Please note that the overview above does not include AC breakers, AC surge protectors (SPD), residual current
devices (RCD), earth / ground cables, or other safety equipment that may be required in the country of
installation. Ensure that the system is installed by a professional according to national electrical safety standards.
Steca Solarix PLI Settings
The following settings refer to the Steca Solarix PLI 5000-48 inverter / charger,
connected to an array of PV modules and the aforementioned PylonTech 48 V
batteries. Please refer to the Solarix PLI manual for further explanation on the
mentioned setting programs:
Maximum charging current:
oProgram 02 set to a value equal to or lower than number of used
US2000B / US2000Bplus / Phantom-S battery packs x 25 A; or the
number of used US3000B battery packs x 37 A.
Example if using 4 pcs. of US2000Bplus: 4 x 25 A = 100 A. Therefore
the maximum charging current must be set to
100 A or lower.
•Battery type:
oProgram 05 User-defined (USE)
•Switch to AC input set-point (relevant when using “SBU” or “Solar first” modes in program 01):
oProgram 12 48 V
•Switch back to solar / battery set-point (relevant when using “SBU” or “Solar first” modes in program 01):
oProgram 13 51 V
Charger source priority (this is assuming you wish to utilise as much solar power as possible, if you do
not, then choose another setting):
o
oProgram 16 Solar first (CSO)
Program 11 (maximum AC input charging current) 2A
The reason “Solar first” is recommended here as opposed to “Only solar”, is that when the
battery is in a low-voltage state and the Solarix PLI switches to AC input / grid operation, the
Solarix PLI inverter’s self-consumption of approximately 50 W is still provided by the battery.
To compensate for this (and thus prevent the battery voltage from dropping too low if there are
prolonged periods without sunshine), it is recommended to charge the battery very slightly
(less than 100 W when setting program 11 to 2A as recommended), when the Solarix PLI is in
AC input / grid mode. This ensures that the battery will not be gradually depleted when the grid
is available and there is no sunshine. Choosing a higher value than 2A would reduce the energy
cost-savings potential from this system.
Steca Solarix PLI 5000-48
Using PylonTech Lithium Battery Packs with the
Steca Solarix PLI 5000-48 Inverter Charger
Latest update: 03.07.2018
Page 2 of 3