Kantech IoPass SA-500 User manual

WARNING: This manual contains information on limitations regarding product use
and function and information on the limitations as to liability of the manufacturer.
The entire manual should be carefully read.
IoPass™
Stand-Alone Door Controller
Installation Manual
DN1445-0303 / V.2.22

Warning! Please Read Carefully
Note to Installers
This warning contains vital information. As the only individual in con-
tact with system users, it is your responsibility to bring each item in
this warning to the attention of the users of this system.
System Failures
This system has been carefully designed to be as effective as possible.
There are circumstances, however, involving fire, burglary, or other
types of emergencies where it may not provide protection. Any access
system of any type may be compromised deliberately or may fail to
operate as expected for a variety of reasons. Some but not all of these
reasons may be:
Inadequate Installation
An access system must be installed properly in order to provide ade-
quate protection. Every installation should be evaluated by a qualified
professional to ensure that every access point is adequately controlled
to the building owner’s or facility management’s expectations. Electric
solenoid locks, magnetic locks and gate controllers should be secure
and operate as intended. All latches used with the system should have
adequate holding power (lbs of force) and latch cavity size for the door
weight type (glass, wood, steel) used. A reevaluation must be done
during and after construction activity. An evaluation by the fire and/or
postal carrier is recommended if this service is available. All autho-
rized emergency personnel should be able to gain immediate access to
the premises when required.
Criminal Knowledge
This system contains security features which were known to be effec-
tive at the time of manufacture. It is possible for persons with criminal
intent to develop techniques which reduce the effectiveness of these
features. It is important that a security system be reviewed periodically
to ensure that its features remain effective and that it be updated or
replaced if it is found that it does not provide the protection expected.
Access by Intruders
Intruders may enter through an unprotected access point, circumvent a
sensing device, evade detection by moving through an area of insuffi-
cient coverage, disconnecting a device, immediately following a per-
son through the controlled gate or door, or interfering with the proper
operation of the system.
Power Failure
Control units, intrusion detectors, smoke detectors and many other
security devices require an adequate power supply for proper opera-
tion. If a device operates from batteries, it is possible for the batteries to
fail. Even if the batteries have not failed, they must be charged, in good
condition and installed correctly. If a device operates only by AC
power, any interruption, however brief, will render that device inopera-
tive while it does not have power. Power interruptions of any length are
often accompanied by voltage fluctuations which may damage elec-
tronic equipment such as a security system. After a power interruption
has occurred, immediately conduct a complete system test to ensure
that the system operates as intended.
System Users
A user may not be able to operate the system due to permanent or tem-
porary physical disability, inability to reach the keypad, or unfamiliar-
ity with the correct operation. It is important that all system users be
trained in the correct operation of the system and that they know how
to respond when prompted.
Warning Devices
Warning devices such as sirens, bells, horns, or strobes may not warn
people or waken someone sleeping if there is an intervening wall or
door. If warning devices are located on a different level of the premise,
then it is less likely that the occupants will be alerted or awakened.
Audible warning devices may be interfered with by other noise sources
such as stereos, radios, televisions, air conditioners or other appliances,
or passing traffic. Audible warning devices, however loud, may not be
heard by a hearing-impaired person.
Component Failure
Although every effort has been made to make this system as reliable as
possible, the system may fail to function as intended due to the failure
of a component.
Security and Insurance
Regardless of its capabilities, a system is not a substitute for property
or life insurance. A system also is not a substitute for property owners,
renters, or other occupants to act prudently to prevent or minimize the
harmful effects of an emergency situation.

Limited Warranty
Kantech Systems warrants the original purchaser that for a period of
twelve months from the date of purchase, the product shall be free of
defects in materials and workmanship under normal use. During the
warranty period, Kantech Systems shall, at its option, repair or replace
any defective product upon return of the product to its factory, at no
charge for labour and materials. Any replacement and/or repaired parts
are warranted for the remainder of the original warranty or ninety (90)
days, whichever is longer. The original owner must promptly notify
Kantech Systems in writing that there is defect in material or work-
manship, such written notice to be received in all events prior to expi-
ration of the warranty period.
International Warranty
The warranty for international customers is the same as for any cus-
tomer within Canada and the United States, with the exception that
Kantech Systems shall not be responsible for any customs fees, taxes,
or VAT that may be due.
Warranty Procedure
To obtain service under this warranty, please return the item(s) in ques-
tion to the point of purchase. All authorized distributors and dealers
have a warranty program. Anyone returning goods to Kantech Systems
must first obtain an authorization number. Kantech Systems will not
accept any shipment whatsoever for which prior authorization has not
been obtained.
Conditions to Void Warranty
This warranty applies only to defects in parts and workmanship relat-
ing to normal use. It does not cover:
damage incurred in shipping or handling;
damage caused by disaster such as fire, flood, wind,
earthquake or lightning;
damage due to causes beyond the control of Kantech Sys-
tems such as excessive voltage, mechanical shock or
water damage;
damage caused by unauthorized attachment, alterations,
modifications or foreign objects;
damage caused by peripherals (unless such peripherals
were supplied by Kantech Systems);
defects caused by failure to provide a suitable installation
environment for the products;
damage caused by use of the products for purposes other
than those for which it was designed;
damage from improper maintenance;
damage arising out of any other abuse, mishandling or
improper application of the products.
Kantech Systems’s liability for failure to repair the product under this
warranty after a reasonable number of attempts will be limited to a
replacement of the product, as the exclusive remedy for breach of war-
ranty. Under no circumstances shall Kantech Systems be liable for any
special, incidental, or consequential damages based upon breach of
warranty, breach of contract, negligence, strict liability, or any other
legal theory. Such damages include, but are not limited to, loss of prof-
its, loss of the product or any associated equipment, cost of capital, cost
of substitute or replacement equipment, facilities or services, down
time, purchaser’s time, the claims of third parties, including customers,
and injury to property.
Disclaimer of Warranties
This warranty contains the entire warranty and shall be in lieu of any
and all other warranties, whether expressed or implied (including all
implied warranties of merchantability or fitness for a particular pur-
pose) And of all other obligations or liabilities on the part of Kantech
Systems neither assumes nor authorizes any other person purporting to
act on its behalf to modify or to change this warranty, nor to assume for
it any other warranty or liability concerning this product.
This disclaimer of warranties and limited warranty are governed by the
laws of the state of California, U.S.A.
WARNING: Kantech Systems recommends that the entire system
be completely tested on a regular basis. However, despite frequent
testing, and due to, but not limited to, criminal tampering or elec-
trical disruption, it is possible for this product to fail to perform as
expected.
Out of Warranty Repairs
Kantech Systems will at its option repair or replace out-of-warranty
products which are returned to its factory according to the following
conditions. Anyone returning goods to Kantech Systems must first
obtain an authorization number. Kantech Systems will not accept any
shipment whatsoever for which prior authorization has not been
obtained.
Products which Kantech Systems determines to be repairable will be
repaired and returned. A set fee which Kantech Systems has predeter-
mined and which may be revised from time to time, will be charged for
each unit repaired.
Products which Kantech Systems determines not to be repairable will
be replaced by the nearest equivalent product available at that time.
The current market price of the replacement product will be charged
for each replacement unit.


v
Table of Contents
Section 1 • Introduction to IoPass™ 7
1.1 Product Overview .........................................................7
1.2 About this Manual ........................................................7
1.2.1 - New in this Version ...........................................7
1.2.2 - Record Sheet and Worksheet ............................7
1.3 Features .........................................................................7
1.4 Specifications ................................................................8
Section 2 • Installing and W iring IoPass™ 9
2.1 Unpacking the IoPass Unit ...........................................9
2.2 Required Equipment .....................................................9
2.3 Selecting a Mounting Location .....................................9
2.4 Typical Mounting Diagram ..........................................9
2.5 Mounting the IoPass Unit .............................................9
2.6 Mounting the IoProx P100 Reader .............................10
2.7 Connecting the Door Locking Device ........................10
2.8 Connecting the T.Rex Exit Detector or Exit Button ...10
2.9 Connecting the Door Contact .....................................10
2.10 Connecting the Alarm Annunciator ............................10
2.11 Setting Relay 1 Functions ...........................................11
2.12 Connecting the Power .................................................11
General Wiring Diagram ......................................... 12
Section 3 • Programming IoPass™ - Introduction 13
3.1 IoPass Programming Mode .........................................13
3.2 IoPass Factory Defaults ..............................................13
Section 4 • Programming IoPass™ - Features 15
4.1 Access Mode Selection ...............................................15
4.2 System Passwords ......................................................15
4.3 Card Management .......................................................15
4.4 Relay-1 Functions .......................................................15
4.5 Alarm Relay Functions ...............................................15
4.6 Tamper Alarm Function .............................................15
4.7 Forced Entry Alarm Function .....................................15
4.8 Door Ajar Alarm Function ..........................................16
4.9 PIN Error Alarm Function ..........................................16
4.10 Beeper Key Tone Function .........................................16
4.11 Loop Type Selection ...................................................16
4.12 Strike Relay Activation Timer ....................................16
4.13 Reset to Factory Default .............................................16
4.14 Selecting the System Language ..................................16
Section 5 • Programming IoPass™-Step by Step 17
5.1 Selecting the System Language ..................................17
5.2 Selecting the Access Mode .........................................17
5.3 Managing Passwords ..................................................17
5.3.1 - Modifying the Master Password ......................17
5.3.2 - Modifying the Main Password ........................18
5.3.3 - Modifying the Auxiliary Password .................18
5.3.4 - Modifying the Guard Password .......................18
5.4 Adding & Deleting Cards ...........................................19
5.4.1 - Single Add/Single Deletion .............................19
5.4.2 - Batch Add/Batch Deletion ..............................19
5.4.3 - Adding & Deleting Auxiliary Cards ...............20
5.5 Viewing Cards ............................................................20
5.6 Verifying a Card Number ...........................................21
5.7 Guard Function Configuration (Relay-1) ...................21
5.7.1 - Enabling the Guard Function ..........................21
5.7.2 - Arming / Disarming Quick Reference ............21
5.7.3 - Viewing the Audit Trail ..................................22
5.8 Auxiliary Function Configuration (Relay-1) ..............22
5.8.1 - Enabling the Auxiliary Function .....................22
5.9 Configuring the Duress Function (Relay-1) ...............23
5.9.1 - Enabling the Duress Function .........................23
5.9.2 - Setting the Duress Relay Timer ......................23
5.9.3 - Using the Duress Function ..............................23
5.10 Configuring the Tamper Alarm Function ...................23
5.10.1 - Enabling the Tamper Alarm Function ...........23
5.10.2 - Using the Tamper Alarm Function ................24
5.11 Configuring the Forced Entry Alarm ..........................24
5.11.1 - Enabling/Disabling the Force Entry Alarm
Function ..........................................................24
5.11.2 - Using the Force Entry Function ...................24
5.12 Configuring the Door Ajar Function ..........................24
5.12.1 - Enabling/Disabling the Door Ajar Function .24
5.12.2 - Activating the Alarm Relay on Door Ajar ....25
5.12.3 - Setting the Door Ajar Timer ..........................25
5.12.4 - Using the Door Ajar Function .......................25
5.13 PIN Error Function Configuration ..............................25
5.13.1 - Enabling the PIN Error Function ..................25
5.13.2 - Enabling Auto-Deletion on PIN Error ..........25
5.14 Beeper Key Tone Configuration .................................26
5.15 Loop Type Configuration ...........................................26
5.16 Alarm Relay Timer Configuration .............................26
5.17 Setting the Strike Relay Timer ...................................27
5.18 Resetting the IoPass Unit to Factory Defaults ............27
Quick Reference Programming Table ................... 28
Programming Worksheet ....................................... 29
Card Information Record Sheet ............................. 30
Using the IoPass™ System .................................... 31

vi

Introduction to IoPass™- Product Overview
7
Section 1 •Introduction to IoPass™
1.1 Product Overview
The IoPass is a fully programmable stand-alone access
control system that allows entry using proximity
technology, keypad or both, for up to 5,000 users. Compact
and surface mount, the IoPass is programmed directly from
the keypad. The system is available in two models: with
integrated or external proximity reader.
Easy Programming
Programming is performed directly from the keypad with
visual confirmation of each operation on the 16-character,
2-line LCD display.
Custom Language
IoPass lets you select the system operating language.
Messages are displayed in English, French, Spanish,
German and Dutch.
Lockout on Invalid Password
To prevent unauthorized persons from gaining password
entry by trial and error, the system activates an alarm relay
and/or automatically deletes the card number after five
tries, once the option is selected in the system.
Integrated or External IoProx Proximity Reader
Two IoPass models are available. The integrated proximity
reader model is used for indoor installations. The external
proximity reader model provides a vandal and weather
resistant feature.
Higher Security Provided by Concealed Relay Module
The IoPass relay module is separate from the unit and can
be concealed inside a wall or ceiling. The relay module
acts as a connecting module between the IoPass unit and
the system devices. Devices (door contact, strike, exit
button or detector, alarm annunciator, power, etc.) are
connected to this module.
1.2 About this Manual
This Installation Manual provides installation and
programming instructions for IoPass installers. Please read
this manual carefully before installing or programming the
IoPass unit.
1.2.1 - New in this Version
This version of the manual was released to support the new
revision of the IoPass firmware (as of version 2.22 The
new features include:
1. Reset function: you can clear the IoPass memory and
reset it to factory default values.
2. View function: you can view the next and previous
card (access and auxiliary card) programmed in the
system.
3. Custom language selection: the IoPass unit can be
operated in five languages (English, French, Spanish,
German and Dutch).
4. More transaction in the Audit trail: 380 last
transactions (instead of 10).
5. User PIN required for arming/disarming the unit.
1.2.2 - Record Sheet and Worksheet
You can find the Card Information Record Sheet on
page 30. Please photocopy this form as reference material
so you can keep a record of the cards that are programmed
in the IoPass unit.
You can also find a Programming Worksheet to record
the settings that were modified within the unit. For more
information, refer to the “Quick Reference Programming
Table”, page 28.
1.3 Features
•Proximity type reader with a read range up to 10 cm
(4");
•Capacity to store up to 5,000 user records;
•Large 2-line LCD of 16 characters with back light
feature including power saver function: the backlight
will turn off if inactive for more than 3 minutes;
•Three (3) access mode options:
•Card only (default);
•Card and PIN;
•Card only OR main password.
•Relay 1 offers one of the three (3) following options:
•Ability to arm and disarm an external alarm system;
•Duress function;
•Auxiliary card function.
•Cards can be enrolled/deleted in batch mode;
•The “Alarm Relay”can be activated if:
•an incorrect password is entered five times
consecutively within four (4) minutes;
•the unit detects a forced entry;
•the front cover of the unit is removed (tamper alarm
function);
•the door is opened longer than pre-set time (door ajar
function).
•Last 380 Access Granted card numbers can be viewed
on-screen;
•Audible key tones;
•Strike, alarm and duress relay have a selectable
activation timer (1-255 seconds);
•Selectable door left open timer (1-255 seconds);
•Can be mounted on a standard flush mount electrical
box (vertical or horizontal positioning of the box
acceptable).

Introduction to IoPass™- Specifications
8
1.4 Specifications
•Typical read range—Up to 10 cm (4")1;
•Input voltage—12VDC;
•Current DC maximum—300mA;
•Display—16 characters, 2 lines, LCD with backlight;
•Cards:
•Access cards—5000 cards
•Auxiliary cards—20 cards
•Dimensions (H • W • D):
•cm—15 x 11 x 4.5
•in—5.9 x 4.3 x 1.8
•Weight—380g (13.5oz);
•Case material—Gray ABS (UL 94V-0);
•LED indicator—Bicolor (green/red);
•Operating temperatures—0°C to 50°C (32°F to
122°F);
•Operating humidity—5% to 95% (relative humidity
non-condensing);
•Door contact input—NO or NC selectable;
•Request-to-Exit input—NO or NC selectable;
•Relay output (Strike, Alarm and Relay-1 relay)—Form
C, NO and NC, 3A, 24VDC;
•Strike, Alarm and Relay-1 timer—1 to 255 sec.;
•Door ajar timer—1 to 255 sec.;
•Audit trail—On unit, last 380 transactions;
•Compatible cards—IoProx cards P10SHL, P20DYE
and P40KEY;
•PIN length—4 digits;
•Certifications—CE and FCC.
1. Reduced read range with keytag and Dye-Sub cards.

Installing and Wiring IoPass™- Unpacking the IoPass Unit
9
Section 2 •Installing and Wiring IoPass™
2.1 Unpacking the IoPass Unit
Check that the following parts are in your IoPass package:
•One (1) IoPass unit (SA-500 or SA-600);
•One (1) relay module (SA-RM56 including connectors);
•One (1) hardware kit;
•Ten (10) proximity keytags (P40KEY);
•One (1) IoProx P100 proximity reader (with SA-600
model only).
NOTE: The SA-RM56 relay module comes with all the
necessary connectors to facilitate installation.
2.2 Required Equipment
•Power supply—12VDC, 1A (required);
•Cables (required):
•Between IoPass and reader
2 twisted pairs, solid conductor #22AWG
UNSHIELDED
•Between IoPass and relay module
2 twisted pairs, solid conductor, #22AWG
UNSHIELDED
•Between relay module and power supply
1 pair, solid conductor #22AWG UNSHIELDED
NOTE: Maximum wiring distance between equipment—
150m (500’).
•Door contact (recommended);
•Locking device (required);
•Door alarm or annunciator (recommended);
•T.Rex Request-to-Exit detector (recommended).
2.3 Selecting a Mounting Location
Select a mounting location for the unit using the following
guidelines:
•Close to the door being supervised;
•Away from areas with a large amount of background
noise;
•It is recommended that you mount the unit so that the
LCD is visible to users when requesting access. The top
of the unit should not be higher than 45 to 50 inches
from the floor.
2.4 Typical Mounting Diagram
2.5 Mounting the IoPass Unit
1. Remove the front panel by squeezing the sides of the
unit and sliding forward;
2. Use the provided paper-sticker template to mark the
position of the holes on the wall;
3. Mount the base unit to the wall using four (4) screws
(provided) to secure the unit to the wall;
4. Replace the cover by gently sliding it back on the
unit;
5. The unit offers a tamper alarm protection in case
someone tries to remove the cover. For more
information, please refer to “Configuring the Tamper
Alarm Function”(page 23).

Installing and Wiring IoPass™- Mounting the IoProx P100 Reader
10
2.6 Mounting the IoProx P100 Reader
NOTE: For model SA-600 only.
To mount the IoProx proximity reader, please refer to
installation instructions provided with the reader.
NOTE: If the IoPass unit and P100 reader are not on the
same side of the door, you will not be able to use the “card
and PIN”mode since the keypad of the IoPass unit will not
be accessible to cardholders when a valid card is presented
to the P100 reader.
Wiring Diagram
2.7 Connecting the Door Locking Device
To install the door locking device, refer to the
manufacturer’s instructions. To connect it, refer to the
diagram below.
Wiring Diagram
2.8 Connecting the T.Rex Exit Detector or Exit
Button
To install the T.Rex Exit Detector/push button, refer to the
manufacturer’s instructions. To connect it, refer to the
diagram below.
Wiring Diagram
2.9 Connecting the Door Contact
To install the door contact, refer to the manufacturer’s
instructions. To connect it, refer to the diagram below.
Wiring Diagram
2.10Connecting the Alarm Annunciator
To install the alarm annunciator, refer to the
manufacturer’s instructions. To connect the annunciator
(i.e.: horn, bell, etc.), refer to the diagram below.
Wiring Diagram

Installing and Wiring IoPass™- Setting Relay 1 Functions
11
2.11 Setting Relay 1 Functions
Depending on how you intend to use Relay-1, you will
need to configure the jumpers, located on the SA-RM56
relay module, before you mount it inside the wall.
NOTE: For more information on the relay function, please
refer to “Relay-1 Functions”(page 15).
Jumper Settings:
2.12Connecting the Power
Once all other wiring is complete, power up the unit.
Wiring Diagram
NOTE: Once all connections are finished, you may start to
program the unit. Before you do so, we recommend you
read the section called “Programming IoPass™-
Introduction”(page 13).
Relay-1 Function
Function 1 2 3
DURESS ON OFF OFF
GUARD OFF ON OFF
AUX. CARD OFF OFF ON

Installing and Wiring IoPass™- Connecting the Power
12
General Wiring Diagram

Programming IoPass™- Introduction - IoPass Programming Mode
13
Section 3 •Programming IoPass™- Introduction
3.1 IoPass Programming Mode
To enter the programming mode, you have to enter the 6-
digit Master Password followed by the [#] key. The default
Master Password is [111111].
The LCD will display the following information:
1. ENROLL 2. PASSWD
3. TIMER 4. SYSTEM
From these basic functions, more options are available.
When programming the unit, you need to know that:
•The [*] key is used to either go back to the previous
menu, or delete what was entered.
•The [#] key is used to accept, save the data that was
modified or programmed in the system and quit.
3.2 IoPass Factory Defaults
The factory defaults consists of a series of options that are
automatically set up in the unit as the “basic”system
configuration and can be modified.
Description Factory
Default
To
Modify
Access mode Card only (mode 0) See p. 17
Master password 111111 (always
enabled)
See p. 17
Main password 1234 (always
enabled)
See p. 18
Duress function Disabled See p. 23
Auxiliary function Disabled See p. 22
Auxiliary password 1234567 (default)
when enabled
See p. 18
Guard function Disabled See p. 21
Guard password 123 (default)
when enabled
See p. 18
Tamper alarm func-
tion
Disabled See p. 23
Forced entry alarm
function
Enabled See p. 24
Door ajar Enabled See p. 24
Alarm relay acti-
vated on door ajar
Disabled See p. 24
Incorrect PIN keyed
in incorrectly five
times activates
alarm relay (P-ERR)
Disabled See p. 25
Card auto-deletion
on PIN error (5
times)
Disabled See p. 25
Beeper key tones Enabled See p. 26
Alarm relay activa-
tion timer when
door left open more
then the preset time
(door ajar)
30 seconds (has to
remain open more
than 30 seconds to
trigger alarm
relay—if the func-
tion is enabled)
See p. 24
Duress relay active
time (Relay-1)
10 seconds (when
enabled)
See p. 23
Auxiliary relay
active (Relay-1)
time
3 seconds Cannot be
modified
Guard relay active
time (Relay-1)
Remains activated
until deactivated
manually
Cannot be
modified
Alarm relay active
time
240 seconds
(4 min.)
See p. 26
Strike relay active
time
10 seconds See p. 27
Exit button input
type
Normally Open
(NO)
See p. 26
Door contact type Normally Open
(NO)
See p. 26
Description Factory
Default
To
Modify

Programming IoPass™- Introduction - IoPass Factory Defaults
14

Programming IoPass™- Features - Access Mode Selection
15
Section 4 •Programming IoPass™- Features
4.1 Access Mode Selection
Before you start registering cardholders, you must select
the suitable access mode for your installation.
This function allows the system administrator to decide
how access will be granted to cardholders (card only, with
PIN, etc.). The default access mode is set to “Mode 0 -
Card Only”.
NOTE: For more information on access modes, refer to “5.2
Selecting the Access Mode”, page 17.
4.2 System Passwords
Four passwords can be programmed in the IoPass unit:
•The master password: it is used to program the
IoPass unit, to access the programming mode as well
as to protect the parameters of the unit. For security
purposes, you should modify the master password
before you start programming the IoPass unit.
•The main password is a “global”password that can
be used when access mode “2”is selected.
•Auxiliary password: it used to activate an auxiliary
relay when the auxiliary function is enabled in the
IoPass unit. This password will automatically be
enabled when you enable the auxiliary function.
•The guard password is used to arm or disarm the
connected security system when the guard function
is enabled in the unit. This password will automati-
cally be enabled when you enable the guard func-
tion.
NOTE: For more information on passwords and how to
modify them, refer to “5.3 Managing Passwords”, page 17.
4.3 Card Management
Up to 5,000 user cards (plus 20 auxiliary cards) can be
registered in the IoPass unit. Depending on how many
cards you need to program, you can simply add them one
at a time or use the batch process to add a pre-selected
batch of cards in the unit.
For more information on cards, auxiliary cards and all
functions related to cards, refer to one of the following
sections:
•“5.4 Adding & Deleting Cards”, page 19:
•“5.4.1 - Single Add/Single Deletion”, page 19;
•“5.4.2 - Batch Add/Batch Deletion”, page 19;
•“5.4.3 - Adding & Deleting Auxiliary Cards”, page
20.
•“5.5 Viewing Cards”, page 20;
•“5.6 Verifying a Card Number”, page 21;
4.4 Relay-1 Functions
The “Relay-1”(located on the relay module) function
depends on your requirements.
There are three (3) possibilities, but ONLY ONE can be
configured. Depending on your choice, the jumpers of the
relay module need to be set up accordingly.
•Guard Function—This function is used to arm/dis-
arm the connected security system. Either by using a
password and card, or simply a password to arm the
system.
•Auxiliary Function—This function provides the
ability to activate an external device without unlock-
ing the door. This relay can be used to activate the
lighting control, an HVAC control, or simply to
unlock an auxiliary door.
•Duress Function—In general, this relay would be
connected to an external alarm system’s panic input.
When the duress relay is activated, it triggers the
panic input on the alarm system, sending a signal to
the central station to dispatch the police.
NOTE: For more information on how to configure and use
these features, refer to “5.7 Guard Function Configuration
(Relay-1)”, page 21; to “5.8 Auxiliary Function Configuration
(Relay-1)”, page 22, and to “5.9 Configuring the Duress
Function (Relay-1)”, page 23.
4.5 Alarm Relay Functions
An alarm relay is provided on the relay module. This alarm relay
can be activated by the following events:
•Tamper Alarm (if enabled);
•Forced Entry (enabled by default);
•Door Ajar (if enabled);
•Incorrect Password keyed in five times consecutively
within four (4) minutes (if enabled).
NOTE: The alarm relay is always “enabled”, but users can
configure options that can trigger this relay as detailed in
section “5.16 Alarm Relay Timer Configuration”, page 26
(default 240 seconds).
4.6 Tamper Alarm Function
When enabled, the tamper alarm function automatically
activates the “Alarm Relay”and sound the internal buzzer
when the front panel of the unit is removed.
NOTE: Please refer to “5.10 Configuring the Tamper Alarm
Function”, page 23 for more information.
4.7 Forced Entry Alarm Function
The Forced Entry Alarm Function is already enabled in the
unit. This function automatically activates the “Alarm
Relay”when the door contact detects unauthorized access

Programming IoPass™- Features - Door Ajar Alarm Function
16
(without card or password or both). When this occurs, a
“door forced open”type of event is generated.
NOTE: For more information refer to “5.11 Configuring the
Forced Entry Alarm”, page 24.
4.8 Door Ajar Alarm Function
Already enabled in the unit, this function activates the
“Alarm Relay”when the door is opened longer than the
pre-set time following an access granted operation.
The user can decide if the alarm relay needs to be activated
when this situation occurs.
NOTE: Please refer to “5.12 Configuring the Door Ajar
Function”, page 24 for more information.
4.9 PIN Error Alarm Function
This function, if enabled, will automatically activate the
“Alarm Relay”when a cardholder keys in his PIN
incorrectly five (5) times consecutively within four (4)
minutes.
Furthermore, the card can automatically be deleted (from
the unit’s memory) when this situation occurs.
NOTE: Please refer to “5.13 PIN Error Function
Configuration”, page 25 for more information.
4.10Beeper Key Tone Function
This function, already enabled in the unit, provides an
audible “beep”tone when the keys of the keypad are used.
NOTE: Please refer to “5.14 Beeper Key Tone
Configuration”, page 26 for more information.
4.11 Loop Type Selection
The IoPass unit allows the installer to modify the loop type
of the exit button and door contact.
These normally open contacts can be modified to normally
closed to suit installer’s requirements.
NOTE: For more information refer to “5.15 Loop Type
Configuration”, page 26.
4.12Strike Relay Activation Timer
By default, the locking device relay is pre-set to 10
seconds, meaning that the door will remain unlocked for
that period of time.
The timer can be modified from 1-255 seconds.
NOTE: For more information refer to “5.17 Setting the
Strike Relay Timer”, page 27.
4.13Reset to Factory Default
A reset function is available in the unit. It is used to clear
all configured options and cards from the unit memory
which will bring back the IoPass unit to factory defaults.
To clear the memory, the master password is required.
NOTE: For more information refer to “Resetting the IoPass
Unit to Factory Defaults”(page 27).
4.14Selecting the System Language
IoPass offers users the ability to select the System operating lan-
guage. You can operate the system in English, French, Spanish,
German and Dutch.
NOTE: For more information on setting the system
language, refer to “Selecting the System Language”(page
17).

Programming IoPass™-Step by Step - Selecting the System Language
17
Section 5 •Programming IoPass™-Step by Step
5.1 Selecting the System Language
IoPass offers users the ability to select the System operating lan-
guage. To select the system language:
1. Enter the master password (default is [111111]), fol-
lowed by the [#] key.
2. The LCD displays the following:
1. ENROLL 2. PASSWD
3. TIMER 4. SYSTEM
3. Press [4-System]. The LCD displays:
1. ALARM 2. CHECK
3. MODE 4. OTHER
4. Press [4-Other]. The LCD displays:
1. TONE 2. DURESS
3. MORE 4. LANGUAGE.
5. Press [4-Language]. The LCD displays the current
language. For example, if the IoPass is set to display
messages in English, it will display:
ENGLISH
Press ’1’---Change
6. Press [1] until the desired language is displayed, then
press the [*] or the [#] key. The IoPass unit will start
displaying messages in the selected language.
NOTE: Pressing the [#] key brings you back to the
Welcome message (Ready for card). Pressing the [*] key
changes the display language in the selected language
without going back to the Welcome message.
5.2 Selecting the Access Mode
The access mode is the most important function of the
system. Before you start enrolling cards, you need to
determine how access will be granted to users.
Three (3) access modes are available in the system:
•Mode “0”- Card only - DEFAULT: This mode
only requires the user to present his card to be
granted access.
•Mode “1”- Card and PIN: This mode requires that
the user presents his card and then enters his PIN on
the keypad. Make sure the keypad can be accessed
by cardholders if you are using this mode.
•Mode “2”- Card only OR main password only:
This mode will require that the user presents his card
to the reader to be granted access OR enters his
main password using the keypad to be granted
access.
To Select an Access Mode:
1. Enter the master password (default is [111111]), [#].
NOTE: It is strongly recommended to modify the default
password before programming the unit. To modify the
master password, refer to “Managing Passwords”(page
17).
2. The LCD displays the following:
1. ENROLL 2. PASSWD
3. TIMER 4. SYSTEM
3. Press [4-System]. The LCD displays:
1. ALARM 2. CHECK
3. MODE 4. OTHER
4. Press [3-Mode]. The LCD displays:
1-ACCESS MODE
2-DOOR_INPUT
5. Select [1-Access mode]. The LCD displays:
CURRENT: MODE ? (?=0,1 or 2)
PRESS ’1’ --] CHANGE
6. Press [1] until desired mode is displayed. Pressing
this key will toggle between selections;
7. When the required mode is displayed (0, 1 or 2),
press [#] to save and exit.
5.3 Managing Passwords
Four (4) passwords can be programmed in the IoPass unit.
It is recommended to record system passwords on the
“Quick Reference Programming Table”(page 28), and
keep it in a secure location.
5.3.1 - Modifying the Master Password
The master password is used to access the programming
mode and to protect the parameters of the IoPass
controller.
To Modify the Master Password
1. Enter the master password (default is [111111]), then
[#].
2. The LCD displays the following:
1. ENROLL 2. PASSWD
3. TIMER 4. SYSTEM
3. Press [2-Passwd]. The LCD displays the following:
1. MASTER 2. MAIN
3. AUX.CR 4. GUARD
4. Press [1-Master]. The LCD displays:
Current: 111111
New:
5. Enter the new master password. This password must
be 6 characters.
6. Press [#] to save and exit.

Programming IoPass™-Step by Step - Managing Passwords
18
5.3.2 - Modifying the Main Password
The main password is a “global”password that can be used
when Access mode “2”is selected. This access mode
offers two options:
•Users present the card to the reader, OR
•They enter the main password to gain access.
To Modify the Main Password:
1. Enter the master password (default is [111111]) then
[#]. The LCD displays the following:
1. ENROLL 2. PASSWD
3. TIMER 4. SYSTEM
2. Press [2-Passwd]. The LCD displays the following:
1. MASTER 2. MAIN
3. AUX.CR 4. GUARD
3. Press [2-Main]. The LCD displays the default Main
password:
Current: 1234
New:
4. Enter the new main password. This password must be
4 characters.
5. Press [#] to save and exit.
5.3.3 - Modifying the Auxiliary Password
The auxiliary password is used to activate an auxiliary
relay when the auxiliary function is enabled in the IoPass
unit.
You can either use the auxiliary card OR the auxiliary
password to activate the auxiliary relay.
To Modify the Auxiliary Password:
1. Enter the master password (default is [111111]) then
[#]. The LCD displays the following:
1. ENROLL 2. PASSWD
3. TIMER 4. SYSTEM
2. Press [2-Passwd]. The LCD displays the following:
1. MASTER 2. MAIN
3. AUX.CR 4. GUARD
3. Press [3-Aux.Cr]. The LCD displays the default
password and invites you to enter a new one:
Current: 1234567
New:
4. Enter the new auxiliary password. This password
must be 7 characters.
5. Press [#] to save and exit.
5.3.4 - Modifying the Guard Password
The guard password is used to arm or disarm the connected
security system when the guard function is enabled. The
Guard password is automatically enabled when you enable
the guard function.
To Modify the Guard Password
1. Enter the master password (default is [111111]) then
[#]. The LCD displays the following:
1. ENROLL 2. PASSWD
3. TIMER 4. SYSTEM
2. Press [2-Passwd]. The LCD displays the following:
1. MASTER 2. MAIN
3. AUX.CR 4. GUARD
3. Press [4-Guard]. The LCD displays the default
password and invites you to enter a new one:
Current: 123
New:
4. Enter the new guard password. This password must
be 3 characters.
5. Press [#] to save and exit.

Programming IoPass™-Step by Step - Adding & Deleting Cards
19
5.4 Adding & Deleting Cards
Up to 5,000 cards can be stored in the unit (plus 20
auxiliary cards).
NOTE: Once you have selected the “Access Mode”, you
may start enrolling cards. Otherwise, please refer to
“Access Mode Selection”(page 15).
Use the provided “Card Information Record Sheet”(page
30) to store user information (card number, name and PIN
if applicable). Also, if you are using the PIN feature, you
may want to gather the PIN from cardholders in advance.
All new cards must be enrolled into the unit before access
is allowed. Up to 5,000 cards can be stored in the unit (plus
20 auxiliary cards).
Cards are stored based on their programming sequence
within the unit. If a card that is not enrolled is presented to
the reader, the message INVALID CARD is displayed.
NOTE: Depending on how many cards you need to
program, you can simply add them one at a time or use the
batch process to add a pre-selected batch of cards in the
unit.
If the maximum number of cards (access/auxiliary) has
been reached, the message NO SPACE will be displayed
each time you attempt to add a new card:
5.4.1 - Single Add/Single Deletion
To add/delete a single card:
1. Enter the master password (default is [111111]) fol-
lowed by the [#] key. The LCD displays the follow-
ing:
1. ENROLL 2. PASSWD
3. TIMER 4. SYSTEM
2. Press [1-Enroll]. The LCD displays:
1-ACCESS CARD
2-AUX. CARD
3. Press [1-Access Card]. The LCD displays:
1. PROGRAM CARDS
2. VIEW CARDS
4. Press [1-Program Cards]. The LCD displays:
1. S_ADD 2. S_DEL
3. B_ADD 4. B_DEL
5. Press:
•[1-S_Add] to add a new card, or
•[2-S_Del] to delete a card from the unit.
The LCD displays:
TOTAL CARDS: XX (xx=# of cards in
unit)
CARD NO.__:______
6. There are two ways to enter the card number in the
system:
•You can simply present the card to the reader and the
number will automatically be entered.
•You can type in the number (XX:XXXXX) printed on
the card followed by the [#] sign using the keypad. If
you need to enter special characters (hexadecimal)
see “Special Characters (Hexadecimal)”below, OR
7. Once you have entered the card number, you will see
the following screen:
CARD NO. XX:XXXX
PIN:
OR
ALREADY USED
PIN:
8. To enter the PIN, enter the 4-digit code using the
keypad. Use the [#] key to accept;
NOTE: If you leave the PIN blank, the unit will assume that
no PIN was entered and the user will not be prompted for
his PIN.
9. Once the card has been accepted, the system will
display:
ACCEPTED
10. Following the acceptance message, the unit will
display the add/delete card screen. To add/delete
another card simply repeat steps 5 and up.
11. To exit the programming mode press [#], [#].
5.4.2 - Batch Add/Batch Deletion
Before you can use the batch mode to enroll new cards, it
is essential that the group of cards be numbered
sequentially.
Special Characters (Hexadecimal)
When inputting the card number using the keypad,
you may need to program special characters. You can
do this using hexadecimal digits. The following
hexadecimal digits will insert special characters into
the card number. To program a hexadecimal digit
press [*], then press the number corresponding to the
hexadecimal digit.
•For A press [0]
•For B press [1]
•For C press [2]
•For D press [3]
•For E press [4]
•For F press [5]
If another hexadecimal digit is required, press [*]
again, then press the corresponding number. The
IoPass will return to decimal programming on the next
digit.
Example: To program “4E”, you would enter:
•[4] - programs a “4”
•[*][4] - programs an “E”

Programming IoPass™-Step by Step - Viewing Cards
20
To Add/Delete a group of cards:
1. Enter the master password (default is [111111]) fol-
lowed by the [#] key. The LCD displays the follow-
ing:
1. ENROLL 2. PASSWD
3. TIMER 4. SYSTEM
2. Press [1-Enroll]. The LCD displays:
1-ACCESS CARD
2-AUX. CARD
3. Press [1-Access Card]. The LCD displays:
1. PROGRAM CARDS
2. VIEW CARDS
4. Press [1-Program Cards]. The LCD displays:
1. S_ADD 2. S_DEL
3. B_ADD 4. B_DEL
5. Press [3-B_Add] to add cards or [4-B_Del] to delete a
batch of cards. The LCD displays:
TOTAL CARDS: XX (xx=#cards in unit)
CARD NO.__:______
6. There are two ways to enter the card number in the
system:
•You can simply present the card to the reader and the
number will automatically be entered.
•enter the card number manually followed by the [#].
To enter special characters (hexadecimal) refer to the
section “Special Characters (Hexadecimal)”(page
19).
7. Once you have entered the first card number, the
LCD will display the following screen:
CARD NO. XX:XXXXX
TOTAL:
8. Enter the total number of sequential cards that you
wish to add/delete followed by the [#] key to accept.
The LCD will display:
Processing...xx
For example if you wanted to add 250 cards that are
sequentially numbered you would enter the first card
(lowest) number and then select 250 for the total. If
for example you enter [01:00001] as the first card
number, the system would automatically program
cards [01:00001] to [01:00250] into the system.
NOTE: Cards that were enrolled in the unit using the “batch
mode”will function without having to enter the PIN, even if
the mode is selected. You will have to enter the PINs using
the Single Add feature. When you delete a card, the PIN
associated with the card is also deleted.
5.4.3 - Adding & Deleting Auxiliary Cards
Auxiliary cards are used to activate an external device
without unlocking the door. For more information, refer to
“5.8 Auxiliary Function Configuration (Relay-1)”, page
22.
To Add/delete Auxiliary Cards:
1. Enter the master password (default is [111111]) fol-
lowed by the [#] key. The LCD displays the follow-
ing:
1. ENROLL 2. PASSWD
3. TIMER 4. SYSTEM
2. Press [1-Enroll]. The LCD displays:
1-ACCESS CARD
2-AUX.CARD
3. Press [2-Aux.Card]. The LCD displays:
1. PROGRAM CARDS
2. VIEW CARDS
4. Press [1-Program Cards]. The LCD displays:
1. S_ADD
2. S_DEL
5. Press [1-S_Add] to add a card or [2-S_Del] to delete
a card. The LCD displays:
TOTAL CARDS: XX
CARD NO.__:______
6. Enter the card number in the system by simply
presenting the card to the reader, or by entering the
card number manually followed by the [#]; to enter
special characters refer to “Special Characters
(Hexadecimal)”(page 19).
7. Once you have entered the card number, the LCD
will display:
ACCEPTED
8. Once the card has been accepted, the system will
return to the add/delete card screen. To add or delete
another card simply repeat steps 5 and up. To exit the
programming mode press [#], [#].
5.5 Viewing Cards
You may view the cards that are programmed in the unit’s
memory. These are sorted based or their programming
order within the unit. For example, if cards numbered
01:00000 to 01:00005 are programmed and you delete the
card number 01:00004, when you add a new card (for
example 01:00009), it is placed where the last card was
deleted: 01:00000, 01:00001, 01:00002, 01:00003,
01:00009, 01:00005.
1. Enter the master password (default is [111111]) fol-
lowed by the [#] key. The LCD displays the follow-
ing:
1. ENROLL 2. PASSWD
3. TIMER 4. SYSTEM
2. Press [1-Enroll]. The LCD displays:
1-ACCESS CARD
2-AUX. CARD
This manual suits for next models
1
Table of contents
Other Kantech Controllers manuals

Kantech
Kantech Door Controller Innovative and Powerful... User manual

Kantech
Kantech KT-1 User manual

Kantech
Kantech KT-1 User manual

Kantech
Kantech Door Controller Innovative and Powerful... User manual

Kantech
Kantech KT-1 User manual

Kantech
Kantech KT-NCC User manual

Kantech
Kantech KT-315 User manual

Kantech
Kantech Door Controller Innovative and Powerful... User manual

Kantech
Kantech KT-NCC User manual

Kantech
Kantech Door Controller Innovative and Powerful... User manual