus is terminated by an active bus terminator at the start and end of each
segment. Both bus terminators must always be powered, to ensure fault-free
operation.
If there are more than 32 users, repeaters must be used to link up the individu-
al bus segments.
Network topology linear bus, active bus termination at both ends,
stub cables are only permissible for baud rates
≤1.5 Mbit/sec.
Medium shielded twisted-pair cable
Number of stations 32 stations in each segment without repeater (line amplifier).
With repeaters, this can be expanded to 126.
Connector preferably 9-pin sub-D connector

9
2 Profibus description
Cable length The maximum cable length depends on the transmission speed. The cable
length specified can be extended by using repeaters. It is recommended not
to connect more than 3 repeaters in series.
Range based on transmission speed
Cable data These cable length specifications refer to the cable type described below:
Characteristic impedance: 135 — 165 Ω
Capacitance per unit length: < 30 pf/m
Loop resistance: 110 Ω/km
Core dia.: 0.64 mm
Core cross-section: > 0.34 mm²
It is preferable to use a 9-pin sub-D connector for PROFIBUS networks incor-
porating RS485 transmission technology. The pin assignment at the connector
and the wiring are shown at the end of this chapter.
PROFIBUS cables and connectors are supplied by several manufacturers.
Please refer to the PROFIBUS product catalog (www.profibus.com) for types
and addresses of suppliers.
When connecting up the devices, make sure that the data lines are not re-
versed. It is absolutely essential to use shielded data lines. The braided shield
and the screen foil underneath (if present) should be connected to the protec-
tive earth on both sides, and with good conductivity. Furthermore, the data
lines should be routed separately from all high-voltage cables, as far as this is
possible.
As a suitable cable we recommend the following type from Siemens:
Simatic Net Profibus 6XV1
Order No. 830-0AH10
* (UL) CMX 75 °C (Shielded) AWG 22 *
Baud rate
(kbit/s)
9.6 19.2 93.75 187.5 500 1500 12000
Range/segment 1200 m 1200 m 1200 m 1000 m 400 m 200 m 100 m

2 Profibus description
10
Data rate For installation, the use of stub cables must be avoided for data rates above
1.5 Mbit/sec.
Wiring and
bus termination
HFor important tips on installation, please refer to the Installation
Guidelines PROFIBUS DP, Order No. 2.111 by the PNO (Profibus
User Organization).
Address:
Profibus Nutzerorganisation e.V.
Haid- u. Neu-Straße 7
D-76131 Karlsruhe, Germany
Internet: www.profibus.com
Recommendation:
Please follow the installation recommendations
made by the PNO, especially for the simultaneous use
of frequency inverters.

11
2 Profibus description
2.3 PROFIBUS DP
PROFIBUS DP is designed for high-speed data exchange at the field level.
The central control devices, PLC/PC for instance, communicate through a fast
serial connection with distributed field devices such as I/O, paperless
recorders and controllers. Data exchange with these distributed devices is
mainly cyclic. The communication functions required for this are defined by
the basic PROFIBUS DP functions in accordance with EN 50 170.
Basic
functions The central controller (master) reads the input information cyclically from the
slaves and writes the output information cyclically to the slaves. The bus cycle
time must be shorter than the program cycle time of the central PLC. In addi-
tion to cyclic user data transmission, PROFIBUS DP provides powerful func-
tions for diagnostics and commissioning.
Transmission technology:
• RS485 twisted pair
• Baud rates from 9.6 kbit/sec up to 12 Mbit/sec
Bus access:
• Master and slave devices, max. 126 users on one bus
Communication:
• Peer-to-peer (user data communication)
• Cyclic master-slave user data communication
Operating states:
• Operate: Cyclic transmission of input and output data
• Clear: Inputs are read, outputs remain in secure state
• Stop: Only master-master data transfer is possible
Synchronization:
• Sync mode: not supported by the recorder
• Freeze mode: not supported by the recorder
Functionality:
• Cyclic user data transfer between DP master and DP slave(s)
• Dynamic activation or deactivation of individual DP slaves
• Checking the configuration of the DP slaves
• Address assignment for the DP slaves via the bus
• Configuration of the DP master via the bus
• maximum of 246 bytes input/output data for each DP slave
Protective functions:
• Address monitoring for the DP slaves
• Access protection for inputs/outputs of the DP slaves
• Monitoring of user data communication with adjustable monitoring timer
in the master
Device types:
• DP master Class 2, e. g. programming/project design devices
• DP master Class 1, e. g. central automation devices such as PLC, PC…
• DP slave e. g. devices with binary or analog inputs/outputs, controllers,
recorders...

2 Profibus description
12
Cyclic
data
transmission
The data transmission between the master and the DP slaves is carried out by
the master in a defined, recurring order. When configuring the bus system, the
user defines the assignment of a DP slave to the master. It is also defined
which DP slaves are to be included in, or excluded from, the cyclic user data
communication.
Data transmission between the master and the DP slaves is divided into three
phases: parameterization, configuration and data transfer. Before a DP slave
enters the data transfer phase, the master checks in the parameterization and
configuration phase whether the planned configuration matches the actual de-
vice configuration. In the course of this check, the device type, format and
length information, as well as the number of inputs and outputs must agree.
These checks provide the user with reliable protection against parameteriza-
tion errors. In addition to the user data transfer, which is performed automati-
cally by the master, new parameterization data can be sent to the DP slaves at
the request of the user.
User data transmission in PROFIBUS DP

13
3 Configuring a PROFIBUS system
3.1 GSD files
Device base data (GSD) enable open project design.
PROFIBUS devices have different features. They differ with respect to the
available functionality (e. g. number of I/O signals, diagnostic messages) or
possible bus parameters, such as baud rate and time monitoring. These pa-
rameters vary individually for each device type and manufacturer. In order to
obtain simple Plug & Play configuration for PROFIBUS, the characteristic de-
vice features are defined in an electronic device data sheet (Device Data Base
File, GSD file). The standardized GSD files expand open communication up to
the operator level. By means of the project design tool, which is based on the
GSD files, devices from different manufacturers can be integrated into a bus
system, simply and user-friendly. The GSD files provide a clear and compre-
hensive description of a device type in a precisely defined format. GSD files
are prepared according to the application. The defined data format permits the
project design system to simply read in the GSD files of any PROFIBUS DP
device and automatically use this information when configuring the bus sys-
tem. Already during the project design phase, the project design system can
automatically perform checks for input errors and the consistency of data en-
tered in relation to the entire system.
The GSD files are divided into three sections.
•General specifications
This section contains information on manufacturer and device names,
hardware and software release states, baud rates supported and the
possible time intervals for monitoring times.
•DP master-related specifications
This section contains all the parameters related to DP-master devices only,
such as the maximum number of DP slaves that can be connected, or
upload and download options. This section is not available for slave
devices.
•DP-slave related specifications
This section contains all slave-related specifications, such as the number
and type of the I/O channels, specification of diagnostic texts and
information on the consistency of I/O data.
The GSD format is designed for flexibility. It contains lists, such as the baud
rates supported by the device, as well as the possibility of describing the mod-
ules available in a modular device.

3 Configuring a PROFIBUS system
14
3.2 Configuration procedure
Plug & Play To simplify the configuration of the PROFIBUS system, the master (PLC) is
configured using the PROFIBUS configurator and the GSD files, or in the PLC
through the hardware configurator.
Configuration steps:
- Create GSD file by using the GSD generator
- Load GSD files of the PROFIBUS slaves into the PROFIBUS network
configuration software
- Perform configuration
- Load configuration into the system (e.g. PLC)
The GSD file The characteristic device features of a PROFIBUS slave are specified by the
manufacturer, clearly and comprehensively in a precisely defined format, in the
GSD file (Device Data Base File).
The PROFIBUS
configurator /
hardware
configurator
(PLC)
This software can read in the GSD files for PROFIBUS DP devices of any man-
ufacturer and integrate them for the configuration of the bus system.
Already in the project design phase, the PROFIBUS configurator automatically
checks the files that have been entered for errors in system consistency.
The result of the configuration is read into the master (PLC).

15
3 Configuring a PROFIBUS system
3.3 The GSD generator
3.3.1 General
GSD files for recorders with a PROFIBUS interface are generated by the user
with the aid of the GSD generator.
The recorders with a PROFIBUS interface can send or receive a large variety
of variables (parameters). Since, however, in most applications, only a portion
of these variables will be sent via PROFIBUS, the GSD generator makes a se-
lection of these variables.
After selection of the device, all available variables are shown in the “Parame-
ters“ window. Only after these have been copied to the “Input” or “Output”
window will they later be contained in the GSD file for processing or pre-
processing by the master (PLC).
3.3.2 Operation
File menu Input window
(referred to the master)
Window with available
parameters Output window
(referred to the master)
Status line
Delete entry from input window
Delete entry from output window
Exit program

3 Configuring a PROFIBUS system
16
File menu The file menu can be called up using the Alt-D combination or the left mouse
button. It provides the following options:
New After calling up the function which creates a new
GSD file, the available devices are selected. After se-
lection of the required device, all available parame-
ters are shown in the parameter window.
Open This function opens an existing GSD file.
Save/
Save as This function is available for saving the generated or
altered GSD file.
Diagnosis Using this function, the GSD file can be tested in
conjunction with a PROFIBUS DP adapter from B+W.
Print preview shows the preview of a report1that can be printed.
Print prints a report1.
Standard
settings The language to be used at the next restart of the
program can be selected here.
Exit exits the program.
H1. The report contains additions information for the PLC programmer
(e.g. data type of the selected parameters).
vChapter 3.3.3 “Example report”

17
3 Configuring a PROFIBUS system
3.3.3 Example report
I/O report
Device: RECORDER
Length of inputs (byte): 7
Length of outputs (byte): 4
Inputs
Byte Description Type
-------------------------------------------------------------------------
[ 0] Interface status BYTE
[ 1] int. logic inputs\Bool_Out01 BOOLEAN
[ 2] int. logic inputs\Bool_Out02 BOOLEAN
[ 3] int. analog inputs 16Bit\Int_Out01 INTEGER
[ 5] int. analog inputs 16Bit\Int_Out02 INTEGER
Outputs
Byte Description Type
-------------------------------------------------------------------------
[ 0] ext. analog inputs 16Bit\Int_In01 INTEGER
[ 2] ext. analog inputs 16Bit\Int_In02 INTEGER

3 Configuring a PROFIBUS system
18
Select
parameter If an existing file has been opened, or a new one created, all available parame-
ters are shown in the parameter window.
A click with the left mouse button on the “+” ( ) symbol
or “-” ( ) will extend the parameter list or reduce it.
Click on the parameter with the left mouse button, and, keeping it pressed,
copy it to the input or output window by Drag & Drop.
Remove
parameter Parameters are deleted from the input or output window using the corre-
sponding button.
Device name (editable).
The name is shown in the PLC program
(hardware catalog).
HThe parameter “Interface status” will automatically appear in the input
window and cannot be deleted. It is used for diagnosis of the internal
data transmission in the device and can be requested by the PLC:
0 : internal communication in device is OK
unequal 0 : faulty communication in device

19
3 Configuring a PROFIBUS system
3.4 Connection example
The example below shows the path for the connection of a recorder to a S7
from Siemens.
3.4.1 RECORDER
hConnect the device to the PLC.
hSet the device address.
The device (instrument) address can be selected via the instrument keys or
through the setup program.
3.4.2 GSD generator
hStart up the GSD generator (Example: Start ÎPrograms Î
OEM devices ÎProfibus ÎGSD generator).
hSelect the recorder.
hSelect the variables that are transmitted to the master.

3 Configuring a PROFIBUS system
20
hSave the GSD file in any folder.
3.4.3 PLC configuration
hStart the PLC software.
hCall up the hardware configuration and execute menu command
“Install new GSE”.
The new GSD file is read in and processed, and the recorder is inserted in
the hardware catalog.
PLC with its
components
Bus
This manual suits for next models
1
Table of contents
Other JUMO Voice Recorder manuals

JUMO
JUMO LOGOSCREEN 601 User manual

JUMO
JUMO Logoline 500 junior User manual

JUMO
JUMO LOGOSCREEN Series User manual

JUMO
JUMO LOGOSCREEN cf User manual

JUMO
JUMO LOGOSCREEN 500 User manual

JUMO
JUMO AQUIS touch S User manual

JUMO
JUMO LOGOSCREEN nt User manual

JUMO
JUMO LOGOLINE 500d User manual

JUMO
JUMO LOGOSCREEN 600 Reference guide

JUMO
JUMO LOGOSCREEN nt User manual