Karassn KS-858G User manual

PSTN&GSM/GPRS Alarm System
User Manual
123
456
789
0#
*
RUN AC PWR ARM EMC
Z1 Z2 Z3 Z4
Z5 Z6 27 Z8
ARM
SEY
OK
RESET
WELCOME

Contents
1.System Introduction-------------------------------------------------------------------------------------- 1
2.Main Functions -------------------------------------------------------------------------------------------- 1
3.System Diagram ------------------------------------------------------------------------------------------- 2
4.System Installation --------------------------------------------------------------------------------------- 3
5.Keypad Programming Instructions --------------------------------------------------------------------- 7
Directive 00: Set/modify installer code ---------------------------------------------------------------- 7
Directive 01-09: Set/modify user's code/master code ---------------------------------------------- 8
Directive 10-14: Set common telephone number ---------------------------------------------------- 8
Directive 15-19: Set zone list to dial corresponding telephone number when alarming ------ 9
Directive 20: Set dialing mode -------------------------------------------------------------------------- 9
Directive 21: Set telephone communication protocol ----------------------------------------------- 9
Directive 22: Set dialing times -------------------------------------------------------------------------- 9
Directive 23: Set ringing times -------------------------------------------------------------------------- 9
Directive 24: Set ADEMCO accounts ------------------------------------------------------------------ 10
Directive 25: Set KS 6+2 accounts --------------------------------------------------------------------- 10
Directive 26: Set wireless siren ------------------------------------------------------------------------- 10
Directive 27: Open/close phone line cut off report function ---------------------------------------- 10
Directive 28: Set timing communication zone list --------------------------------------------------- 10
Directive 30: Set zone attribute ------------------------------------------------------------------------ 10
Directive 31: Set wired zone respond speed --------------------------------------------------------- 10
Directive 32: Set circuit Type For Wired Zone -------------------------------------------------------- 11
Directive 33: Set Arm/Alarm delay time for appointed zones -------------------------------------- 11
Directive 34: Set inner siren alarm duration for appointed zones --------------------------------- 11
Directive 35: Set linkage alarm duration for appointed zones ------------------------------------- 12
Directive 36: Set the first group of Arm/Disarm timer for zone list --------------------------------- 12
Directive 37: Set the second group of Arm/Disarm timer for zone list ---------------------------- 13
Directive 38: Correct Date and Time ------------------------------------------------------------------- 13
Directive 41-48: Partition Register --------------------------------------------------------------------- 13
Directive 49: Query device ID number (Can not be modified) ------------------------------------- 14
Directive 50: Record your message ------------------------------------------------------------------- 14
Directive 51: Periodic test ------------------------------------------------------------------------------- 14
Directive 52: Enable/disable forced arm -------------------------------------------------------------- 14
Directive 53: Enable/disable bypass reporting function -------------------------------------------- 14
Directive 54: Duration of DTMF dialing ---------------------------------------------------------------- 14
Directive 55: Interval time of DTMF dialing ----------------------------------------------------------- 14
Directive 56: Enable/disable GPRS -------------------------------------------------------------------- 14
Directive 57: Set and query IP address of master server ------------------------------------------- 14
Directive 58: Set and query the master server port number ---------------------------------------- 14
Directive 59: Set and query heartbreak time ---------------------------------------------------------- 15
Directive 60: Register/delete remote controllers ----------------------------------------------------- 15
Directive 69: Delete all remote controller -------------------------------------------------------------- 15
Directive 70: Set and query APP binding password -------------------------------------------------- 15
Directive 71-78: Register/delete detectors ------------------------------------------------------------ 15
Directive 80: Set to factory default -------------------------------------------------------------------- 16
6.User Operation Instructions ----------------------------------------------------------------------------- 19
7.APP Programming Instructions ------------------------------------------------------------------------- 24
8.Main Technical Specification ---------------------------------------------------------------------------- 26
9.Operation Precautions ----------------------------------------------------------------------------------- 26
10.Simple Troubleshooting -------------------------------------------------------------------------------- 27

1.Alarm host 1pc 2.Key 2pcs
3.Remote controller 2pcs 4.Radio antenna 1pc
5.GSM antenna 1pc 6. Double-end telephone line 1pc
7.2.2KΩline end Resistance 8pcs 8. Screw 2pcs
9.Self tapping Screw 3pcs 10. Plastic Bolt 3pcs
11.User's Manual 1pc 12. Power lead 1pc
The list of standard full kit
1.Introduction
This is a Telephone&GSM/GPRS dual networking Alarm system with LCD display and 4*4 keyboard, and
there are 16 zones (8 wireless zones and 8 wired zones). It works perfectly with remote controllers (up to 8
remote controllers), various wireless/wired detectors, door sensor, manual call point, and wireless/wired
sirens. And they make up a complete safeguard system to guard against theft, fire and gas leakage,
emergency alarm and so on. This alarm host can be stored up to 5 groups of pre-set telephone numbers
(fixed/mobile telephone number). Once alarm happens, the alarm host will activate siren to make alarm
sound immediately, and dial pre-set telephone numbers at the same time, two-way audio after alarm can
be achieved through the optional GSM&GPRS module; mobile APP receives alarm information, remote
control and programming supported; central monitor software receives alarm information, remote control
and programming supported too. It is widely used in residence, marketplace, finance system and
enterprise.
2. Main Functions:
2.1 Support two-way audio.
2.2 Support mobile APP remote control and programming, inquire record. Support central monitor software.
2.3 It is easy to operate with 4*4 keyboard and lattice LCD display.
2.4 Voice pre-recorded, it guides to operate by sound and correctly reports alarm information when alarming.
2.5 There are 8-wired zones and 8 wireless zones altogether, and they share with the zone number.
2.6 8 sub zones can be programmed independently. And the zone list can be set freely in each sub zone, 8 r
emote controllers and 8 user's codes can separately program for 8 sub zones to ARM/DISARM
independently.
2.7 Code classification, 1 installer code, 1 master code, and 8 common user 's codes. Add number 1 at the
end of master code/ common user's code, and then it will become duress code.
2.8 Support to ADEMCO CONTACT ID communication protocol
2.9 5 groups of telephone numbers (mobile and pager number) can be set. Dialing type (tone or pulse) and
appointed communication zone can be programmed. Arm/disarm, whether to report the information of
system state can be set freely.
2.10 It rushes to report alarm information when alarming (the line should be correctly connected)
2.11 Telephone line cut off or short-circuit will send an alarm. (Indicate sound or siren are optional)
2.12 Dial the telephone number, which connected with alarm host to arm/disarm and start alarm on the spot
function remotely through telephone or mobile phone.
2.13 Automatically learn code between Wireless PIR detector, remote controller and alarm host (each zone
can be learned up to 3 detectors, so it can be learned up to 24 detectors and 8 remote controllers
altogether).
2.14 Wired zone respond speed is 50ms-750ms, and the circuit types (Normal Open, Normal Close and
Line-end resistance) can be set freely to connect with all kinds of wired detector.
2.15 Two timers can be set to Arm/Disarm different zones independently.
2.16 Alarm delay time (00-99 seconds) and Arm delay time (00-99 seconds) can be set for appointed zones.
2.17 It has completed self-check function, alarm host/detector disassembly, AC power cut, backup battery
lower of alarm host and detector will activate alarming.
-1-

2.18 Linkage with wired/wireless Siren
2.19 Latest 30 pieces of alarm record (Alarm information, Month/Day/hour/minute) can be recorded, and
the user and time of the last arm time and the last disarm time can be recorded. If the records are over
30 pieces, then it will delete the preceding ones automatically. User cannot change/delete the records.
2.20 Wireless detector reports to alarm host for on/off. The report will be kept in record by alarm host.
2.21 Both AC220V and 12V/7Ah rechargeable battery supply power. Usually, it charges the backup battery
automatically, and they switch automatically. The backup battery can work for 24 hours or more in
standby time. And it reports when power lower to avoid battery damaging, it adopts limited current
discharge protection circuit.
2.22 Remote control arm and disarm linkage active siren, and the user prompts clearer.
2.23 Arm/disarm and alarm BELL output.
2.24 Supports testing call the monitor center or report to the network central monitor software periodically .
2.25 Support zone malfunction detection and recovery.
2.26 When the zone is malfunction, it can be forced to arm, and report the zone bypass alarm to inform the
user in time that the zone has a malfunction and improve safety.
3.System Diagram
Wired&wireless Siren
APP Control
Central Monitor
Software
Telephone Two-way Audio
Wired PIR
Detector
Wireless PIR
Detector
Microwave+PIR
Detector
Wireless Smoke
Detector
Remote Controller
-2-
IP Camera
Cloud

4.System Installation
Thank you for choosing our products! As you known, any kinds of products, to assure its credibility
and fully display all its functions, it should be installed and used correctly. So we recommend
installing by professional personnel. Otherwise, we will not be responsible for malfunctions caused
by improper installing or use. Please contacts with our local agency if you need our professional
personnel!
4.1 Install preparation
①Firstly, make a scheme of all defense zones according to user' needs, and choose suitable kinds
of detectors.
②Fix the setup places of all fittings, like alarm host detectors and sirens.
③Draw a setup map marking the types and specification of detectors and cable conductors in all
zones, and marking the different usages of all kinds of color lines. Don' use the same color cables in
the different zones of the same system. (The scheme and the map should be filed for maintenance
afterwards)
Note: Consider the factors as follows when making defense scheme and drawing the map.
After making sure the credibility of detector, it should be fixed in hide places, and the alarm host
should be fixed in a place where is easy to reach but not easy to be found, and there should have
sockets nearby, it also should be near to telephone line and within the detector defense zone. Siren
or trumpet should be set in the best place. Emergency button should be set in the most convince
place.
When installing wired detector, the cable should be fixed in hide place, like line groove in ceiling.
Don' use the same color cables in the different zones of the same system.
There should be no big mental or other electrical applicants which can produce interferes (like
television, ir-condition, computer and micro-oven and so on) near to the install place of alarm host
and other wireless telecommunication equipment Otherwise, it will affect its normal wireless
communication function.
Considering all factors, which could cause interferes when adopting wireless detectors and wireless
siren. Usually, in open area, the distance between the above detector, siren and alarm host can
reach to 400m. The alarm host should be set indoors. Otherwise, in the course of transmitting,
wireless signal may be absorbed or weaken by all equipment material indoors. Moreover, other
signals of wireless equipment may make interferes to this transmit signal. Therefore, the
transmitting distance is less than 400m when used indoors.
④.How to connect power lead with alarm host:
lll: Connect it with yellow line of power lead
N: Connect it with brown line of power lead
L: Connect it with blue line of power lead
4.2 Start to install
Connection picture 1
-3-

4.2.1 Machine case installing
*Firstly, take out alarm host form packing box, and open the cap with key.
*Take out circuit board from machine case to avoid damaging it when fixing machine case.
*Make a Pre-mode hole
*Mark the install place of nail on the wall where the alarm host will be fixed.
*Put the cable through pre-mode hole to fix machine case on the wall.
*Return the circuit board and fix it firmly.
Note: The nail mounting the alarm host should be fasten and can bear three times of weight of alarm
host at least.
4.2.2 Ground connection
The alarm host should be connected with ground in order to make anti-lightning strike circuit work
normally.
4.2.3 Control line connection of alarm host
When connecting, the line should be connected strictly according to the different uses of different
color cables. Then spread the line according to the setup map, and lead the cable to the place where
the alarm host will be fixed. Then connect the line end to the alarm host. When connecting, the cable
end should be bared, and the length of bared should be equal to the connect port where would be
inserted. It will cause poor contact if the line inserted is too short; and it will cause short circuit if the
line inserted is too long. If more than two lines should be connected to the same end, then the bared
line should be twisted firmly, then insert them into the hole. After that, screw the screw cap firmly to
bear pulling Strength.
4.2.4 AC connection
The AC is a transformer with 18V, 25-40 VA 500V 60Hz. connect its secondary to the AC end of alarm
host don't connect its primary to the socket controlled by switch. Don't connect it to the circuit with
GFI. After connecting all lines, power it on.
Note: The alarm host will indicate if the AC line cut off for 8 minutes. When there is something wrong
with program system, the alarm host will report that AC is cut off. And the alarm host also will report
that it recovers after recovering for 4 minutes
-4-
AC AC
BELL C SW C AUX C
Z1 C Z2 Z3 C Z4 Z5 C Z6 Z7 C Z8
NC NO COM PHONE LINE TAMPER C
12V
DC
7AH
18V AC
C
25-40VA
50/60HZ
Voltage10-13.5VDC
J11
J14
MAX MIN
SIM
Button
Battery
Connect Socket
Volume Wireless Transceiver
Module
Battery
Black
Red
SMA Connector
Pluggable Module Anti-tamper is only effective
when connecting interfaces
Programmable
Outputting Interface
Tamper
Interface
Black is cathode
Red is anode
Sealed Lead-acid battery
Power Auxiliary Interface
Voltage 10-13.5VDC
Current should not beyond 0.75A
Power-cut Replace
Equipment
Current should not beyond 2A
Wired Siren User phone Line-connection Box
Red is anode
Black is cathode

4.2.5 Backup battery connection
To make sure alarm host will work normally in case the AC cut off, the alarm host should be connected
with storage battery as picture 1. Connecting the red line to the anode, and connecting the black line
to the cathode. It will damage the battery if they are connected wrongly, and it uses 12V 7Ah sealed
storage battery. Don't use non-recharged battery or non-sealed storage battery. We suggest
changing the battery every 3 or 5 years.
Note: The alarm host will alarm if the voltage is lower than 10.5V. Moreover, it will indicate if there is
something wrong with program system, and when voltage is lower than 8.5V, it will cut off the power
supply to protect the battery. Don't connect the battery before finishing all lines connection.
4.2.6 Auxiliary connects with power.
SW and C end are interfaces, which can be cut off. It provides equipment, which need to recover the
cut off state after alarming, with +12V/500mA DC. The representative equipment include glass
–broken sensor and smoke detector. AUX and C end are interfaces, which cannot be cut off. It can
provide wired fitting with +12V/500mA DC power. SW & D C end and AUX & C end are protected by
fast thawing fuse (0.75A, 3AG)
4.2.7 Siren outputting connection
Bell&C is the siren-outputting interface. It provides stable 12V DC power when alarming. Fast
thawing fuse F1 (2A, 3AG) protects the interface circuit. When the current over 2A,then the fuse F1
will melt to cut off the connection between alarm host and signal. Note the polarity before connecting.
The anode is connected to the Bell end, and the cathode is connected to the C end as picture1. Note:
if the fuse melts, please cut all alarm host power. After clearing all obstructions, change the fuse, and
then power it on. Don't change it with large capacity fuse.
4.2.8 Program alliance output connection
NC、NO、COM are program alliance outputting interfaces, they can be programmed to control the
switch of some electrical equipment when there are alarms in some zones . NC is normal close end.
And NO is normal open end, COM is common end. Their interfaces can connect with 1A120V AC/24V
DC. If the power of being controlled equipment over interface loads, the current condenser capability
should be enlarged to avoid damaging the board of alarm host.
4.2.9 wired zones connection
Z1-Z8&C have 8 interfaces connecting with line in wired zones. In zone circuit, Z1-Z8 end is anode, C
end is cathode, so when connecting, please pay attention to the polarity of detector alarm output
interface, So as not to damage other parts of apparatus. But it is no need to distinguish the polarities
when fittings are hand-pressing switch or foot-trampling switch.
Every zone circuit can be programmed singly to different circuit types, like “normal close” 、
“normal open” or “line end resistance”. If it is programmed to be “normal close” or “normal open”,
the detector's alarm outputting interface can be connected directly to the both ends of zone circuit; If
it is programmed to be “line end resistance”, the correspondent zone circuit end should be connected
with 2.2KΩ resistance(other zone circuits unused for the moment also should be connected).
Connection principles: normal open detector should be connected in parallel with 2.2K resistances;
normal close detector should be concatenated with 2.2K resistances (and the resistance should be
as near to detector as possible). In order to avoid zone circuit lines damaged (be cut off or short
circuit), you had better program corresponding zone circuit to be “line end resistance”. If both
resistance down-lead and out-line are connected to the same interface. They should be twisted and
screwed firmly, then inserted into the interface, and screw the snail firmly. If resistance down lead is
wire-wrapped and connected with out-lines, it should be soldered after wire-wrapped connection.
Moreover, the parts of resistance down lead should be as short as possible to avoid short circuit by
touching with other metals after twisted.
When the detector need alarm host to provide power, the anode and cathode of the detector's power
input interface should be separately connected with SW and C interfaces or AUX and C interfaces.
-5-

Connection picture 2. Wired zone line-connection diagram
AUX CZ1 C
+12V G ND ALA RM TAM PER
+ -
2.2K
AUX CZ1 C
+12V GND ALARM TAMPER
+ -
AUX CZ1 C
+12V GND ALARM TAMPER
+ -
Line-connection
ends of alarm host
2.2K
Normal Open End with resistance Normal Close End with resistance Normal Open End/ Normal Close
End without resistance
Line-connection
ends of alarm host
Line-connection
ends of alarm host
Line-connection ends of detector Line-connection ends of detector Line-connection ends of detector
4.2.10 Telephone line connection
PHONE is the interface of telephone incoming line. LINE is extension interface. When alarming, in
order to make alarm host reporting the alarm information to the manage center and user, LINE
in t er fa c es sh o ul d b e con ne c te d w i t h te le ph o ne in c o m in g l i n e. Ex t en s i o n an d oth e r
telecommunication equipment can be connected with PHONE interface. But don't oppositely connect
with incoming line. They should be connected as Connection picture 1.
4.2.11 Anti-tamper line connection
TAMPER&C is the anti-tamper zone interface. It can be set two switches on the case. One is to avoid
opening the cap illegally; the other one is to avoid moving or dissembling the alarm host.
The install steps of anti-tamper switch
①Adjust the anti-tamper switch in the right-under corner of case. As to the switch used to prevent
alarm host dissembling, its short-circuit end should be put through the small hole under board of
case. As to the switch used to prevent cap opening, short-circuit end should be put to outer case.
②concatenate both ani-tamper switches, and then connect the line end with TAMPER&C interface.
4.3 System Debugging
Firstly, check if all lines are connected correctly, next, connect with battery, and cover the case cap.
Then connect with AC power to program. Lastly, test sytem to check if all detector fittings can work
normally and can communicate normally with alarm host or if the alarm host correctly performs all
alarm functions.Then the system installation is finished.
4.4 SIM card installation precautions
Please refer o the alarm host wiring diagram for the installation direction of the SIM card.
①When installing the SIM card, do not touch other components on the PCB to avoid damage to the
alarm host due to static electricity and affect the normal use of the product.
②Pulling the SIM card with power will cause permanent damage to the SIM card! Please remember to
unplug the AC power plug and backup battery plugs before installing the SIM card.
③Ensure that this SIM card has a certain balance of funds, which is used to dial the alarm call or pay
the fee generated when sending the SMS. If you need to connect to the APP or network central
monitor software, the SIM card needs to open the data service.
④Please try to choose a local SIM card with good GSM network signal. The quality of the GSM
network signal directly affects the reliability of the communication module.
⑤Be sure to install the GSM antenna and be sure to tighten the screws on the SMA plug, Because the
installation of GSM antenna directly affects the signal strength and power consumption of the
communication module.
-6-

5. Keypad Programming Instructions
5.1 Preprogramming instructions
1). Program mode
[SET] + [CODE] + [OK] + [Program Directive] + [OK ]+ Directive Index + OK + Reset
Note: [SET] + [CODE ] + [OK ]is used to enter program state. [SET] + [Installer's Code] +
[OK ]is used to enter installer program state. [SET] + [Master's Code ] + [OK ] is used to enter
users program state.
2). The system can enter program state only in disarm state and cannot receive any alarm signals
(including low power of alarm host).
3). In program state, it can't receive any alarm signals.
4). Press “Reset” key can erase the latest inputs. Repeatedly press “Reset” key to return to the last menu.
5). If there are not any operations within 60 seconds in program state, the system will exit automatically.
6). Press “Reset”key to scroll wanted program, or press corresponding program indicative directly.
7). In program state, the system can be programmed continuously.
8) In program state, if you desire to change one Program Directive to the other one, you shall press
“Reset” key ,then enter wanted directives.
5.2 Program Instruction
Enter program state
Panel is in standby state (or repeatedly press “Reset” key to set panel in standby state). Press
[SET]key, the panel will indicate“Enter Code”. LCD display will show as picture 3. You are allowed to
enter Installer Code or Master Code. Then press [OK ]key. “Bi—Bi—”means setup correctly, and enter
program state. LCD display show as picture 4. If the code you input is incorrect, it will indicate that“The
code you entered is incorrect, please re-enter the code”. LCD display will show as picture 3. If wrong code
is entered three times continuously, the panel will occur on-site alarm and keyboard will be locked for one
minute automatically.
[ ] [ ] [ ]
Picture 3 Picture 4
Directive 00: Set or modify installer code
In installer program state, Press[00]+ [OK ]. LCD display will show as picture 5. Enter[new code 6 digits]
+[new code 6 digits] + [OK ]. “Bi—Bi—”means setup correctly. The LCD display will show as picture6. Press
“Reset”key for more programs.
For instance, if you want to change installer code to be “123456”. Please press [00]+ [OK ]+[123456]+
[123456] + [OK ]
Installer Code default is “000000”
Picture 5 Picture 6
-7-

Directive 01-09: Set and modify user code/master code
In installer or master program state:
st
Press[01 ]+[OK ]+[ users code 4 digits ]+[users code 4 digits]+ [OK ] to set the 1 user code
nd
Press[02 ]+[OK ]+[ users code 4 digits ]+[users code 4 digits]+ [OK ] to set the 2 user code
rd
Press[03 ]+[OK ]+[ users code 4 digits ]+[users code 4 digits]+ [OK ] to set the 3 user code
th
Press[04 ]+[OK ]+[ users code 4 digits ]+[users code 4 digits]+ [OK ] to set the 4 user code
th
Press[05 ]+[OK ]+[ users code 4 digits ]+[users code 4 digits]+ [OK ] to set the 5 user code
th
Press[06 ]+[OK ]+[ users code 4 digits ]+[users code 4 digits]+ [OK ] to set the 6 user code
th
Press[07 ]+[OK ]+[ users code 4 digits ]+[users code 4 digits]+ [OK ] to set the 7 user code
th
Press[08 ]+[OK ]+[ users code 4 digits ]+[users code 4 digits]+ [OK ] to set the 8 user code
Press[09 ]+[OK ]+[ master code 4 digits ]+[master code 4 digits]+ [OK ] to set master code
For instance, set the new code “5678” to be the second user code.
Enter installer or master program state:
Press [02 ]+[OK ]+[5678]+[5678]+ [OK ]
The LCD display will show as below.
Picture 7
Note 1:Different user's code can not set to be the same, and also can not be the same as other duress code
Note 2:Press “#” after directive to delete user code
For instance, you want to delete the 8th user code
In installer or master program state, Press [08 ]+[OK ] +[ # ]+[OK ]
Note 3:1-8 user's codes and 1-8 remote controllers are defined to be 1-8 users, and different users can
operate corresponding zone independently.
1234 is master's code and there is no user's code by default.
Directive 10-14: Set alarm phone numbers
In installer program state
Press [ 10 ]+[OK ] +[Phone NO. ]+[OK ]to set the 1st alarm phone number
Press [ 11 ]+[OK ] +[Phone NO. ]+[OK ]to set the 2nd alarm phone number
Press [ 12 ]+[OK ] +[Phone NO. ]+[OK ]to set the 3rd alarm phone number
Press [ 13 ]+[OK ] +[Phone NO. ]+[OK ]to set the 4th alarm phone number
Press [ 14 ]+[OK ] +[Phone NO. ]+[OK ]to set the 5th alarm phone number
Note:
1.Press an “*” for 3 seconds to pause dial. It is used for extension number and semi-pager station. For
instance, alarm phone number 2532182*804. It means dial 2532182 first, and stop for 3 seconds,
then dial 804.
2.Press “#” to delete the appointed alarm number. For instance, only press [ 11 ]+[OK ] +[# ]
+[OK ]to delete the second phone number.
3.Each alarm phone (including *) should not beyond 20 digits.
4.For wrong alarm phone numbers, they can be re-inputting directly. Or delete the wrong ones, and
then input the right number.
For instance, to set the second phone number 2532182, and the extension number is 804.
In installer program state
Press [ 11 ]+[OK ] +[2532182*804 ]+[OK ]
LCD display will show as below
Picture 8
-8-

No stored phone numbers by default
Directive 15-19: Set zone list to dial corresponding telephone number when alarming
How to set self-test report function
In installer program state
st
Press [15]+[OK ] +[appointed zone no.]+[OK ]to set appointed zones to dial the 1 phone number.
nd
Press [16]+[OK ] +[appointed zone no.]+[OK ]to set appointed zones to dial the 2 alarm phone number
rd
Press [17]+[OK ] +[appointed zone no.]+[OK ]to set appointed zones to dial the 3 alarm phone number
th
Press [18]+[OK ] +[appointed zone no.]+[OK ]to set appointed zones to dial the 4 alarm phone number
th
Press [19]+[OK ] +[appointed zone no.]+[OK ]to set appointed zones to dial the 5 alarm phone number
Note: The alarm host can set inform whether or not for Arm/Disarm and malfunction inspection. Code 9 is for Arm/Disarm.
Code 10 is for malfunction inspection (malfunction inspection includes backup power lower of alarm host/detector, AC
power cut off). Input[SET 0]for 10. It will show on LCD.
For instance, you want to set zone 1, 3, 5, 7 to dial the first alarm phone number when there are alarm occur. You can
set as follows:
alarm
Picture 9
In installer program state
Press [15]+[OK ] +[1, 3, 5, 7]+[OK ]
LCD display will show as below
If you want to set 2, 4, 6, 8 zones. When those zones occurs alarm or Armed/Disarmed and panel malfunction inspection
report, it will dial the second alarm phone number automatically.
In installer program state
Press [16]+[OK ] +[2, 4, 6, 8, 9, SET 0 ]+[OK ]
LCD display will show as below
Picture 10
In Ex-factory state, all zones dial all phone numbers except for Arm/Disarm and malfunction inspection.
Directive 21: Set telephone communication Protocol
In installer program state
Press[21]+[OK ] +[x x x x x]+[OK ], x= (0, 1,2,3,4) means communication code, 0 for closed, 1 for GSM
CONTACT ID protocol alarm, 2 for PSTN CONTACT ID protocol alarm, 3 for PSTN audio alarm, 4 for GSM audio alarm.
x x x x x is protocols for 5 alarm phone numbers.
For instance, the first and the second alarm number for PSTN CONTACT ID protocol alarm, the third, forth and fifth
alarm number for GSM audio alarm.
In installer program state
Press[21]+[OK ] +[2 2 4 4 4]+[OK ]
LCD display will show as below
Picture 11
Noted: All phone numbers are set to be PSTN audio alarm by default
Directive 22: Set dialing times
In installer program state,
Press[22]+[OK ] +[x]+[OK ] , x= (1-9)
Note: The dialing times is for alarm phone which was not received successfully
In Ex-factory state, it has been set to be 5 times.
Directive 23: Set ring times
In installer program state
Press[23]+[OK ] +[x x]+[OK ], x x= (05-15)
Note: alarm host receives a remote call, when the ring times arrive, the panel will enter program state , then you can
set remotely.In Ex-factory state, it has been set to be 8 times.
alarm
-9-

Directive 24: Set ADEMCO account
In installer program state,
Press[24]+[OK ] +[Account 4 digits]+[OK ]
Note: when networking with ADEMCO center, the code should be 4 bits (0000-9999)
No account by default
Directive 26: Set wireless siren
In installer program state,
Press [26]+[OK ] +[wireless siren code 8 digits]+[OK ]
Note: the 8 digits siren code is marked at the back of siren
If you want to erase siren code, in installer program state, press [26]+[OK ] +[#]+[OK ]
No wireless siren code by default
Directive 27: Open/Close phone line -cutting report function
In installer program state,
Press[27]+[OK ] +[0 or 1]+[OK ], 0 for close report, 1 for open report.
Close report by default
Directive 30: Set zone attribute
In installer program state,
Press[30]+[OK ] +[xxxxxxxx]+[OK ], x is zone attribute of each zone. 8 x is for 8 zones
X value scale ,you can see attribute table below
Note:
1.Zone attribute depends on detector types.
2.Fire alarm, Gas alarm, Emergency alarm and Medical alarm are treated as 24 hours per day. It is not
control by Arm/Disarm.
3.Vacant zone or no used zone can be bypass.
4.The zone attribute number should be 8 digits
5.If zones are set to doorbell zone in attribute, it is only for door alert, no alarm and can't dial alarm
phone numbers.
All zones attribute are set to be Intrusion alarm by default.
Attribute table
Code Zone Attribute
0 Bypass
1 Fire Alarm
2 Gas Alarm
3 Emergency Alarm
4 Medical Alarm
5 Intrusion Alarm
6 Perimeter
7 Door-bell
Directive 31: Set wired zone respond time
In installer program state,
Press[31]+[OK ] +[xxxxxxxx]+[OK ], X means response time for zone 1 to 8 zone.
X value please see table below
-10-

Code Wired zone respond time
1 50ms
2 (default) 100ms
3 250ms
4 500ms
5 750ms
100ms for all wired zones by default
Directive 32: Set wired zone type
In installer program state,
Press[32]+[OK ] +[xxxxxxxx]+[OK ], X is wired zoned type for zone 1 to 8.
X value see table below
Code Name Wired zone type
1 Normal Open
2 Normal Close
3 End of line Resistance
Note: If you select zone type of end of line resistance, for N/O (Normal Open) device, you have to
connect with a parallel-connection 2.2k resistances. For N/C (Normal Close), you have to concatenate
with a 2.2k resistor in series. (End of line resistance type is recommended for all zones.)
N/O zone type for all zones by default
Directive 33: Set Alarm delay/Arm delay for appointed zones.
In installer program state,
Press[33]+[OK ] +[Alarm delay time][Arm delay time][appointed zones 1-8]+[OK]
Alarm delay time range: 00-99 seconds (2 digits)
Arm delay time range: 00-99 seconds (2 digits)
Zone number range : 1、2、3……8
For instance, if you desire to set zone 1、 3、 5 、7 for alarm delay and arm delay, alarm delay time is
30 seconds; arm delay time is 50 seconds
In installer program state, Press[33]+[OK ] +[30 ][50][1 3 5 7 ]+[OK]. The screen
will show as below
Picture 12
No alarm delay time and arm delay time by default
Directive 34: Set inner siren duration for appointed zones
In installer program state, press[34]+[OK ] +[yy][xx….xxx]+[OK], x means zone number
which ranges from 1to 8,and 9 (telephone line malfunction). The number of “x” should be 9 at most,
yy=(03-99),which is siren alarm output duration (minute)
-11-

For instance, If you desire to set zone 2、 4、 6 and phone line malfunction, built-in siren duration is
30 minutes when it alarms, In install program state,
Press[34]+[OK ] +[30][2 4 6 9]+[OK]
The screen will show as below.
Picture 13
Inner siren duration 20 minutes for all zones by default
No built-in siren for phone line broken by default
Note: The emergency alarm duration of remote controller and anti-tamper alarm duration of detector are
unlimited by the time.
Directive 35: Set linkage alarm output duration for appointed zones.
In installer program state, press[35]+[OK ] +[linkage alarm duration]
[appointed zones.]+[OK]
Linkage alarm duration range: 00-99 minutes (2 digits)
Zone number range: 1、 2、3……9 (9 is for phone line malfunction)
For instance, If you desire to set zone 2、 4、 6 and phone line malfunction when it alarms, Linkage
alarm siren duration is 30 minutes. In install program state, press[35]+[OK ] +[30]
[2 4 6 8 9]+[OK]
The screen will show as below.
Picture 14
Linkage alarm duration 20 minutes for all zones by default,
No linkage alarm for phone line malfunction by default
Directive 36: Set the first timer of Arm/Disarm
In installer program or in master program state,
Press[36]+[OK ] +[Arm time][ Disarm time] [partition No.]+[OK]
Arm time ranges are 4 digits, 2 digits for hour, 2 digits for minute
Disarm time ranges are 4 digits, 2 digits for hour, 2 digits for minute
Partition number range is 1、 2……9. (9 is for all partitions)
For instance, if you desire to arm at 08:00pm, and disarm at 18:00pm for all partitions automatically.
In install program state for all partitions,
Press[36]+[OK ] +[0800][1800][9]+[OK].
The screen will show as below.
Picture 15
Press[36]+[OK ] +[#.]+[OK]to delete the first timer.
Directive 37: Set the second timer for Arm/Disarm
In installer or master program state,
Press[37]+[OK ] +[Arm time] [ Disarm time][Partition no.]+[OK]
-12-

Arm time ranges are 4 digits, 2 digits for hour, 2 digits for minute
Disarm time ranges are 4 digits, 2 digits for hour, 2 digits for minute
Partition number range is 1、 2……9. (9 is for all partitions)
For instance, if you desire to arm at 18:20pm, and disarm at 07:40 am next morning for partition 1, 2
automatically. In install program state for all partitions,
Press[37]+[OK ] +[1820][0740][1 2]+[OK].
The screen will show as below.
Picture 16
Press[37]+[OK] +[#]+[OK]to delete the second timer.
No timer for Arm/Disarm by default
Directive 38: Correct Date and Time
In installer or master program state,
Press[38]+[OK ] +[month][date][hour] [minutes]+[OK]
Two digits is for month, date, hour and minutes each.
Directive 41-48: Partition Register
In installer program state,
Press[41]+[OK ] +[appointed zone no.]+[OK]for the 1st partition
Press[42]+[OK ] +[appointed zone no.]+[OK]for the 2nd partition
Press[43]+[OK ] +[appointed zone no.]+[OK]for the 3rd partition
Press[44]+[OK ] +[appointed zone no.]+[OK]for the 4th partition
Press[45]+[OK ] +[appointed zone no.]+[OK]for the 5th partition
Press[46]+[OK ] +[appointed zone no.]+[OK]for the 6th partition
Press[47]+[OK ] +[appointed zone no.]+[OK]for the 7th partition
Press[48]+[OK ] +[appointed zone no.]+[OK]for the 8th partition
Zone number range is 1, 2, 3,……8
Note:
1.Each zone can be registered repeatedly in different partitions.
2.Delete partitions
3.1-8 users codes and 1-8 remote controllers are defined to be 1-8 users, and different users can
operate corresponding zone independently.
Press[41]+[OK ] +[#]+[OK]to delete the 1st partition
Press[42]+[OK ] +[#]+[OK]to delete the 2nd partition
Press[43]+[OK ] +[#]+[OK]to delete the 3rd partition
Press[44]+[OK ] +[#]+[OK]to delete the 4th partition
Press[45]+[OK ] +[#]+[OK]to delete the 5th partition
Press[46]+[OK ] +[#]+[OK]to delete the 6th partition
Press[47]+[OK ] +[#]+[OK]to delete the 7th partition
Press[48]+[OK ] +[#]+[OK]to delete the 8th partition
For instance, you appointed zone 1, 3, 5, 7 registered in the first partition. In installer or master
program state ,
Press[41]+[OK ] +[1, 3, 5, 7 ]+[OK]for the 1st partition
The screen display will show as below.
-13-

Picture 17
Directive 49: Query device ID number (Can not be modified)
In installer program state,
Press[49]+[OK ], the device ID number of the alarm host will automatically displays on the LCD
screen.(The device ID number is composed of 12 digits or letters)
Directive 50: Record your message
In installer program state,
Press[50]+[OK ]to enter the record menu, and press [0]+[OK ]to start record message for
10 seconds. Close microphone to record and press [OK ]to finish. Press [1]+[OK ]to display
record message. In record menu, press[0]+[OK ]to record repeatedly.
Directive 51: Periodic test
In installer program state,
Press[51]+[OK ]+[xx]+[OK ], xx=(00-99), Set the timer for periodic test reporting. The
range value is 00-99 hours. When it is 00, the periodic test function is turned off.
Note: The alarm host will re-clock every time when the device is powered on or the CPU is reset.
Directive 52: Enable/disable forced arm
In installer program state,
Press[52]+[OK ]+[x]+[OK ], x=(0-1), 0 means disable forced arm, and the wired zone
must be normal or bypassed to be armed. 1 means enable forced arm, and automatic bypass of
abnormal wired zones.
Directive 53: Enable/disable bypass reporting function
In installer program state,
Press[53]+[OK ]+[x]+[OK ], x=(0-1), 0 means disable bypass reporting function, 1 means
enable bypass reporting function and bypass recovery reporting.
Directive 54: Duration of DTMF dialing
In installer program state,
Press[54]+[OK ]+[x]+[OK ], x=(50-250 millisecond), factory default is 60 millisecond
Directive 55: Interval time of DTMF dialing
In installer program state,
Press[55]+[OK ]+[x]+[OK ], x=(50-250 millisecond), factory default is 60 millisecond
Directive 56: Enable/disable GPRS
In installer program state,
Press[56]+[OK ]+[x]+[OK ], x=(0-1), 0 means disable GPRS, 1 means enable GPRS.
Note: factory default is enable, please enable GPRS before connect to network central monitor
software.
Directive 57: Set and query IP address of master server
In installer program state,
Press[57]+[OK ]+[IP address]+[OK ]
For instance, set IP address:120.25.250.113
Enter installer or master program state: Press [57 ]+[OK ]+[120]*[25]* [250]*[113]
+[OK ]
Note: The DNS domain name or IP address can be displayed during the query. Only the IP address
can be set when setting, and the domain name cannot be set.
Directive 58: Set and query the master server port number
In installer program state,
Press[58]+[OK ]+[x]+[OK ], x=(1-65535)
For instance, server port number:9022
Enter installer or master program state: Press [58 ]+[OK ]+[9022]+[OK ]
-14-

Directive 59: Set and query heartbreak time
In installer program state,
Press[59]+[OK ]+[x]+[OK ], x=(10-300)in seconds
Directive 60: Register/delete remote controller
In installer program state,
Press[60]+[OK ]to enter register remote controller menu, and input code number 1 to 8 for
corresponding remote controller and[OK ]key to confirm.
On remote controller registering menu.
st
Press[1]+ [OK]to register the 1 remote controller
nd
Press[2]+ [OK]to register the 2 remote controller
……
Up to 8 remote controllers
If the code is vacant, the screen will show as picture18, if the code have been registered, It will show
as Picture19
Register a remote controller in vacant code, press Arm key on remote controller, “Bi-Bi-” indicate
register successfully. If the code have been registered, there is a “Di—” indicative alert ,in that menu,
Press [#]+[OK]to delete the original register firstly, then register it the same as vacant code.
st
Press [1]+ [OK]+ [#]+ [OK] to delete the 1 remote controller
nd
Press [2]+ [OK]+ [#]+ [OK]to delete the 2 remote controller
….
Up to 8 remote controllers
Note: 1. when learning remote controller, alarm host will recognize automatically to see if this code
has been learned, if this remote controller has been learned, then the alarm host will refuse to learn
this code, and it will make a “Di…”sound.
1.After learning, you should test to see if this code has been learned successfully.
2.1-8 remote controller and 1-8 user's code are defined to be 1-8 users, and they can separately
operate in 1-8 sub zones.
Directive 69: Delete all remote controller
In installer program state,
Press [69]+[OK ] +[#]+[OK]to delete all registered remote controllers.
Picture 19Picture 18
Directive 70: Set and query APP bond password
In installer program state,
Press[70]+[OK ]+[xxxxxx]+[OK ], x=(0-9), password recommended at least 6 digits,
default password please refer to the sticker on the alarm host.
Note: When APP binding a alarm host, it must fill in the correct password to bind successfully.
Directive 71-78: Register/delete sensors
In installer program state,
st
Press[71]+[OK ]to enter the 1 zone register.
st
Press[1]+[OK ]to register the 1 sensor
nd
Press[2]+[OK ]to register the 2 sensor
rd
Press[3]+[OK ]to register the 3 sensor
nd
Press[72]+[OK ]to enter the 2 zone register.
st
Press[1]+[OK ]to register the 1 sensor
nd
Press[2]+[OK ]to register the 2 sensor
rd
Press[3]+[OK ]to register the 3 sensor
……
Up to 8 zone registers
-15-

For instance, register the third sensor in the second zone.
In installer program state,
Press[72]+[OK ]to enter the second zone sensor register. Press [3]+[OK ]to enter the
third code.
Picture20 for vacant code, Picture21 for registered code.
Picture 19Picture 18
Register a sensor in a vacant code and trigger it, Bi-Bi-means register successfully.
If the code has been registered, you have to delete it before register the new sensor. Press[#]+
[OK]to delete previous registered firstly, then register it the same as vacant code.
In installer program state,
Press [79]+[OK ] +[#]+[OK]to delete all registered sensors.
Press[71]+[OK ]+ to enter the 1st zone register.
Press[1]+[OK ]+[#]+[OK ]to delete the 1st sensor
Press[2]+[OK ]+[#]+[OK ]to register the 2nd sensor
Press[3]+[OK ]+[#]+[OK ]to delete the 3rd sensor
Press[72]+[OK ]to enter the 2nd zone register.
Press[1]+[OK ]+[#]+[OK ]to delete the 1st sensor
Press[2]+[OK ]+[#]+[OK ]to delete the 2nd sensor
Press[3]+[OK ]+[#]+[OK ]to delete the 3rd sensor
……
Directive 80: Set to factory default
In installer program state,
Press[80]+[OK ]+[#]+[OK], the alarm host will come back to default state.
5.3 Program Table
Note: Both installer code and master code can be programmed for those marked “*” in remark column.
Others have to be programmed by installer code.
Program
Directive Definition Default
Users
memo Remark
00 Modify installer code 000000
01 Set/delete the 1st user code No *
02 Set/delete the 2nd user code No *
03 Set/delete the 3rd user code No *
04 Set/delete the 4th user code No *
05 Set/delete the 5th user code No *
06 Set/delete the 6th user code No *
07 Set/delete the 7th user code No *
08 Set/delete the 8th ser code No *
09 Modify master code 1234 *
-16-

Program
Directive Definition Default
Users
memo
Remark
10 Set/delete the 1st phone number No
11 Set/delete the 2nd alarm phone number No
12 Set/delete the 3rd alarm phone number No
13 Set/delete the 4th alarm phone number No
14 Set/delete the 5th alarm phone number No
15
16
17
18
19
20 Set dialing type 0 (tone)
21 Set telephone communication protocol 00000
22 Set dialing times 5
23 Set ring times 8
24 Set ADEMCO account No
26 Set wireless siren No
27 Open/close phone line cut report 0(close)
28 Set timing communication zones No
30 Set zone attribute 55555555
31 Set wired zone response speed 22222222
32 Set wiring type 11111111
33 No
34 2012345678
35 2012345678
36 Set the 1st timer for Arm/Disarm No *
37 Set 2nd timer for Arm/Disarm No *
38 Correct Date and Time *
41 12345678
42 12345678
43 12345678
44 12345678
alarm
Set/delete the 1st alarm phone number
for appointed zones
Set/delete the 2nd alarm phone number
for appointed zones
Set/delete the 3rd alarm phone number
for appointed zones
Set/delete the 4th alarm phone number
for appointed zones
Set/delete the 5th alarm phone number
for appointed zones
12345678
12345678
12345678
12345678
12345678
Set alarm delay/Arm delay for appointed zones
Set inner siren duration for appointed zone
Set linkage alarm output for appointed zones
Set/delete the 1st partition for appointed zones
Set/delete the 2nd partition for appointed zones
Set/delete the 3rd partition for appointed zones
Set/delete the 4th partition for appointed zones
-17-

Program
Directive Definition Default
Users
memo
Remark
45 Set/delete the 5th partition for appointed zones 12345678
46 Set/delete the 6th partition for appointed zones 12345678
47 Set/delete the 7th partition for appointed zones 12345678
48 Set/delete the 8th partition for appointed zones 12345678
49 Query device ID number
50 Record message No
51 Periodic test 00
52 Enable/disable forced arm 0
53 Enable/disable bypass reporting function 0
54 Duration of DTMF dialing 60ms
55 Interval time of DTMF dialing 60ms
56 Enable/disable GPRS 1
57 Set and query IP address of master server
58 Set and query the master server port number 9022
59 Set and query heartbreak time 55 seconds
60 Register/delete remote controller No
69 Delete all register remote controllers
70 Set and query APP binding password 6 digits
71 Register/delete sensor in the 1st zone No
72 Register/delete sensor in the 2nd zone No
73 Register/delete sensor in the 3rd zone No
74 Register/delete sensor in the 4th zone No
75 Register/delete sensor in the 5th one No
76 Register/delete sensor in the 6th one No
77 Register/delete sensor in the 7th zone No
78 Register/delete sensor in the 8th zone No
79 Delete all registered sensors
80 Set to factory default
www.karassn110.com
-18-
Table of contents
Other Karassn Security System manuals