Jung eNet FMAS26UP User manual

eNet radio switch/push-button actuator 2-gang mini
eNet
eNet radio switch/push-button actuator 2-gang mini
Art. No. : FMAS26UP
Operating instructions
1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled
persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the devise or
load. In so doing, take all the circuit breakers into account, which support dangerous
voltages to the device and or load.
Danger of electric shock. Device is not suitable for disconnection from supply voltage.
Do not use device as a venetian blind actuator. Otherwise the Venetian drive motor may
be destroyed.
The radio communication takes place via a non-exclusively available transmission path,
and is therefore not suitable for safety-related applications, such as emergency stop and
emergency call.
These instructions are an integral part of the product, and must remain with the end
customer.
2 Device components
Figure 1: Front view
(1) Operating mode switch
(2) Prog button and status LED for output 1
(3) Prog button and status LED for output 2
(4) Measuring points for voltage measurement, terminals rear-mounted
3 Function
Intended use
- Switching of lighting and motors
- Operation with suitable eNet radio transmitters
1/10
82579123
J0082579123 24.06.2016

- Installation in appliance box according to DIN 49073 with a suitable cover
- Installation in surface-mounted housing or panel-mounted housing (accessories) for
suspended ceilings
Product characteristics
- Operating mode switch for switching/push-button actuator switch-over together for both
outputs or parameterisation via eNet server
- Independent switching of two electrical loads
- Status feedback to radio transmitter
- Scene operation possible
- Status indicator via LED
Switching operation:
- Switch-on telegram: Device switches on
- Switch-off telegram: Device switches off
Push-button operation:
- Relay contact remains closed as long as ON or OFF telegrams are being received
- The maximum switch-on time is 60 seconds
Can be set with eNet server for each output:
- Flash function
- Run-on time
- Switch-on delay / switch-off delay
- Operation as NO or NC contacts
- Switch-off warning
- Minimum switching repeat time
- Operation locks
- Continuous on, Continuous off
iIf settings are changed with the eNet server, operation and signalling could vary from what
is described here.
iThe parameter list is in the Internet in the documentation for this device.
Supplementary functions with eNet server:
- Update of the device software
- Repeater function
- Reading of error memory
Behaviour after mains voltage return
The response after mains voltage return can be configured with the eNet server. Default setting:
Off.
4 Operation
Operation is with radio transmitters, please observe the radio transmitter instructions.
5 Information for electrically skilled persons
5.1 Fitting and electrical connection
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before carrying out work on the device or load, disengage all the
corresponding circuit breakers. Cover up live parts in the working environment.
Mounting and connecting actuator
To ensure good transmission quality, keep a sufficient distance from any possible sources of
interference, e.g. metallic surfaces, microwave ovens, hi-fi and TV systems, ballasts or
transformers.
2/10
82579123
J0082579123 24.06.2016
eNet
eNet radio switch/push-button actuator 2-gang mini

Figure 2: Connection example
oConnect loads as shown in the wiring example (figure 2).
oInsert the actuator in the appliance box in such a way that the Prog button and status LED
are visible.
Figure 3: Operating mode switch
Switch position Function
PC Operating mode and parameter set with eNet
server.*)
MPush-button operation
KSwitching operation
*) If the operating mode switch is turned from the position PC to another operating mode, the
parameters are set to the default setting. The settings made with the eNet server will be
lost.
oSet the operating mode switch.
oSwitch on mains voltage.
iThe load can be switched by briefly pressing the Prog button.
Status LED lights up: output switched on
Status-LED off: output switched off
oPerform commissioning.
3/10
82579123
J0082579123 24.06.2016
eNet
eNet radio switch/push-button actuator 2-gang mini

iIn installation positions that are not easily accessible, turn the operating mode switch to
position PC after commissioning and performing a function test. Subsequent changes to
the device settings can thus be carried out with the aid of the eNet-Server without involving
excessive installation work.
oMount the cover.
5.2 Commissioning
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
During commissioning, cover the parts carrying voltage on radio transmitters
and actuators and in their surrounding area.
iThe actuator can also be commissioned with eNet server as an alternative to the
commissioning described here.
Connecting output to radio transmitters
Load is switched off.
oPress the Prog button for longer than 4 seconds.
The load switches on.
The status LED flashes after 4 seconds and the load switches off. The output is in
programming mode for approx. 1 minute.
oSwitch radio transmitter to programming mode (see radio transmitter instructions).
oTrigger telegram on the radio transmitter.
The status LED of the corresponding output is illuminated for 5 seconds.
The output is connected to the radio transmitter. The actuator and radio transmitter exit the
programming mode automatically.
iIf the status LED of the actuator flashes 3 times at 1-second intervals for approx.
5 seconds, then the programming operation was not successful. All the memory locations
in the actuator or radio transmitter are occupied.
iAll On and All Off buttons of a radio transmitter are connected to the actuator automatically
as soon as the first connection to the radio transmitter takes place.
iScene buttons must be connected separately.
Disconnecting connection to a radio transmitter
oCarry out the same steps as when connecting (see Connecting actuator to radio
transmitters).
The status LED flashes quickly for 5 seconds. The actuator is disconnected from the radio
transmitter. The actuator and radio transmitter exit the programming mode automatically.
iIf there several connections or scene buttons for a radio transmitter, all connections must
be disconnected individually.
iAll On and All Off buttons of a radio transmitter are disconnected automatically as soon as
the last connection of the corresponding output to the radio transmitter is disconnected.
Manual disconnection is not possible.
Resetting the output to the factory setting
All connections to radio transmitters are disconnected and parameters are reset to default
setting. If the operating mode switch is on PC, switching operation is set.
iThe connections in the radio transmitters are preserved and must be deleted separately.
Load is switched off.
oPress the Prog button of the corresponding output for at least 20 seconds.
The load switches on.
The status LED flashes after 4 seconds and the load switches off. The status LED flashes
faster after 20 seconds.
4/10
82579123
J0082579123 24.06.2016
eNet
eNet radio switch/push-button actuator 2-gang mini

oRelease Prog button and press briefly once again within 10 seconds.
The status LED flashes more slowly for approx. 5 seconds.
The output is reset to default setting.
Resetting the device to the factory setting
oReset all outputs (see Resetting the output to the default setting).
All the status LEDs flash as soon as the last output is reset. Device is reset to default
setting.
6 Appendix
6.1 Technical data
Rated voltage AC 230V~
Mains frequency 50 / 60Hz
Ambient temperature -25 ... +70°C
Switching current at 35 °C
Ohmic 16A (AC1)
For switching current >10A connecting cable 2.5mm²
Current carrying capacity of device max. 16A
Fluorescent lamps 4AX
Minimum switching current AC 100mA
Contact type µ
Standby power max. 0.5W
Connected load per output at 35°C
Incandescent lamps 2300W
HV halogen lamps 2000W
Tronic transformers 1500W
Inductive transformers 1000VA
HV-LED lamps typical 500W
Compact fl lamp. typical 500W
Fluorescent lamps, uncompensated 920VA
Motors 450VA
Capacitive load 690VA (560 µF)
Connection
single stranded 0.75 ... 4mm²
Finely stranded with conductor sleeve 0.75 ... 2.5mm²
Dimensions Ø×H 53×28 mm
Radio frequency 868.0 ... 868.6MHz
Transmission capacity max. 20mW
Transmitting range in free field typ. 100m
Receiver category 2
6.2 Parameter list
The device parameters can be changed with the eNet server:
Settings window
Device settings
Parameters Setting options, Basic
setting
Explanations
Manual commissioning On, Off
Basic setting: On
Disables manual
commissioning for all device
channels. In the "Off" setting,
the device cannot be reset to
the factory setting.
5/10
82579123
J0082579123 24.06.2016
eNet
eNet radio switch/push-button actuator 2-gang mini

Repeater mode On, Off
Basic setting: Off
In addition to its other
functions, the device can be
used as a repeater. In the
"On" setting, the device
repeats all the received
telegrams.
Settings, channel
Parameters Setting options, Basic
setting
Explanations
Manual commissioning On, Off
Basic setting: On
Blocks manual commissioning
for the device channel. In the
"Off" setting, the device
cannot be reset to the factory
setting.
Operating mode Switching operation
Push-button operation
Flashing
Continuous on
Continuous off
Basic setting: Switching
operation
Switching operation
After switch-on, the device
remains stable in the "On"
state, and stable in the "Off"
state after switch-off.
Push-button operation
The device switches "On"
when any channel button of a
radio transmitter is pressed
and "Off" when the button is
released. It is irrelevant
whether the "On" or "Off"
channel button is pressed.
Flashing
Switch-on starts flashing and
switch-off stops flashing. The
default flash frequency is 1
Hz. This frequency is also the
maximum flash frequency.
The flash frequency can be
changed using parameters.
The parameter "Switch-off
delay" is used for the pulse
time and the parameter
"Switch-on delay" for the
pause time.
Continuous on
The output switches to
continuously "On". All
operations of radio
transmitters and the Prog
button are ignored.
Continuous off
The output switches to
continuously "Off". All
operations of radio
transmitters and the Prog
button are ignored.
Local Operation On, Off
Basic setting: On
Blocks the output for operation
using the Prog button.
6/10
82579123
J0082579123 24.06.2016
eNet
eNet radio switch/push-button actuator 2-gang mini

Manual switch-off of the run-
on time
On, Off
Basic setting: Off
Allows manual switch-off of a
running run-on time. If the
parameter is switched off, then
a switch-off command will also
switch the actuator on. This
parameter is directly
connected to the "Run-on
time" parameter.
Switch-on delay 0 s … 24 h
Basic setting: 0 s
The load switches on after a
delay. Repeated switch-on
commands restart the delay
time. If the load has not yet
been switched on due to the
delay when a switch-off
command comes, then the
load will remain off.
In Flashing operating mode,
the pause time is set using
this parameter.
Comment: The set times apply
to operation using radio
transmitters. The relay is
switched immediately when
the Prog button is pressed.
Switch-off delay 0 s … 24 h
Basic setting: 0 s
The load switches off after a
delay. Repeated switch-off
commands restart the delay
time. If the load has not yet
been switched off due to the
delay when a switch-on
command comes, then the
load will remain on.
In Flashing operating mode,
the pulse times are set using
this parameter.
Comment: The set times apply
to operation using radio
transmitters. The relay is
switched immediately when
the Prog button is pressed.
Run-on time 0 s … 24 h
Basic setting: 0 s
As soon as a run-on time has
been entered, the actuator will
no longer remain on
permanently, but only for the
length of the run-on time. The
run-on time is restarted if
actuation is repeated. This
parameter is directly
connected to the "Manual
switch-off of run-on time"
parameter.
Comment: The set times apply
to operation using radio
transmitters. The relay is
switched immediately when
the Prog button is pressed.
Behaviour after the end of the
disabling function
On
Off
no change
Last value
Basic setting: No change
Behaviour of the output when
a block is removed.
7/10
82579123
J0082579123 24.06.2016
eNet
eNet radio switch/push-button actuator 2-gang mini

Behaviour on voltage return On
Off
Last value
Configured brightness
Basic setting: Off
Defines the behaviour of the
output after voltage return.
Manual saving of the scene
values
On, Off
Basic setting: On
Disables the saving of the
current actuator state (On/Off)
as scene value in an actuator
for a command via a
transmitter.
Timer behaviour, voltage
return
Off
Restart
Basic setting: Off
Specifies whether the timers
for switch-on delay, switch-off
delay and run-on time remain
off after voltage return or
whether they restart. Directly
connected to the parameters
"Switch-on delay", "Switch-off
delay" and "Run-on time".
Switch-off warning On, Off
Basic setting: Off
If the switch-off warning is
active, the light is not switched
off directly. The light goes off
30, 15 and 6 seconds before
permanent switch-off. During
the switch-off warning, a
switch-on telegram effects
direct switch-on. It is not
possible to terminate the time
using a switch-off telegram.
Priority, lock-out protection 0...4
Basic setting: 1
Specifies the priority for
recalling and removing a
scene of type Lock-out
protection for the channel.
Priority, restraint 0...4
Basic setting: 2
Specifies the priority for
recalling and removing a
scene of type Restraint for the
channel.
Priority, wind alarm 0...4
Basic setting: 3
Specifies the priority for
recalling and removing a
scene of type Wind alarm for
the channel.
Priority, sun protection 0...4
Basic setting: 0
Specifies the priority for
recalling and removing a
scene of type Sun protection
for the channel.
Priority, twilight 0...4
Basic setting: 0
Specifies the priority for
recalling and removing a
scene of type Twilight for the
channel.
8/10
82579123
J0082579123 24.06.2016
eNet
eNet radio switch/push-button actuator 2-gang mini

Switch-off on brightness
overshoot
On, Off
Basic setting: On
Allows automatic switch-off
according to the brightness. If
the parameter is On, then the
light controller switches off
automatically when the
brightness setpoint is greatly
exceeded. This parameter is
not yet active, as a light
controller has not yet been
implemented.
Switch-on on brightness
undershoot
On, Off
Basic setting: Off
Allows automatic switch-on
according to the brightness. If
the parameter is On, then the
light controller switches on
automatically when the
brightness setpoint is greatly
undershot. We recommend
only using the parameter in
connection with the parameter
"Switch-off on brightness
overshoot". This parameter is
not yet active, as a light
controller has not yet been
implemented.
Invert switching output On, Off
Basic setting: Off
Inverts the switching output
from NO contact function
(factory setting) to NC contact
function
Minimum switching repeat
time
100 ms ... 10 sec
Basic setting: 100 ms
Limits the switching speed of
the device by increasing the
value, in order to protect the
load, for example. Only when
the set time has elapsed is
switching possible again. The
last command during the
blocking time is executed after
a delay. The switching repeat
time starts after each
switching operation.
Operating hours 0...65535
Basic setting: Current value
The time is counted during
which the load is physically
switched on (relay contact
closed).
This parameter can be reset to
"0", for example after
exchanging the load.
The Reset button is used to
reset the meter to "0". The
device must be programmed
to apply the change.
Information window
During channel selection in the Information window, the following settings can be made or
values displayed.
Display value Explanations
Load state The load can be switched on or off.
Restraint Display of forced position status.
9/10
82579123
J0082579123 24.06.2016
eNet
eNet radio switch/push-button actuator 2-gang mini

Operating hours Display of the operating hours since the last
restart in the Settings window Einstellungen.
iThe value can be updated using the arrow next to the display values.
6.3 Accessories
Mounting adapter for mini housing Art. No. FM-EBG
eNet server for rail mounting Art. No. ENET-SERVER
Albrecht Jung GmbH & Co. KG hereby declares that the radio system type
Art. No. FMAS26UP
corresponds to the directive 2014/53/EU. You can find the full article number on the device. The
complete text of the EU Declaration of Conformity is available under the Internet address:
www.jung.de/ce
6.5 Warranty
The warranty follows about the specialty store in between the legal framework as provided for
by law.
ALBRECHT JUNG GMBH & CO. KG
Volmestraße 1
58579 Schalksmühle
GERMANY
Telefon: +49 2355 806-0
Telefax: +49 2355 806-204
www.jung.de
10/10
82579123
J0082579123 24.06.2016
eNet
eNet radio switch/push-button actuator 2-gang mini
Table of contents
Other Jung Controllers manuals

Jung
Jung Smart Control 7 Operator's manual

Jung
Jung 3210 UP User manual

Jung
Jung FAJ 6 UP User manual

Jung
Jung eNet FM AS 16 REG User manual

Jung
Jung KNX 4093 KRM TS D User manual

Jung
Jung LS TOUCH User manual

Jung
Jung FST 1240 REG User manual

Jung
Jung 1741DSTE User manual

Jung
Jung 1713DSTE User manual

Jung
Jung LB management User manual
Popular Controllers manuals by other brands

BIFFI
BIFFI OLGA Series Installation, operation and maintenance manual

Demasled
Demasled GSM-L10 user manual

SWARCO
SWARCO McCain Omni eX quick start guide

Sinope
Sinope Calypso RM3500ZB installation guide

Johnson Controls
Johnson Controls FEC25 installation instructions

Woodward
Woodward UG40 Installation and operation manual