KEBCO Combivert R6 User manual

COMBIVERT
INSTRUCTION MANUAL Power Supply and Regenerative
Unit
Type R6-N Size 15/19
Original manual
Document Part Version
20116581 ENG 02


Inhaltsverzeichnis
1. Preface............................................................................................................. 6
1.1 Information on special measures.......................................................................................6
1.2 Documentation.....................................................................................................................6
1.3 Validity and liability .............................................................................................................7
1.4 Copyright..............................................................................................................................7
1.5 Speciedapplication...........................................................................................................8
1.5.1 Standard operation ................................................................................................................8
1.5.2 Abnormal operation ...............................................................................................................9
1.6 Product description.............................................................................................................9
1.7 Part code ............................................................................................................................10
2. Safety Instructions ....................................................................................... 11
2.1 General instructions.......................................................................................................... 11
2.2 Transport, storage and installation..................................................................................12
2.3 Electrical connection.........................................................................................................12
2.4 EMC instructions ...............................................................................................................16
2.5 EMC conform installation .................................................................................................16
3. Technical Data .............................................................................................. 17
3.1 Standard unit size..............................................................................................................17
3.2 Special unit Peak Power ...................................................................................................18
3.3 Overload (OL) function......................................................................................................19
3.4 Operating conditions.........................................................................................................20
3.5 Accessories........................................................................................................................21
3.6 Options ...............................................................................................................................21
3.7 Dimensions and weights...................................................................................................22
3.7.1 COMBIVERT R6-N ..............................................................................................................22
3.7.2 Commutation reactor ...........................................................................................................22
3.7.3 Radiointerferencelter........................................................................................................23
3.7.4 Fuse holder with cover.........................................................................................................25
3.7.5 Ferrite rings..........................................................................................................................25
4. Installation..................................................................................................... 26
4.1 EMC-compatible control cabinet installation..................................................................26
4.2 Installation instructions ....................................................................................................26
4.3 Connection of the COMBIVERT R6-N ..............................................................................27
4.3.1 General description of inverter input terminals ....................................................................27
4.3.2 Connection terminals of the R6-N power circuit ..................................................................29
4.3.3 Terminalscommutationreactor/harmoniclter...................................................................30
4.4 Connection Power Unit R6-N............................................................................................31
4.4.1 Powersupplyandregenerativeoperationatinvertercurrent≤currentofone
COMBIVERT R6-N ..............................................................................................................31
4.4.2 Powersupplyandregenerativeoperationatinvertercurrent≤currentofone
COMBIVERT R6-N ..............................................................................................................31
4.4.3 Powersupplyandregenerativeoperationatinvertercurrents≤currentofoneR6-N.........32
3
Table of Contents

4.4.4 Regenerative operation with decoupling diodes ..................................................................33
4.4.5 Regenerative operation at parallel operation of up to two R6-N with decoupling diodes ....36
4.5 Connection of the control board version N.....................................................................38
4.5.1 Assignment of the control terminal strip X2A.......................................................................38
4.5.2 Assignment of the sockets X2D...........................................................................................39
4.5.3 Wiring example ....................................................................................................................40
5. Operation of the Unit.................................................................................... 41
5.1 Operation with PC and system software COMBIVIS ......................................................41
5.2 Switch-on procedure .........................................................................................................41
5.3 Parameter summary ..........................................................................................................42
5.4 Password input ..................................................................................................................43
5.5 Monitoring and analysis parameters ...............................................................................43
5.6 Special adjustments ..........................................................................................................46
A. Annex A ......................................................................................................... 50
A.1 Dimension of power supply and regenerative units ......................................................50
A.2 DC link capacities of KEB frequency inverters...............................................................51
A.3 Decoupling diodes.............................................................................................................53
A.3.1 Assignment ..........................................................................................................................53
A.3.2 Dimensions of the decoupling diodes ..................................................................................53
B. Annex B ......................................................................................................... 55
B.1 Certication........................................................................................................................55
B.1.1 CE-Marking..........................................................................................................................55
B.1.2 ULCertication ....................................................................................................................55
4
Table of Contents

Listofgures
Figure 1: Overload (OL) function............................................................................................19
Figure 2: Overload (OL) function............................................................................................19
Figure 3: Dimensions and weights for the COMBIVERT R6-N ..............................................22
Figure 4: Commutation reactor ..............................................................................................22
Figure5: Radiointerferencelter14E6T60-3000..................................................................23
Figure6: Radiointerferencelter14E6T60-3000..................................................................23
Figure7: Radiointerferencelter14E6T60-3000..................................................................24
Figure8: Radiointerferencelter14E6T60-3000..................................................................24
Figure 9: Fuse holder .............................................................................................................25
Figure 10: EMC-compatible control cabinet installation ...........................................................26
Figure 11: General description of input terminals at KEB inverter ...........................................28
Figure 12: Description of the input terminals of the COMBIVERT R6-N..................................29
Figure 13: Terminals / earth handle..........................................................................................30
Figure14: Terminalsforcommutationreactor/harmoniclter................................................30
Figure15: Powersupplyandregenerativeoperationatinvertercurrent≤currentofone
COMBIVERT R6-N .................................................................................................31
Figure16: Powersupplyandregenerativeoperationatinvertercurrents≤invertercurrent ...32
Figure17: Powersupplyandregenerativeoperationatinvertercurrent≥invertercurrent.....32
Figure18: Regenerativeinvertercurrents≤invertercurrent(typeA1/A2)...............................34
Figure19: Regenerativeinvertercurrents≤invertercurrent(typeB1/B2) ..............................35
Figure 20: Regenerative operation at parallel operation ..........................................................37
Figure 21: Wiring example R6-N..............................................................................................40
Figure 22: Dimension of power supply and regenerative units ................................................50
Figure 23: Dimensions of the decoupling diodes .....................................................................54
5
Table of Contents

6
Preface
1. Preface
The described hard and software are developments of the KEB Automation KG. The en-
closed documents correspond to conditions valid at printing. Misprint, mistakes and technical
changes reserved.
1.1 Information on special measures
Theusedpictogramshavefollowingsignicance:
Danger Is used, when death or serious bodily injury may be the consequence
of non-observance of the measure.
Warning Is used, when bodily injury and/or substantial property damage may
be the consequence of non-observance of the measure.
Caution Is used, when property damage may be the consequence of non-ob-
servance of the measure.
Attention Is used, when noise sensitive or unrequested operation may be the
consequence of non-observance of the measure.
Info Is used, when a better or simpler result can be the consequence of the
measure.
For a special case the instructions can be supplemented by additional pictograms and text.
1.2 Documentation
Attention Documentation via www.keb.de
Prior to performing any work on the unit, it is absolutely necessary to down-
load and read the documentation, especially the safety precautions and in-
structions for use. Follow these steps to get the documentation:
Step 1 Read the material number (Mat.No.) from nameplate
Step 2
Input the material number at "www.keb.de => Service => Downloads" and
click "search".
Downloads
Search for specific material numbers
Please enter a comlete (11-digit) material number.
Search for:
search
xxxxxxx-xxxx
continued on the next page

7
Preface
Step 3
The entire documentation associated with the device will be displayed, in-
cluding the instruction manuals in German and English. If available, other
translations are also indicated. Make sure that the user understands the pro-
vided language.
Should you be unable to read or understand the documentation, do not
take any further steps. Please inform our support network for further
assistance.
Non-observance of the safety and operating instructions leads to the loss of any liability
claims. The warnings and safety instructions in this manual work only supplementary. This
list is not exhaustive.
1.3 Validity and liability
The use of our units in the target products is beyond of our control and therefore exclu-
sively the responsibility of the machine manufacturer, system integrator or customer.
Theinformationcontainedinthetechnicaldocumentation,aswellasanyuser-specicadvice
in spoken and written and through tests, are made to best of our knowledge and information
about the application. However, they are considered for information only without responsibil-
ity. This also applies to any violation of industrial property rights of a third-party.
Selection of our units in view of their suitability for the intended use must be done generally
by the user.
Tests can only be done within the application by the machine manufacturer. They must
be repeated, even if only parts of hardware, software or the unit adjustment are mod-
ied.
Danger by tamper from unauthorized personnel
Unauthorised opening and tampering may lead to death, bodily injury, prop-
ertydamageandmalfunctions.Modicationorrepairispermittedonlyby
KEB authorized personnel. Infringement will annul the liability for resulting
consequences.
Thesuspensionofliabilityisespeciallyvalidalsoforoperationinterruptionloss,lossofprot,
data loss or other damages. The disclaimer will void the warranty. This is also valid, if we
referredrsttothepossibilityofsuchdamages.
If single regulations should be or become void, invalid or impracticable, the effectivity of all
other regulations or agreements is not affected.
Through multitude applications not each possible case of installation, operation or mainte-
nance can be considered. If you require further information or if special problems arise which
are not treated in detail in the documentation, you can request the required information from
the local agency of the company KEB Automation KG.
1.4 Copyright
The customer may use the instruction manual as well as further documents or parts from it
for internal purposes. Copyrights are with KEB Automation KG and remain valid in its entirety.

8
Preface
KEB®, COMBIVERT®, KEB COMBICONTROL®and COMBIVIS®are registered trademarks
of KEB Automation KG.
Other wordmarks or/and logos are trademarks (™) or registered trademarks (®) of their re-
spectiveownersandarelistedinthefootnoteontherstoccurrence.
When creating our documents we pay attention with the utmost care to the rights of third
parties. Should we have not marked a trademark or breach a copyright, please inform us in
order to have the possibility of remedy.
1.5 Speciedapplication
The COMBIVERT R6-N serves exclusively for the supply of frequency inverters with DC input
and/or regeneration of excess energy into the supply system. The operation of other electrical
consumers is prohibited and can lead to malfunctions or to the destruction of the units.
The used semiconductors and components of the KEB Automation KG are developed and di-
mensioned for the use in industrial products. If the KEB COMBIVERT F5 is used in machines,
which work under exceptional conditions or if essential functions, life-supporting measures or
anextraordinarysafetystepmustbefullled,thenecessaryreliabilityandsecuritymustbe
ensured by the machine builder.
The operation of our products outside the indicated limit values of the technical data leads to
the loss of any liability claims.
All output functions of the R6 are "one-channel according to ISO 13849, no diagnostic cov-
erage and therefore not safe". If required, additional protective measures must be met by the
user.
1.5.1 Standard operation
If the DC link voltage increases to a value above the peak value of the mains voltage (nega-
tive power), regeneration of the current into the mains occurs automatically. The regenerative
levelisdenedwithparameterCP.34orcS.02.Themainsvoltageisanalogmeasured.The
regenerativecurrentisequaltothefeed-in,wherebythecurrentowperiodscorrespondto
the times of a B6 bridge circuit. Regeneration is completed if the regenerative and puls off
level (CP.32 or cS.06) is fallen below.

9
Preface
1.5.2 Abnormal operation
When exceeding the permissible limit values for voltage, current or temperature the current
owbetweenDClinkandmainsisblockedduringregeneration.Anappropriateerrormes-
sage is also displayed during supply. The unit must be disconnected from the supply system
or the load must be switched off in case of overcurrent or overload. This can be done by
opening the control release of the frequency inverter.
At factory setting the modulation is switched off in case of a net phase failure and error mes-
sage E.nEt is displayed.
Special adjustments from KEB are necessary if the modulation and/or the standard operation
shouldstartagainwithinadenedtimeincaseofreturnofpowersupply.
1.6 Product description
This instruction manual describes the power supply and regenerative unit KEB COMBIVERT
R6-N. The COMBIVERT R6-N has the following features.
The supply unit
• converts a three-phase input voltage into DC voltage.
• supplies single KEB frequency inverter or via DC interconnection.
• can be parallel connected while maintaining a base load if higher power supply is required.
• increases the stability of the DC link voltage in the DC interconnection.
The regenerative unit
• feeds back the excess energy from generatoric operation into the supply system.
• reduces the energy demand.
• reduces the heat emission.
• is environmentally friendly and space-saving.
• replaces braking resistor and braking transistor.
• is cost-saving.
• hasthesamecurrentow(harmoniccomponents)suchasfeed-inandrarelynoise
level
The COMBIVERT R6-N is generally protected against overcurrent, ground fault and tempera-
ture. Appropriate dimensioned DC fuses protects the DC link circuit against short-circuit. The
following accessories are necessary for operation with the COMBIVERT R6-N:
• Mains choke
• EMClterE6(forobservanceofEMCstandard)respectivelyvoltagelimitation

10
Preface
1.7 Part code
1 9 R 6 N 3 E - 9 0 0 A
Type A: Standard
B: Flat rear
D: ext. fan power supply
E: Special fan
Design 0: Standard
reserved 0: Standard
1: modiedstandard(increasedoverload)
Voltage 9: 3-ph.; 180…550 V; AC
Housing E
Options 0: without 3: Precharging, DC-fuses
1: Precharging
Control N 1N.R6
Series R6
Inverter size 15 (13), 19 (16)

2. Safety Instructions
2.1 General instructions
Danger Electric Shock
COMBIVERT R6 power supply and regenerative units contain dangerous
voltages which can cause death or serious injury.
COMBIVERT R6 can be adjusted by way that energy is regenerated into the
supply system in case of power failure at regenerative operation. Therefore
a dangerous high tension can exist in the unit after switching off the supply
system.
Before working with the unit check the isolation from supply by meas-
urements in the unit.
Care should be taken to ensure correct and safe operation to minimise risk
to personnel and equipment.
Warning OnlyQualiedElectro-Personnel
All work from the transport, to installation and start-up as well as mainte-
nancemayonlybedonebyqualiedpersonnel(IEC364and/orCENELEC
HD 384 and IEC-Report 664 and note national safety regulations). According
tothismanual qualied staffmeans those whoareabletorecogniseand
judge the possible dangers based on their technical training and experience
and those with knowledge of the relevant standards and who are familiar with
theeldofpowertransmission.
Attention Observe standards
The COMBIVERT must not be started until it is determined that the installa-
tion complies with the Machine directive (2006/42/EC) as well as the EMC-di-
rective (2004/108/EC)(note EN 60204).
The COMBIVERT meets the requirements of the Low-Voltage Directive
2006/95/EC. The harmonized standard of the series EN 61800-5-1 (VDE
0160) is used.
This is a product of limited availability in accordance with IEC 61800-3. This
product may cause radio interference in residential areas. In this case, the
operator must take appropriate measures.
11
Safety Instructions

2.2 Transport, storage and installation
The storage of the COMBIVERT must be done in the original packing. It is to be protected
against humidity and excessive cooling and thermal effect. A long-distance transport must be
carriedoutintheoriginalpacking.Itistobesecuredagainstimpactinuence.Observethe
markingonthenalpacking!AfterremovingthenalpackingtheCOMBIVERTmustbeshut
down on a stable base.
Warning Protect Against Accidental Contact
The COMBIVERT R6 must be protected against invalid loading. Components and covers
must not be bent or moved as this may affect insulation distances. The units contain electro-
static sensitive devices which can be destroyed by inappropriate handling. For that reason
the contact of electronic devices and contacts is to be avoided. The equipment must not be
switched on if it is damaged as it may no longer comply with mandatory standards.
Make sure that during installation there is enough minimum clearance and enough cooling.
Climatic conditions must be observed in accordance with the instruction manual.
Warning Hot surface
Heat sinks can reach temperatures, which can cause burns when touching. If
in case of structural measures a direct contact cannot be avoided, a warning
notice "hot surface" must be mounted at the machine.
2.3 Electrical connection
Danger Observe capacitor discharge time
Before any installation and connection work, the system must be switched off and secured.
After clearing the DC link capacitors are still charged with high voltage for a short period of
time. The unit can be worked on again, after it has been switched off for 5 minutes.
Caution Safe isolation
The terminals of the control terminal strip are securely isolated in accordance with EN 61800-
5-1. With existing or newly wired circuits the person installing the units or machines must
ensure that the EN requirements are met. With frequency inverters that are not isolated from
the supply circuit all control lines must be included in other protective measures (e.g. double
insulation or shielded, earthed and insulated).
12
Safety Instructions

Danger Voltage with respect to ground
The connection of COMBIVERT R6 is allowed to:
a) symmetrical mains with a voltage phase (L1, L2, L3) with respect to neutral conductor/
ground (N/PE) of maximum 305 V.
b) phase conductor grounded supply networks:
• the control system is no longer regarded as “safe isolated circuit”, further protection
measures are required therefore (see "Safe isolation").
• with this type of power system, the max. voltage phase / earth must not exceed 528 V
absolute
• appropriate, external DC fuses at the DC connections are necessary for the 400 V class.
Use the COMBIVERT R6-N without internal DC fuses.
• ContactKEBregardingEMClter.
Attention Fixed connection
TheCOMBIVERTR6isdesignedforxedconnection,sincedischargecurrentsof>3.5mA
occurespeciallywhenusingtogetherwithEMIlters.Therefore,therequirementsorinstruc-
tions from EN 60204-1 (VDE 0113) and EN 61800-5-1 (IEC 0160-5-1) must be observed.
Caution Insulation measurement
When doing an insulation or voltage measurement in accordance with in EN 60204-1 /
VDE0113-1,thepowersemiconductoroftheunitandexistingradiointerferenceltersmust
be disconnected because of the danger of destruction. This is permissible in compliance
with the standard, since all inverters are given a high voltage test in the end control at KEB.
In the case of special requirements please contact KEB.
Caution Different earth potentials
When using components without isolated inputs/outputs, it is necessary that equipotential
bonding exists between the components to be connected (e.g. through the equalizer). Dis-
regard can cause destruction of the components by the equalizing currents.
13
Safety Instructions

Caution Prevent malfunctions
A trouble-free and safe operation of the COMBIVERT R6 is only guaranteed when the con-
nection instructions below are strictly followed. Incorrect operation or damage may result
from incorrect installation:
• Pay attention to mains voltage.
• Install power cables and control cables separately (>15 cm separation).
• Useshielded/twistedcontrollines.LayshieldatonesidetoCOMBIVERTR6-NtoPE!
• Only use suitable circuit elements to control the logic and analog inputs, whose contacts
are rated for extra-low voltages.
• Housing of the COMBIVERT R6 must be well earthed. Screens of larger power cable
must be directly and securely attached to both the inverter PE terminal and the motor
ground terminal (remove paint).
• Ground the cabinet or the system earth star point with the shortest connection to mains
earth. (avoid earth loops)
• UseexclusivelythelinecommutationthrottlespeciedbyKEB.
• The average value of the supplied DC current may not exceed the maximum DC current.
• If several frequency inverters are connected to the COMBIVERT R6-N the max. permis-
sible DC link capacities of all connected frequency inverters must be considered during
supply operation (see technical data).
Warning Automatic restart
The COMBIVERT R6 can be adjusted by such way that the inverter restarts
automatically after an error case (e.g. broken phase line). System design
must take this into account, if appropriate, and additional monitoring or pro-
tective features added where necessary.
Caution Not short-circuit proof (supply)
TheCOMBIVERTR6isnotshort-circuitproofatthemainsinput!Conditionalprotectionat
the mains input is possible if the I2t-protection was adapted with a gR fuse. The short-circuit
protection at DC output is ensured by internal or external aR respectively gR fuses.
Caution Conditionally short-circuit proof (regeneration)
The COMBIVERT R6 is conditionally short-circuit proof (EN61800-5-1 / VDE 0160). The
intended function is guaranteed after resetting the internal protection devices.
Exception:
• If earth- or short circuits often occurs at the output, this can lead to a defect in the unit.
14
Safety Instructions

Attention Cyclic activation and deactivation
With applications requiring the COMBIVERT R6 to be switched on and off cyclically, main-
tain an off-time of at least 5 min. If you require shorter cycle times please contact KEB.
Switchingoffduringtheinitializationphasecancauseundenedconditions.
Attention RCD (residual current operated circuit-breaker)
When using systems with RCD, the instructions or the requirements of VDE 0100 -T530
(IEC 60364-5) must be observed. The recommended tripping current of the RCD type „B“ is
300 mA.
15
Safety Instructions

2.4 EMC instructions
COMBIVERT R6-N represent electrical equipment designed for use in industrial and com-
mercial units. In accordance with the EMC directive 2006/108/EC, it is not obligatory to mark
these devices as they represent components to be further processed by the respective ma-
chine and unit manufacturer and are not operable independently according to the EMC di-
rective. The person installing / operating the machine / unit is obliged to prove the protective
measures demanded by the EMC directive are complied with. The prescribed ratings can
usuallybecompliedwithwhenusingtheradiointerferencevoltageltersspeciedbyKEB,
and when observing the following measures and installation guidelines.
2.5 EMC conform installation
TheCOMBIVERTR6isdesignedtobeusedinthesecondenvironmentasdenedinEN
61800-3(unitwithitsownsupplytransformer).Takeadditionalltermeasureswhenusing
itintherstenvironment(residentialandcommercialareaconnectedtopubliclow-voltage
mains)!
• Install the control cabinet or system in an appropriate and correctly way (see chapter „EMC
conform control cabinet installation“)
• To avoid coupled-in noise, separate supply lines, motor lines, control and data lines (low-volt-
age level < 48 V) and leave a space of at least 15 cm between them when installing.
• In order to maintain low-resistance high frequency connections, earthing and shielding,
as well as other metallic connections (e.g. mounting plate, installed units) must be in met-
al-to-metal contact with the mounting plate, over as large an area as possible. Make ground
connections with a surface as large as possible (earthing strips).
• Only use shielded cable with copper or tin-plated braid, since steel braid is not suitable for
high frequency ranges. The screen must always be installed on the compensating rail and
fastened with clips or guided through the wall of the housing. Do not elongate the screen
end(pigtails)withindividualconductors!
• Ifexternalinterferencesuppressionltersareused,thenthesemustbeinstalledasclose
as possible to (<30 cm from) the interference source and in metal-to-metal contact with the
mounting plate, over as large an area as possible.
• Always equip inductive control elements (contactors, relays etc.) with suppressors such as
varistors, RC-elements or damping diodes.
• All connections must be kept as short as possible and as close as possible to the earth, as
freeoatinglinesworkasactiveandpassiveaerials.
• Keep connection cables straight (do not bundle). Install a non-assigned wire at one sides to
the protective earth conductor.
• Theowandreturncircuitmustbetwistedwhenthelines are not shielded, inorder to
dampen common-mode noise.
• Further information can be found in the internet, see „www.keb.de“.
16
EMC instructions

17
Technical Data
3. Technical Data
3.1 Standard unit size
Standard unit size *) 15 (13) 19 (16)
Housing size E
Phases 3
permitted mains forms TN, TT 5)
Rated voltage *) [V] 400 (230)
Input voltage UL [V] 240/400/480
Mains voltage range [V] 180…550 ±0 %
Mains frequency [Hz] 50 / 60 ±2
DC voltage range *) [VDC]250…780 (UL: 340…680)
Regenerative operation
Output rated power Sn *) [kVA] 18 (10.5) 45 (26)
Rated active power *) [ kW ] 17 (10) 42 (23)
Max. power output *) [kVA] 27 (15.5) 67.5 (39)
Max. active power *) [ kW ] 25.5 (15) 63 (34.5)
Regenerative rated current [A] 26 65
Regenerative DC current [ADC]32 80
Over load current (E.OL) 60 s 1) [A] 39 97.5
Max. regenerative DC current 60 s [ADC]48 120
Power supply operation
Input rated power Sn *) [kVA] 18 (10.5) 48.5 (28)
Rated active power *) [ kW ] 16 (10) 44.5 (25.5)
Max. input power *) [kVA] 27 (15.5) 72.5 (42)
Max. active power *) [ kW ] 24 (14.5) 67 (38)
Rated supply current 2) [A] 26 70
DC supply current [ADC]32 87 3)
Over load current (E.OL) 60 s [A] 39 105
Max. DC supply current 60 s [ADC]48 130
Overload disconnection (E.OL) [%] 160 160
Overvoltage switch-off (E.OP) [VDC]900
Output rated voltage [VDC]540 (310)
Max. permissible DC link capacity 4) *) [µF] 10000 (42000) 10000 (42000)
I2t Integral of the limiting load of the semiconduc-
tor
[A2s] 1200 4500
Max. permissible mains fuse type gR / aR [A] 40 100
Permissible aR fuse Siemens Sitor / Bussmann (no delta power
system)
3NC2240 / FWP-40A22FA 3NC2240 / FWP-40A22FA
Line fuse for UL type RK1 "fast acting" or "J fast acting" 50A / 480V (50A / 250V) 90A / 480V (90A / 250V)
Short-circuit factor at the connection point (Skn" / Sn) or (Sscp / Sn) 20 < Skn" / Sn< 350
Power loss at nominal operating [W] 200 470
Max. heat sink temperature [°C] 70 88
*) Bracket values obtain for operation at 230 V power supply. The unit is automatically adjusted by the software when
switching on.
1) Theoverloadcurrentisspeciedfor1minute.Theoverloadcycleis300seconds.Thiscorrespondstodutyclass2
EN 60146-1-1.
2) The current data are based on a fundamental frequency component of g=0.95. The fundamental frequency com-
ponent or the effective value of the input current is dependent on load and line supply conditions. At uncontrolled
B6convertersthephaseanglecosφ1canbesettoone,sothevalueofthefundamentalfrequencycomponentsis
equal to the value of the power factor.
3) If the DC infeed current > 85ADC use two by two of the DC terminals (++ and --) to meet the requirements of the
UL standard. The connection cables are parallel connected.
4) Please contact KEB for higher values.
5) After consultation KEB IT and delta power system (see also safety instructions, voltage with respect to ground)

18
Technical Data
3.2 Special unit Peak Power
Inverter size *) Special unit Peak Power 19 (16)
Housing size E
Phases 3
Approaved mains phases TN, TT 3)
Rated voltage *) [V] 400 (230)
Input voltage UL [V] 240/400/480
Mains voltage range [V] 180…550 ±0 %
Mains frequency [Hz] 50 / 60 ±2
DC voltage range *) [VDC] 250…780 (UL: 340…680)
Regenerative operation
Output rated power Sn *) [kVA] 45 (26)
Rated active power *) [ kW ] 42 (23)
Max. power output *) [kVA] 81 (46,6)
Max. active power *) [ kW ] 75 (42)
Regenerative rated current [A] 65
Regenerative DC current [ADC] 80
Overload current (E.OL) 10 s [A] 117
Max. regenerative DC current 10 s [ADC] 144
Power supply operation
Input rated power Sn *) [kVA] 48.5 (28)
Rated active power *) [ kW ] 44.5 (25.5)
Max. input power 10 s *) [kVA] 87 (50)
Max. active power 10 s *) [ kW ] 80 (46)
Rated supply current 1) [A] 70
DC supply current 2) [ADC] 87
Overload current (E.OL) 10 s [A] 126
Max. DC supply current 10 s [ADC] 156
Overload disconnection (E.OL) [%] 200
Overvoltage switch-off (E.OP) [VDC] 900
Rated output voltage [VDC] 540 (310)
Max. permissible DC link capacity *) [µF] 10000 (42000)
I2t Integral of the limiting load of the semiconductor
[A2s] 3058
Max. permissible mains fuse type gR / aR [A] 100
Permissible aR fuse Siemens Sitor / Bussmann (no delta power
system)
3NC2240 / FWP-40A22FA
Line fuse for UL type RK1 "fast acting" or "J fast acting" 90A / 480V (90A / 250V)
Short-circuit factor at the connection point (Skn" / Sn) or (Sscp / Sn) 20 < Skn" / Sn< 350
Power dissipation at nominal operating [W] 430
Max. heat sink temperature [°C] 88
*) Bracket values obtain for operation at 230 V power supply. The unit is automatically adjusted by the soft-
ware when switching on.
1) The current data are based on a fundamental frequency component of g=0.95. The fundamental fre-
quency component or the effective value of the input current is dependent on load and line supply
conditions.AtuncontrolledB6convertersthephaseanglecosφ1canbesettoone,sothevalueofthe
fundamental frequency components is equal to the value of the power factor.
2) If the DC supply current > 85ADC use two by two of the DC terminals (++ and --) to meet the require-
ments of the UL standard.
The connection cables are parallel connected.
3) After consultation KEB IT and delta power system (see also safety instructions, voltage with respect to
ground)

19
Technical Data
Warning General instructions
•
Voltagestabilizationmustbeactivatedatthefrequencyinverterifaharmoniclterisused.
•The units are not short-circuit proof without corresponding dimensioned fuses.
•Exceeding of the max. rechargeable DC link capacity can lead to a defect.
•A load removal in the DC link circle may be done only after the message „ready“.
•If the control release is set when switching off the mains, this can lead to an overcurrent error and the
lifetime of the module can be reduced.
•The unit must be disconnected from the supply system or the load must be switched off in case of overcur-
rent or overload.
3.3 Overload (OL) function
Standard:
105
110 120 130 140 150 160
100
150
200
250
270
60
Release time [s]
Load [%]
Figure 1: Overload (OL) function
Modiedstandard(increasedoverload):
105 110 120 130 140 150 160
100
150
200
250
300
10
50
270
180 200
①
Release time [s}
Load [%]
1. Depending on the line supply impedance
Figure 2: Overload (OL) function

20
Technical Data
3.4 Operating conditions
Standard Class Instructions
Denitionacc.
EN 61800-2 Inverter-product standard:
Ratedspecications
EN 61800-5-1 Inverter-product standard:
General safety
Site altitude
max. 2000 m above sea level
With site altitudes over 1000 m a derating of 1 %
per 100 m must be taken into consideration.
Ambient conditions during operation
Climate Temperature EN 60721-3-3 3K3
extended to -10…45 °C
(with temperature over 45°C to max. 55°C
a derating of 5 % per 1 K must be taken into
consideration)
Humidity 3K3 5…85 % (without condensation)
Mechanical Vibration
Track EN50155 max. amplitude of a vibration 1 mm
(5…13 Hz)
max. acceleration amplitude 7 m/s²
(13…200 Hz)
Germ. Lloyd Part 7-3
EN 60721-3-3 3M4
Contamination Gas 3C2
Solids 3S2
Ambient conditions during transport
Climate
Tempera-
ture
EN 60721-3-2
2K3
Humidity 2K3 (without condensation)
Mechanical Vibration 2M1
max. vibration amplitude 3.5 mm
(2…9 Hz)
max. acceleration amplitude 15 m/s²
(9…200 Hz)
Surge 2M1 max. 100 m/s²; 11 ms
Contamination Gas 2C2
Solids 2S2
Ambient conditions for the storage
Climate
Tempera-
ture
EN 60721-3-1
1K4
Humidity 1K3 (without condensation)
Mechanical Vibration 1M1
max. amplitude of a vibration 1 mm
(5…13 Hz)
max. acceleration amplitude 7 m/s²
(13…200 Hz)
Surge 1M1 max. 100 m/s²; 11 ms
Contamination Gas 1C2
Solids 1S2
Type of protection EN 60529 IP20
Environment IEC 664-1 Pollution degree 2
Denitionacc. EN 61800-3 Inverter-product standard: EMC
EMC emitted interference
Cable-based interferences – C2 withEMClterandferriterings
Radiated interferences – EN 61800-3 withEMClterandferriterings
Interference immunity
Static discharges EN 61000-4-2 8 kV AD (air discharge) and CD (contact dis-
charge)
continued on the next page
Other manuals for Combivert R6
4
Table of contents
Other KEBCO Power Supply manuals

KEBCO
KEBCO combivert R6-S User manual

KEBCO
KEBCO Combivert R6 User manual

KEBCO
KEBCO combivert R6-S User manual

KEBCO
KEBCO Combivert R6 User manual

KEBCO
KEBCO COMBIVERT F5 User manual

KEBCO
KEBCO COMBIVERT R5-C User manual

KEBCO
KEBCO combivert R6-S User manual

KEBCO
KEBCO Combivert R6 User manual

KEBCO
KEBCO combivert R6-S User manual