KEBCO Combivert R6 User manual

COMBIVERT
GB INSTRUCTION MANUAL Power Supply
and Regenerative Unit
Type R6-S Size 25
Mat.No. Rev.
00R6SEB-KR00 1J

GB This instruction manual describes the power supply and regenerative unit KEB
COMBIVERT R6-S. Before working with the unit the user must become familiar
with it. This especially applies to the knowledge and observance of the following
safety and warning indications. The pictographs used in this instruction manual
have following meaning:
Danger Attention Information
Warning Essential Mea-
sure
Help
Caution Tip

GB - 3
1. Introduction.................................................4
1.1 Preface ............................................................ 4
1.2 Product description ....................................... 4
1.3 Validity and liability........................................ 5
1.4 Copyright ........................................................ 5
1.5 Speciedapplication ..................................... 5
1.5.1 Standard operation........................................... 5
1.5.2 Abnormal operation.......................................... 5
1.6 Unitidentication........................................... 6
2. Safety Instructions .....................................7
2.1 General instructions ...................................... 7
2.2 Transport, storage and installation .............. 7
2.3 Electrical connection ..................................... 8
2.4 EMC Instructions...........................................11
2.5 EMC conform installation.............................11
3. Technical Data ..........................................12
3.1 Overload (OL) function ................................ 13
3.2 Operating conditions ................................... 13
3.3 Accessories .................................................. 14
3.4 Options.......................................................... 14
3.4.1 Ferrite rings .................................................... 15
3.5 Dimensions and weights ............................. 16
3.5.1 Dimensions air-cooled inverter mounting
version............................................................ 16
3.5.2 Commutation reactor/mains choke ................ 17
3.5.3 Side-mountedEMIlter.................................. 18
3.5.4 Synchronization unit....................................... 18
4. Installation.................................................19
4.1 EMC-compatible control cabinet
installation .................................................... 19
4.2 Installation instructions............................... 19
4.3 Connection of the COMBIVERT R6 ............ 20
4.3.1 General description of inverter input
terminals......................................................... 20
4.3.2 Connection terminals of the power circuit ...... 20
4.3.3 Connections of the control board ................... 21
4.3.4 Connection of the synchronization unit .......... 22
4.4 Connection Power Unit R6 .......................... 23
4.4.1
Power supply and regenrative operation at
invertercurrent≤currentofoneCOMBIVERT
R6-S ......................................................................23
4.4.2
Power supply and regenrative operation at inverter
currents≤currentofoneCOMBIVERTR6-S.........24
4.4.3 Power supply and regenerative operation at
parallel operation of up to three R6-S ............ 25
4.4.4 Regenerative operation at parallel operation
of up to three R6-S with decoupling diodes ... 28
4.5 Connection of the control board version S 30
4.5.1 Assignment of the control terminal strip X2A . 30
4.5.2 Assignment of socket X2B ............................. 30
4.5.3 Wiring example .............................................. 31
4.6 Operator ........................................................ 32
Table of Contents
5. Operation of the Unit................................33
5.1 Keyboard....................................................... 33
5.2 Operation with PC und system software
COMBIVIS ..................................................... 33
5.3 Switch-on procedure ................................... 33
5.4 Parameter summary..................................... 35
5.5 Password input ............................................ 36
5.6 Monitoring and analysis parameters.......... 36
5.7 Special adjustments .................................... 40
Appendix A......................................................43
A.1 Dimensioning power supply and
regenerative units ........................................ 43
A.2 DC link capacitors of KEB frequency
inverters ........................................................ 44
A.3 Decoupling diodes ....................................... 44
A.3.1 Assignment .................................................... 44
A.3.2 Dimensions .................................................... 45
Appendix B......................................................46
B.1 Certication .................................................. 46
B.1.1 CE Marking .................................................... 46

GB - 4
Preface
1. Introduction
1.1 Preface
First we would like to welcome you as a customer of the company Karl E. Brinkmann GmbH
and congratulation to the purchase of this product. You have decided for a product on highest
technical niveau.
Theencloseddocumentsaswellasthespeciedhard-andsoftwarearedevelopmentsofthe
Karl E. Brinkmann GmbH. Errors excepted. The Karl E. Brinkmann GmbH has created these
documents, this hard- and software with best the knowledge. We doesn´t accept the guarantee
thattheusergetstheprotwiththisspecications.TheKarlE.BrinkmannGmbHreservesthe
righttochangespecicationswithoutpriornoticeortoinstructthirdpersons.Thislistisnot
exhaustive.
Theusedpictogramshavefollowingsignicance:
Danger
Warning
Caution
Attention
Essential
Discharge Time
Information
Help
Tip
1.2 Product description
This instruction manual describes the power supply and regenerative unit KEB COMBIVERT
R6-S. The COMBIVERT R6-S has the following features.
The supply unit
• converts a three-phase input voltage into DC voltage.
• supplies KEB frequency inverter individually or via DC interconnection.
• can be switched parallel, if higher power supply is required.
• increases the stability of the DC link voltage in the DC interconnection.
The regenerative unit
• feeds back the excess energy from generatoric operation into the supply system.
• reduces the energy demand.
• reduces the heat emission.
• is environmentally friendly and space-saving.
• replaces braking resistor and braking transistor.
• is cost-saving.
The COMBIVERT R6-S is generally protected against overcurrent, ground fault and tempera-
ture. Appropriate dimensioned DC fuses protects the DC link circuit against short-circuit. The
following accessories are necessary for operation with the COMBIVERT R6-S:
• Mains choke for inverter input
• EMIlter(forobservanceofEMCstandard)

GB - 5
Preface
1.3 Validity and liability
Application and use of our units in the target products is outside of our control and the-
refore exclusively in the area of responsibility of the machine manufacturer.
The information contained in the technical documentation, as well as any user-specic advice
in spoken and written and through tests, are made to best of our knowledge and information
about the application. However, they are considered for information only without responsibility.
This also applies to any violation of industrial property rights of a third-party.
Selection of our units in view of their suitability for the intended use must be done generally by
the user.
Inspections and tests can only be done by the machine manufacturer within the framework of
the application. Inspections and tests must be repeated, even if only parts of hardware, soft-
ware or the unit adjustment are modied.
Unauthorized opening and improper tampering can lead to bodily injuries or liability insurances
and this cause loss of the warranty. Original spare parts and authorized accessories by the
manufacturer serve as security. The use of other parts excludes liability for the consequences
arising out of.
The suspension of liability is especially valid also for shutdown damages, lost prot, data loss
or other consequential damages. This is also valid, if we have been referred to the possibility
of such damages.
Should any part of this agreement be invalid for any reason, it is to be replaced with a corre-
sponding text, which is valid and equivalent to the intended meaning. The rest of the agree-
ment shall remain unaected and valid.
1.4 Copyright
The customer may be use the instruction manual as well as further enclosed documents or
parts from it for internal purposes. KEB has the copyrights and they remain eective also to
the full extent.
1.5 Speciedapplication
The COMBIVERT R6-S serves exclusively for the supply of frequency inverters with DC input
and/or regeneration of excess energy into the supply system. The operation of other electrical
consumers is prohibited and can lead to malfunctions or to the destruction of the units.
1.5.1 Standard operation
IftheDClinkvoltageincreasestoavalueabovethepeakvalueofthemainsvoltage(negative
power),feedbackofthecurrentintothemainsoccursautomatically.Themainsvoltageisana-
logmeasured.Thefeedbackoccursinasquare-waveformat,wherebythecurrentowperiod
correspondstothetimesofaB6bridgecircuit.RegenerationisnishediftheDClinkvoltage
decreasesthesupplypeakvoltage(positivepower).
1.5.2 Abnormal operation
When exceeding the permissible limit values for voltage, current or temperature the current
owbetweenDClinkandmainsisblockedduringregeneration.Anappropriateerrormessage
is also displayed during supply. The unit must be disconnected from the supply system or the
load must be switched off in case of overcurrent. This can be done by opening the control re-
lease of the frequency inverter.
At factory setting the modulation is switched off in case of a net phase and/or a synchronisation
line failure and the error message E.nEt is displayed.
Special adjustments from KEB are necessary if the modulation and/or the standard operation
shouldstartagainwithinadenedtimeincaseofreturnofpowersupply.

GB - 6
Preface
1.6 Unitidentication
2 5 . R 6 . s 1 R - 9 0 0 A
Type A: Heatsink(standard)
Design 0: default
reserved 0: default 1: modieddefault
Voltage 9: 3-ph.; 400 V; AC
housing R
Options 1: internal precharging
Control S: 2B.R6
Series R6
Unit size 25

GB - 7
Safety Instructions
2. Safety Instructions
2.1 General instructions
Electric Shock
COMBIVERT R6 power supply und regenerative units contain dangerous voltages which
can cause death or serious injury.
COMBIVERT R6 can be adjusted by way that energy is refeed into the supply system in
case of power failure at generatoric operation. Therefore a dangerous high tension can exist
in the unit after switching off the supply system.
Before working with the unit check the isolation from supply by measurements in the
unit.
Care should be taken to ensure correct and safe operation to minimise risk to personnel and
equipment.
OnlyQualied
Electro-Perso-
nnel
All work from the transport, to installation and start-up as well as maintenance may only be
donebyqualiedpersonnel(IEC364and/orCENELECHD384andIEC-Report664and
notenationalsafetyregulations).Accordingtothismanualqualiedstaffmeansthosewho
are able to recognise and judge the possible dangers based on their technical training and
experience and those with knowledge of the relevant standards and who are familiar with the
eldofpowertransmission.
Observe Stan-
dards
The COMBIVERT R6 must not be started until it is determined that the installation com-
plieswith2006/42/EC(machinedirective)aswellastheEMCdirective(2004/108/EC)(note
EN60204).
TheCOMBIVERTR6meetstherequirementsoftheLow-VoltageDirective2006/95/EC.The
harmonizedstandardoftheseriesEN61800-5-1(VDE0160)isused.
This is a product of limited availability in accordance with IEC 61800-3. This product may
cause radio interference in residential areas. In this case the operator may need to take
corresponding measures.
2.2 Transport, storage and installation
The storage of the COMBIVERT must be done in the original packing. It is to be protected against humidity and
excessive cooling and thermal effect. A long-distance transport must be carried out in the original packing. It is to
besecuredagainstimpactinuence.Observethemarkingonthenalpacking!Afterremovingthenalpacking
the COMBIVERT must be set down on a stable base.
Protect Against
Accidental
Contact
The COMBIVERT R6 must be protected against invalid loading. Components and covers
must not be bent or moved as this may affect insulation distances. The units contain elec-
trostatically endangered components which can be destroyed by inappropriate handling. For
that reason the contact of electronic components and contacts is to be avoided. The equip-
ment must not be switched on if it is damaged as it may no longer comply with mandatory
standards.
Make sure that during installation there is enough minimum clearance and enough cooling.
Climatic conditions must be observed in accordance with the instruction manual.
Hot Surface
Heat sinks can reach temperatures, which can cause burns when touching. If in case of
structural measures a direct contact cannot be avoided, a warning notice "hot surface" must
be mounted at the machine.

GB - 8
Safety Instructions
2.3 Electrical connection
Note Capacitor
Discharge Time
Before any installation and connection work, the system must be switched off and secured.
After clearing the DC link capacitors are still charged with high voltage for a short period of
time. The unit can be worked on again, after it has been switched off for 5 minutes.
Secure
Isolation
The terminals of the control terminal strip are securely isolated in accordance with EN 61800-
5-1. With existing or newly wired circuits the person installing the units or machines must
ensure the EN requirements are met. With frequency inverters that are not isolated from the
supplycircuitallcontrollinesmustbeincludedinotherprotectivemeasures(e.g.double
insulationorshielded,earthedandinsulated).
Voltage With
Respect To
Ground
Connection of the COMBIVERT R6 is only permissible on symmetrical networks with a maxi-
mumlinevoltage(L1,L2,L3)withrespecttoearth(N/PE)of305V.Anisolatingtransformer
mustbeusedforsupplynetworkswhichexceedthisvalue!Theunitsmaybedamagedif
this is not observed.
Earthed Exter-
nal
Conductor
The COMBIVERT R6 can be connected to power systems with earthed external conductors
(e.g.deltapowersystems)ifthefollowingexceptionsapply:
• the control system is no longer regarded as “securely isolated circuit”, further protection
measures are therefore required
• •withthistypeofpowersystem,themax.voltagephase/earthmustnotexceed528V
absolute
• external DC fuses at the DC connections are necessary for the 400 V class. Use the
COMBIVERT R6-S without internal DC fuses.
Stationary
Connection
TheCOMBIVERTR6isdesignedforxedconnectiononlyasdischargecurrentsof>3.5
mAmayoccurespeciallywhenusingEMIlters.InaccordancewithEN61800-5-1the
following cross sections of the protective earth conductor must be used:
Cross-section
of the phase
conductors
Minimum cross-section of the protective earth conductor
<10 mm²
10 mm² CU or
additional connection terminal for a second protective earth conductor
with the same cross-section as the phase conductor
10…16 mm² Protective earth conductor with cross-section as phase conductor
16…35 mm² Protective earth conductor with a cross-section of 16 mm²
>35mm² Protective earth conductor with a cross-section of 50% of the phase
conductor.
Insulation Mea-
surement
Whenperformingan"InsulationTest"or"VoltageTest"onthecompleteelectricalsystem(as
requiredinEN60204-1/VDE0113-1)theinverterandEMI-lterhavetobedisconnected
(becauseofdangerofdestruction).Thisisincompliancewiththegivenstandardbecause
KEB inverter are 100 % voltage tested at manufacturing output routine test. In case of spe-
cial requirements contact KEB for further information.
Different Earth
Potentials
When using components without isolated inputs / outputs, it is necessary that equipotential
bondingexistsbetweenthecomponentstobeconnected(e.g.throughtheequalizer).Disre-
gard can cause destruction of the components by the equalizing currents.

GB - 9
Safety Instructions
Prevent
Disturbances
A trouble-free and safe operation of the COMBIVERT R6 is only guaranteed when the con-
nection instructions below are strictly followed. Incorrect operation or damage may result
from incorrect installation.
• Pay attention to mains voltage.
• Installpowercablesandcontrolcablesseparately(>15cmseparation).
• Use shielded / twisted control lines. Lay shield at one side to COMBIVERT R6-S to
PE!
• Only use suitable circuit elements to control the logic and analog inputs, whose contacts
are rated for extra-low voltages.
• Housing of the COMBIVERT R6 must be well earthed. Screens of larger power cable
must be directly and securely attached to both the inverter PE terminal and the motor
groundterminal.Removepaintnishwherenecessary.
• Ground the cabinet or the system earth star point with the shortest connection to mains
earth(avoidearthloops)
• UseexclusivelythecommutationreactorspeciedbyKEB.
• The average value of the supplied DC current may not exceed the maximum DC
current.
• If several frequency inverters are connected to the COMVIBERT R6-S the max. permis-
sible DC link capacities of all connected frequency inverters must be considered during
supplyoperation(seetechnicaldata).
Automatic Re-
start
The COMBIVERT R6 can be adjusted by such way that the inverter restarts automatically
afteranerrorcase(e.g.brokenphaseline).Systemdesignmusttakethisintoaccount,if
appropriate, and additional monitoring or protective features added where necessary.
Not Short-Cir-
cuit Proof
(Supply)
The COMBIVERT R6 is not short-circuit proof at the power supply input
!IftheI2t-protection
is adapted with a gR fuse, a conditional protection at supply input is possible. The short-
circuit protection at DC output is ensured by internal or external aR respectively gR fuses.
Conditionally
Short-Circuit
Proof
(Feedback)
TheCOMBIVERTR6isconditionallyshort-circuitproof(EN61800-5-1/VDE0160).After
resetting the internal protection devices, the function as directed is guaranteed.
Exception:
• If an earth-leakage fault or short-circuit often occurs at the output, this can lead to a
defect in the unit.
Cyclic Activati-
on And Deacti-
vation
With applications requiring the COMBIVERT R6 to be switched on and off cyclically, maintain
an off-time of at least 5 min. If you require shorter cycle times please contact KEB.

GB - 10
Safety Instructions
RCD (Residual
Current Ope-
rated Circuit-
Breaker)
If personnel protection of the system is required, the COMBIVERT R6-S must be protected
according to EN 61800-5-1:
• 3-phaseinverters(withB6bridge-connectedrectier)byRCMA’swithseparation(used
privileged)orRCD’stypeB(all-currentsensitiveFI’s)
The tripping current should be 300mA or more, in order to avoid a premature triggering by
dischargecurrents(about200mA.Dependentontheload, the length of themotorcable
and the use of a radio interference lter, substantially higher leakage current can occur.
The connection instructions from the manufacturer and the valid local reqirements must be
observed.
Dependentontheavailablemainsform(TN,IT,TT)furtherprotectivemeasuresareneces-
saryinaccordancewithVDEPart4104(Part4;Chapter41).
For example, with TN-mains this protection is made with overcurrent protective devices,
with IT-mains it is insulation monitoring with a pulse-code measuring method. A protective
separation can be used with all mains forms as long as the required power and cable lengths
permit this.
The person setting up the unit must present proof of compatibility before installing the inver-
ter!
Circuit diagram of low voltage distribution (principle of the protective elements)
Mains
to further
sub-divisions
Outlet 1
Outlet 2
Outlet 3
Level1
Level2
type
A
type
A
RCD
type A
sel. T RCMA/
RCD
type B
Isolator
according to
EN 60947-2
To further consumers that do not pre-
vent the tripping of the FI.
To the consumers not
compatible with FI.

GB - 11
EMC Instructions
2.4 EMC Instructions
COMBIVERT R6-S represent electrical equipment designed for use in industrial and commercial units. In accor-
dance with the EMC directive 2006/108/EC, it is not obligatory to mark these devices as they represent compo-
nents to be further processed by the respective machine and unit manufacturer and are not operable indepen-
dently according to the EMC directive. The person installing / operating the machine / unit is obliged to proove the
protective measures demanded by the EMC directive are complied with. The prescribed ratings can usually be
compliedwithwhenusingtheradiointerferencevoltageltersspeciedbyKEB,andwhenobservingthefollowing
measures and installation guidelines.
2.5 EMC conform installation
TheCOMBIVERTR6isdesignedtobeusedinthesecondenvironmentasdenedinEN61800-3(unitwithits
ownsupplytransformer).Takeadditionalmeasureswhenusingitintherstenvironment(residentialandcom-
mercialareaconnectedtopubliclow-voltagemains)!
• Installthecontrolcabinetorsysteminanappropriateandcorrectlyway(seechapter„controlcabinetinstal-
lation“)
• Toavoidcoupled-innoise,separatesupplylines,motorlines,controlanddatalines(low-voltagelevel<48V)
and leave a space of at least 15 cm between them when installing.
• In order to maintain low-resistance high frequency connections, earthing and shielding, as well as other metal-
licconnections(e.g.mountingplate,installedunits)mustbeinmetal-to-metalcontactwiththemountingplate,
overaslargeanareaaspossible.Makegroundconnectionswithasurfaceaslargeaspossible(earthing
strips).
• Only use shielded cable with copper or tin-plated braid, since steel braid is not suitable for high frequency
ranges. The screen must always be installed on the compensating rail and fastened with clips or guided
throughthewallofthehousing.Donotelongatethescreenend(pigtails)withindividualconductors!
• Ifexternalinterferencesuppressionltersareused,thenthesemustbeinstalled as close as possible to
(<30cmfrom)theinterferencesourceandinmetal-to-metalcontactwiththemoutingplate,overaslargean
area as possible.
• Alwaysequipinductive controlelements(contactors,relaysetc.)withsuppressorssuchas varistors,RC-
elements or damping diodes.
• Allconnectionsmustbekeptasshortaspossibleandascloseaspossibletotheearth,asfreeoatinglines
work as active and passive aerials.
• Keepconnectioncablesstraight(donotbundle).Installanon-assignedwireatonesidestotheprotective
earth conductor.
• Theowandreturncircuitmustbetwistedwhenthelinesarenotshielded,inordertodampencommon-mode
noise.
• The cable for phase synchronisation between mains choke and COMBIVERT R6-S may not exceed a line
length of 1 m.
• Furtherinformationsarefoundintheinternet,see„www.keb.de“.

GB - 12
Technical Data
3. Technical Data
Unit size 25
Housing size R
Phases 3
Rated voltage [V] 400
Mains voltage range [V] 305…528 ±0 %
Mains frequency [Hz] 50 / 60 ±2
DC voltage range [VDC]420…747 ±0 %
Regenerative operation
Output rated power [kVA] 153
Rated active power [kW] 140
Max. power output [kVA] 230
Max. active power [kW] 210
Regenerative rated current [A] 221
Regenerative DC current 1) [ADC] 270
Overloadcurrent(E.OL)60s 2) [A] 331
Max. regenerative DC current 60 s [ADC] 405
Power supply operation
Input rated power [kVA] 153
Rated active power [kW] 135
Max. input power [kVA] 230
Max. active power [kW] 202
Rated supply current 3) [A] 221
DC supply current 1) [ADC] 270
Overloadcurrent(E.OL)60s [A] 331
Max. DC supply current 60s [ADC] 405
Overloaddisconnection(E.OL) [%] 160
Overvoltageswitch-off(E.OP) [VDC] 800
Max. permissible DC link capacity 4) [µF] 50000(400Vclass)35000(480Vclass)
Max. permissible total circuit component current
(InOP)[AAC]≤6
Max. permissible mains fuse type gR [A] 315
I2t Integral of the limiting load of the semicon-
ductor [A2s] 39000
Perm.gRfuseSiemensSitor(nodeltapowersystem) 3NE1230-0
Max. permissible DC fuse Siemens Sitor type aR see options
Short-circuitfactorattheconnectionpoint(Smains/SN)<350
Power loss at nominal operating [W] 1300
Max. heat sink temperature [°C] 88
1) Lay two connection cables parallel at a regenerative current > 230 A DC .
2) The overcurrent is specied for 1 minute. The overload cycle is 300 seconds. This corresponds to duty class 2 EN 2‑60146‑01.
3) The current data are based on a fundamental frequency component of g=0,95. The fundamental frequency component or the effective value of
the input current is dependent on load and line supply conditions. At uncontrolled B6 converters the phase angle cosφ1 can be set to one, so the
value of the fundamental frequency components is equal to the value of the power factor.
4) Please contact KEB for higher values.
Voltagestabilizationmustbeactivatedattheinverterifaharmoniclterisused.
The units are not short circuit proof without corresponding dimensioned fuses
Exceeding of the max. rechargeable DC link capacity can lead to a defect.
AloadremovalintheDClinkcirclemaybedoneonlyafterthemessage„ready“.

GB - 13
Technical Data
3.1 Overload (OL) function
Release time [s]
105
110 120 130 140 150 160
100
150
200
250
270
60
Load [%]
3.2 Operating conditions
Standard Standard/
class
Instructions
Denitionaccordingto
EN 61800-2 Inverter product standard:
ratedspecications
EN 61800-5-1 Inverter product standard:
general safety
Site altitude
max. 2000 m above sea level
(withsitealtitudesover1000maderatingof
1 % per 100 m must be taken into considerati-
on)
Ambient conditions during operation
Climate Temperature EN 60721-3-3 3K3
extended to -10…45 °C
(withtemperatureover45°Ctomax.55°Ca
derating of 5 % per 1 K must be taken into con-
sideration)
Humidity 3K3 5…85%(withoutcondensation)
Mechanical Vibration
Track EN 50155 max.amplitudeofavibration1mm(5…13Hz)
max. acceleration amplitude 7 m/s²
(13…200Hz)
Germ.Lloyd Part 7-3
EN 60721-3-3 3M1
Contamination Gas 3C2
Solids 3S2
Ambient conditions during transport
Climate Temperature
EN 60721-3-2
2K3
Humidity 2K3 (withoutcondensation)
Mechanical Vibration 2M1 max.amplitudeofavibration3,5mm(2…9Hz)
max.accelerationamplitude15m/s²(9…200Hz)
Surge 2M1 max. 100 m/s²; 11 ms
Contamination Gas 2C2
Solids 2S2
Ambient conditions for the storage

GB - 14
Technical Data
Climate Temperature
EN 60721-3-1
1K4
Humidity 1K3 (withoutcondensation)
Mechanical Vibration 1M1 max.amplitudeofavibration1mm(5…13Hz)
max.accelerationamplitude7m/s²(13…200Hz)
Surge 1M1 max. 100 m/s²; 11 ms
Contamination Gas 1C2
Solids 1S2
Type of protection EN 60529 IP20
Environment IEC 664-1 Pollution degree 2
Denitionaccordingto EN 61800-3 Inverter product standard: EMC
EMC emitted interference
Cable-based interferences EN 55011 C2 withlter
Radiated interferences EN55011 C2 withlter
Interference immunity
Electro-static discharge EN 61000-4-2 8 kV AD(airdischarge)andCD(contactdischarge)
Burst - control lines + bus EN 61000-4-4 2 kV
Burst - mains supply EN 61000-4-4 4 kV
Surge - mains supply EN 61000-4-5 1 / 2 kV Phase-phase / phase-ground
Immunity to conducted
disturbances,
induced by radio-frequency
elds
EN 61000-4-6 10 V 0,15-80 MHz
Electromagneticelds EN 61000-4-3 10 V/m
Voltage variation /
voltage drop EN 61000-2-1 +10 %, -15 %; 90 %
Voltage unsymmetries /
Frequency changes EN 61000-2-4 3 %; 2 %
3.3 Accessories
Unit size 25
Rated voltage 400 V
Commutation reactor
25Z1B04-1000
150%max.short-termoverload(regenerativemode)
150%max.short-termoverload(supplymode)
Synchronization unit
00R6940-2409
Control cabinet installation; max. distance to
thecommutationchoke/harmoniclter1m
Patch cable
00F50C3-4010
Length1m
for connection of the synchronization unit with R6 regenerative unit
3.4 Options
Unit size 25
Mainslter 25E4T60-1001
in accordance with EN 61800-3
LimitclassC2(onlywithferriterings)
LimitclassC1(onconsultationwithKEB)
DC fuses 1000 V/500A Mat.no. 009025H-3679
Harmoniclter
25Z1C04-1000
Theoverloadcurrentreducesatcertainmainsconditions!Pleasecontact
KEB for data to the THD value at regenerative operation in accordance
with EN 61800-2-12.
Operators Digital operator, Interface operator
Bus operators CAN,ProBus,InterBus,EtherCAT,EhterNet,Sercos,ModBus,Device-
Net, HSP5

GB - 15
Technical Data
3.4.1 Ferrite rings
Ferrite rings are used for the reduction of the cable-based and radiated interferences. For a
high damping, the ferrite rings are attached as close as possible to the interference source,
i.e. at the DC and at the motor output terminals of the frequency inverter. The conductors must
passed through the ferrite core for the use as current-compensated choke. PE must be passed
outside. Further information can be taken from the provided documentation. Which ferrite ring
shall be used is dependent on the used cable cross-section.
Part number Nominal size in mm Inside diameter in mm
0090396-2621 R 42/26/18 24,9
0090390-5241 R 56/32/18 29,5
0090395-3820 R 63/38/25 36,0
0090395-5222 R 87/54/30 54,5
0090395-5520 R 102/66/15 64,5

GB - 16
Technical Data - Dimensions and Weights
3.5 Dimensions and weights
3.5.1 Dimensions air-cooled inverter mounting version
Design Weight
Air-cooled heat sink 25 kg
357
340
495 12,5
11
520
300

GB - 17
Technical Data - Dimensions and Weights
3.5.2 Commutation reactor/mains choke
316
222
153
234
292
200
113
10
16
d
PE
Mat.-number Inductance Irated PV Frequency Weight
mH [A] [W] [Hz] [kg]
25Z1B04-1000 0,133 221 265 45…65 30
Technical data of the connection terminals Max. tightening torque
PE M8 Stay bolt for ring thimble 25 Nm 200 lb inch
D Ø8 Drilling for screw M8

GB - 18
Technical Data - Dimensions and Weights
3.5.3 Side-mountedEMIlter
598
574
20
200
240
1000
PE-Bolzen M10
LINE
INVERTER
3x480V +5% AC/50-60Hz
D-32677 Barntrup
Karl E. Brinkmann GmbH
25.E4.T60-1001
HPF:-25 C - +85 C
250A @ T=45 C
HF-FILTER
630
500
80
110
Mat.-number
Urated Irated PVInterference sup-
pression level/ frated
Weight
[V] [A] [W] Linelength [Hz] [kg]
25E4T60-1001 3x480 250 50 C2 / 30 m 50/60 16
Technical data of the connection terminals/cable Max. tightening torque
PE M10 Stay bolt for ring thimble 37 Nm 320 lb inch
Connection cable eachwith3x70mm²(AWG2/0)
3.5.4 Synchronization unit
171
144 48
77
20
M4M6
8
12
Ø8
Mat.-number 00R6940-2409 Weight 0,65 kg
Technical data of the connection terminals Max. tightening torque
PE M4 Stay bolt for ring thimble 1,3 Nm 12 lb inch
PE M6 4,5 Nm 40 lb inch

GB - 19
Installation
4. Installation
4.1 EMC-compatible control cabinet installation
1 Main fuse
150 mm
30 mm
150 mm
1
2
8
7
10b 9
10c
10a
11
11a
12
4
5
3/6
2 Main contactor
3Harmoniclter(or6)
4 COMBIVERT R6
5Side-mountedEMIlter(≥size25)
Sub-mountedEMIlter(≤size19)
6Commutationreactor(or3)
7 Frequency inverter
8 if necessary external DC fuses
9 Motor lines
10 A ProtectiveEarth(PE)onthemounting
plate power circuit
10b ProtectiveEarth(PE)onthemounting
plate control circuit
10c Equipotential bonding with the
housing earth
11 Mains connection power circuit
11 A Mains connection control circuit
12 Control lines
Largeareacontactatthemounting
plate
Control circuit Power circuit Directionofthecoolingns
4.2 Installation instructions
•Stationarily install and earth COMBIVERT.
•The device must not be permeated by mist or water.
•Allowforsufcientheatdissipationifinstalledinadust-proofhousing.
•Install the COMBIVERT in an appropriate housing in accordance with the local regula-
tions when operating it in explosion-endangered spaces.
•Protect COMBIVERT against conductive and aggressive gases and liquids.
•The lines of the R6-S commutation reactor must be limiting to 50 cm.
•The frequency inverters must be placed in the immediate environment of the R6-S.

GB - 20
Connection Terminals
4.3 Connection of the COMBIVERT R6
4.3.1 General description of inverter input terminals
Starting current limiting
WhenconnectinginverterstoaDCbuspayattentiontotheinternalwiringoftheDCvoltageinputs!
Inverters that directly output the DC link bus to the DC terminals must be integrated into the DC bus by
waythatthesupplyunit(s)limitthestartingcurrent.Theprechargingmustbecompletedwithintense-
conds.10
Maximum DC link capacity
The maximum DC link capacity can be calculated by adding the DC link capacities of all inverters in the
DCbus.Atableforthiscanbefoundintheappendix.Thesupplysource(supplyunitorinverterwithAC
input)mustbesuitableforthisvalue.
Picture 4.3.1 General description of input terminals at KEB inverters
Terminals Description of terminals at KEB inverters
++, – – DC voltage input with starting current limiting; usable as output only if all units supplied by the DC
bus have a starting current limiting at the DC voltage input.
+(PA),- DC voltage output with starting current limiting; usable as input only if the starting current is limited
by the supply source.
PA, PB Connection for braking resistor; optionally only if a braking transistor is installed
L1,L2,L3 Mains input 3-phase
Type A1: AC/DC inverter Type B1: AC inverter Type C1: DC inverter
+
++
--
L1
L2
L3
+PA
-
L1
L2
L3
+
+
++
--
Type A2: AC/DC inverter Type B2: AC inverter Type C2: DC inverter
+
++
--
L1
L2
L3
+PA
-
L1
L2
L3
+
+
++
--
This type can be supplied by mains
and by DC circuit. The starting current
limitation is designed after the input
terminals. When used as output par-
allel connected inverters must have
an own starting current limiting at the
DC voltage input.
This type can be supplied by mains.
In consideration of the DC link capaci-
ty the DC voltage terminals can be
used as output. When used as input
ensure that the starting current is
externally limited.
This type is only a DC inverter with
starting current limiting. The DC in-
verter can be combined with all other
types in consideration of the maxi-
mum DC link capacity.
Other manuals for Combivert R6
4
Table of contents
Other KEBCO Power Supply manuals

KEBCO
KEBCO combivert R6-S User manual

KEBCO
KEBCO combivert R6-S User manual

KEBCO
KEBCO combivert R6-S User manual

KEBCO
KEBCO COMBIVERT F5 User manual

KEBCO
KEBCO COMBIVERT R5-C User manual

KEBCO
KEBCO Combivert R6 User manual

KEBCO
KEBCO combivert R6-S User manual

KEBCO
KEBCO Combivert R6 User manual

KEBCO
KEBCO Combivert R6 User manual