Keyscan CA250 Series Quick start guide


Copyright © 2001 - 2015 Keyscan Inc. All rights reserved.
Information and specifications in this document are subject to change without notice.
Except for the benefit of installation and operation of the Keyscan access control system, no part of this
documentation may be reproduced or transmitted in any form or by any means without the expressed written
permission of Keyscan Inc.
Keyscan Inc. A Member of the Kaba Group
901 Burns Street East
Whitby, Ontario
Canada
L1N 0E6
Phone: 1-888-539-7226 (Toll Free Canada/USA)
Phone: 905-430-7226
Fax: 905-430-7275
Web Site: www.keyscan.ca
Keyscan technical support is available to dealers and installers Monday to Friday 9:00 A.M. to 6:30 P.M.
Eastern Time at the above listed telephone numbers or web address.


Keyscan Inc. –Technical Guide (PC109x - 07.15)
4
Table of Contents
List of Figures ................................................................................................................................... 7
List of Tables................................................................................................................................... 10
Foreword ........................................................................................................................................ 11
Approved Standards..................................................................................................................... 11
Product Certification..................................................................................................................... 11
Electrical Precautions ................................................................................................................... 11
Tools.......................................................................................................................................... 11
Cable Specifications ........................................................................................................................ 12
Grounding .................................................................................................................................. 12
Mount the Enclosure & Circuit Boards ............................................................................................. 15
UL STD 294, CSA STD C22.2 (No. 205), CE, FCC 15 Subpart B.......................................................... 15
Mounting the Metal Enclosure........................................................................................................ 16
Mounting the PC109x Control Board to Metal Standoffs .................................................................... 18
Mounting the DPS-15 Power Supply ............................................................................................... 20
Control Board –Mounting Locations ............................................................................................... 22
Connect Enclosure Tamper Switch to TB3 ....................................................................................... 25
Connect Enclosure Ground Strap ................................................................................................... 25
Typical Door Layout and Hardware ................................................................................................. 27
Door Lock Hardware..................................................................................................................... 28
Door Contacts, Exit Buttons, Auxiliary Inputs .................................................................................. 29
Readers...................................................................................................................................... 30
OCB-8 Relay Board.......................................................................................................................... 31
OCB-8 Relays - Normal and Reversed............................................................................................. 32
Terminating Cables at Door Control Units ....................................................................................... 34
Outputs ...................................................................................................................................... 34
Terminate Lock Wiring at the OCB-8 .............................................................................................. 34
Terminate Auxiliary Outputs with Hardware/Alarms ......................................................................... 41
HC Accessibility Relay................................................................................................................... 45
Pre-alert Output Relay.................................................................................................................. 49
Global Output Relay ..................................................................................................................... 53
Terminate Input Wiring ................................................................................................................ 55
Terminating Cables at Elevator Control Units .................................................................................. 60

Keyscan Inc. –Technical Guide (PC109x - 07.15)
5
OCB-8 Relay Boards..................................................................................................................... 61
Terminate Reader Cables ................................................................................................................ 65
Keyscan & HID Readers ................................................................................................................ 65
Indala Readers ............................................................................................................................ 86
S2 DIP Switches.............................................................................................................................. 91
S2 DIP Switch Functions ............................................................................................................... 91
S2 DIP Switch Settings ................................................................................................................. 93
Important - Circuit Board Function Revisions................................................................................... 95
S1 - System Reset / S3 - Restore Factory Defaults ......................................................................... 96
S1 –System Reset ...................................................................................................................... 96
S3 –Restore Factory Defaults (Clear Memory) ................................................................................ 96
Single ACU Communication ............................................................................................................. 98
Multiple Building Communication on a WAN..................................................................................... 98
Keyscan RS-232 Data Cable .......................................................................................................... 98
CIM Communication ...................................................................................................................... 104
CIM Conventions ........................................................................................................................105
CIM Module Requirements ...........................................................................................................105
CIM Specifications ......................................................................................................................105
BPS/CAN Bus Distance Chart........................................................................................................106
CIM Jumper Settings ...................................................................................................................107
CIM Installation Guidelines...........................................................................................................109
CIM Connection Diagrams............................................................................................................110
Serial Communication .................................................................................................................113
Network Communication via Optional NETCOM2P or NETCOM6P (Encrypted) ......................................114
Network Communication via Optional NETCOM2 Rev. B ...................................................................116
CIM Diagnostic LEDs B3 –B0 .......................................................................................................118
DPS-15 Power Supply Connections ............................................................................................... 120
Power Supply Specifications .........................................................................................................120
Keyscan Circuit Board Current Ratings ..........................................................................................120
DPS-15 Dual Power Supply –Current Calculation............................................................................121
System Power-up .......................................................................................................................123
Test Voltages ................................................................................................................................ 125
Control Board Voltage Test Points .................................................................................................125
Test Points –Communication Terminals.........................................................................................127
Communication Diagnostics .......................................................................................................... 128
Communication Status LEDs ........................................................................................................128
System Status LED .....................................................................................................................130

Keyscan Inc. –Technical Guide (PC109x - 07.15)
6
Card Diagnostics - LED Wiegand Bit Counters.................................................................................131
Appendix A –WSSKP-1 Keypad..................................................................................................... 132
Appendix B –WIEEX2 ................................................................................................................... 135
Warranty....................................................................................................................................... 140
Index ............................................................................................................................................ 141

Keyscan Inc. –Technical Guide (PC109x - 07.15)
7
List of Figures
Figure 1 - Grounding Access Control Units and Cables with CIMs.............................................................. 14
Figure 2 –Mounting the Metal Enclosure ............................................................................................... 16
Figure 3 –Enclosure Knockout & Mounting Hole Locations/Dimensions ..................................................... 17
Figure 4 –Mount and Fasten PC109x Control Board to 3/8" Male/Female Standoffs.................................... 19
Figure 5 –Plastic Stand Off ................................................................................................................. 21
Figure 6 –Mounting Power Supplies ..................................................................................................... 21
Figure 7 –CA250 with Board Mounting Positions .................................................................................... 22
Figure 8 –CA4500 with Board Mounting Positions .................................................................................. 23
Figure 9 –CA8500 with Board Mounting Positions .................................................................................. 23
Figure 10 –EC1500 with Board Mounting Positions ................................................................................ 24
Figure 11 –EC2500 with Board Mounting Positions ................................................................................ 24
Figure 12 –Enclosure Tamper Switch Connected to TB3 Terminal ............................................................ 25
Figure 13 –Enclosure Ground Strap Connection..................................................................................... 25
Figure 14 –Securing the Enclosure Cover ............................................................................................. 26
Figure 15 –Typical Door Layout........................................................................................................... 27
Figure 16 –Typical Door Strike Connection ........................................................................................... 28
Figure 17 –Typical Magnetic Lock Connection ....................................................................................... 28
Figure 18 –Door Contacts, Exit Buttons, PIRs, & Auxiliary Inputs ............................................................ 29
Figure 19 –Typical Door Reader Connection.......................................................................................... 30
Figure 20 –OCB-8 Relay Board PC1102 ................................................................................................ 31
Figure 21 –Lock State - Fail Safe Device .............................................................................................. 36
Figure 22 –Lock State - Fail Secure Device........................................................................................... 37
Figure 23 –Terminate Lock Wiring CA250B ........................................................................................... 38
Figure 24 –Terminate Lock Wiring CA4500B ......................................................................................... 39
Figure 25 –Terminate Lock Wiring CA8500B ......................................................................................... 40
Figure 26 –Terminate Auxiliary Outputs CA250B ................................................................................... 42
Figure 27 –Terminate Auxiliary Outputs CA4500B ................................................................................. 43
Figure 28 –Terminate Auxiliary Output CA8500B................................................................................... 44
Figure 29 –HC Accessibility Relay CA250B/OCB-8 Connections................................................................ 46
Figure 30 –HC Accessibility Output Relay CA4500B/OCB-8 Connections ................................................... 47
Figure 31 –HC Accessibility Output Relay CA8500B/OCB-8 Connections ................................................... 48
Figure 32 –Pre-alert Relay CA250B/OCB-8 Connections ......................................................................... 50

Keyscan Inc. –Technical Guide (PC109x - 07.15)
8
Figure 33 –Pre-alert Relay CA4500B/OCB-8 Connections........................................................................ 51
Figure 34 –Pre-alert Relay CA8500B/OCB-8 Connections........................................................................ 52
Figure 35 –Global OCB-8 Ribbon Cable Connection with CA4500 & CA8500 .............................................. 54
Figure 36 –Terminate Input Wiring –Door Inputs (Contacts).................................................................. 55
Figure 37 –Terminate Input Wiring –RTE Push Button........................................................................... 56
Figure 38 –Terminate Input Wiring –RTE PIR Motion Sensor .................................................................. 57
Figure 39 –Terminate Input Wiring RTE - PIR & Push Button................................................................... 58
Figure 40 –Terminate Input Wiring –AI/SI Inputs................................................................................. 59
Figure 41 - Elevator Control Overview .................................................................................................. 60
Figure 42 –Elevator Layout –Interior of Car ......................................................................................... 60
Figure 43 –Terminate Floor Wiring EC1500B......................................................................................... 62
Figure 44 –Terminate Floor Wiring EC2500B......................................................................................... 63
Figure 45 –Terminate Floor Input Wiring EC1500B ................................................................................ 64
Figure 46 –Terminate Floor Input Wiring EC2500B ................................................................................ 64
Figure 47 –Keyscan K-PROX2 (125 kHz) .............................................................................................. 68
Figure 48 –Keyscan K-VAN Proximity Reader (125 kHz) ......................................................................... 69
Figure 49 –Keyscan K-KPR Keypad / Proximity Reader (125 KHz) ........................................................... 70
Figure 50 –Keyscan K-SMART Reader .................................................................................................. 71
Figure 51 –HID-5395 Wiring............................................................................................................... 72
Figure 52 –HID 5365 / 6005 Wiring..................................................................................................... 73
Figure 53 –HID 5355 Wiring ............................................................................................................... 74
Figure 54 –HID 5375 Wiring ............................................................................................................... 75
Figure 55 –HID 5355KP Wiring ........................................................................................................... 76
Figure 56 –HID iClass KEYR10 ............................................................................................................ 77
Figure 57 –HID iClass KEYR40 ............................................................................................................ 78
Figure 58 –HID iClass KEYRW400........................................................................................................ 79
Figure 59 –HID iClass KEYRK40 .......................................................................................................... 80
Figure 60 –HID iClass R90 Long Range Reader ..................................................................................... 81
Figure 61 –HID iClass R10 Series ........................................................................................................ 82
Figure 62 –HID iClass R15 Series ........................................................................................................ 83
Figure 63 –HID iClass R40 Series ........................................................................................................ 84
Figure 64 –HID iClass RK40 Series ...................................................................................................... 85
Figure 65 –Indala PX 603 and PX 605 Wiring ........................................................................................ 87
Figure 66 –Indala PX610 Wiring .......................................................................................................... 88
Figure 67 –Indala PX 620 Wiring ......................................................................................................... 89

Keyscan Inc. –Technical Guide (PC109x - 07.15)
9
Figure 68 –Indala PXK 501 Wiring ....................................................................................................... 90
Figure 69 –S2 DIP Switch Legend ....................................................................................................... 91
Figure 70 –Location of S2 DIP Switches ............................................................................................... 94
Figure 71 –S3 Restore Default Settings (Clear Memory) & S1 System Reset Locations ............................... 97
Figure 72 –RS-232 Data Cable Connections.......................................................................................... 99
Figure 73 –Communication - Direct Serial ...........................................................................................100
Figure 74 –Single ACU Communication - USB Adaptor ..........................................................................101
Figure 75 - Communication - NETCOM2P or NETCOM6P/ACU ..................................................................102
Figure 76 –Communication - NETCOM2 Rev.B/ACU ..............................................................................103
Figure 77 –CIM Overview ..................................................................................................................104
Figure 78 –CIM Jumper Locations.......................................................................................................107
Figure 79 –CIM to ACU Connections ...................................................................................................111
Figure 80 –CIM to CIM CANBUS Connections .......................................................................................112
Figure 81 –PC Serial Connection - CIMs/ACUs......................................................................................113
Figure 82 –Network Connection with NETCOM2P or 6P - CIMs/ACUs .......................................................115
Figure 83 –Network Connection with NETCOM2 Rev. B - CIMs/ACUs.......................................................117
Figure 84 - CIM Diagnostic LEDs - B3 - B0 ...........................................................................................119
Figure 85 –DPS-15 Power Supply Connections .....................................................................................124
Figure 86 –Control Board Test Points –Voltages ..................................................................................126
Figure 87 –Control Board Communication Test Points ...........................................................................127
Figure 88 - Communication LEDs - CA & EC Control Boards ....................................................................130
Figure 89 - Location of System Status LED...........................................................................................131
Figure 90 –Location of Wiegand Bit Counter LEDs ................................................................................131
Figure 91 –WSSKP-1 Keypad Connection ............................................................................................133
Figure 92 –WSSKP-1 Keypad/Reader Combination Connections .............................................................134
Figure 93 –Wiegand Extender Overview ..............................................................................................137
Figure 94 –WIEEX2 RS485 Connections –(Firmware 6.00 or Higher)......................................................138
Figure 95 –WIEEX2 to OCB-8 Cable Connection ...................................................................................139

Keyscan Inc. –Technical Guide (PC109x - 07.15)
10
List of Tables
Table 1 –Cable Specificationss ............................................................................................................ 12
Table 2 –Battery Duration Times......................................................................................................... 20
Table 3 –OCB-8 Specifications ............................................................................................................ 31
Table 4 - List of Relay States ............................................................................................................... 32
Table 5 –Door Lock Relay Assignments & Ribbon Cable Connections........................................................ 35
Table 6 –Auxiliary Output Relay Assignments & Ribbon Cable Connections ............................................... 41
Table 7 –HC Accessibility Output/Door Assignment................................................................................ 45
Table 8 –Pre-alert Relay to Door Assignments ...................................................................................... 49
Table 9 - OCB-8 Global Output Relay #/ Client Relay Assignments ........................................................... 53
Table 10 –OCB-8 to EC1500B Ribbon Cable Connections ........................................................................ 61
Table 11 –OCB-8 to EC2500B Ribbon Cable Connections ........................................................................ 61
Table 12 –Keyscan & HID Reader Power Specifications .......................................................................... 65
Table 13 –Indala Reader Power Specifications ...................................................................................... 86
Table 14 –S2 DIP Switch Settings ....................................................................................................... 93
Table 15 –CIM Specifications .............................................................................................................106
Table 16 –BPS/CANBUS Distance Chart ..............................................................................................106
Table 17 –CIM Global Master Jumper J3..............................................................................................107
Table 18 –CIM 0 –Jumper J4 ............................................................................................................108
Table 19 –CIM CAN Bus Termination Jumpers J5 –J8 ...........................................................................108
Table 20 –CIM Serial Bit Rate Jumpers J9 –J11 ...................................................................................109
Table 21 –CIM Diagnostic LED Codes..................................................................................................118
Table 22 –Keyscan Circuit Board Current Ratings .................................................................................121
Table 23 - ACU Supply - Current Calculation Table ................................................................................122
Table 24 - AUX RDR Supply - Current Calculation Table .........................................................................122
Table 25 –Control Board Test Points - Voltages....................................................................................125
Table 26 –Communication Voltage Test Points .....................................................................................127
Table 27 –Communication Status LEDs ...............................................................................................128
Table 28 - System Status LED ............................................................................................................130
Table 29 –Keypad Power Specifications...............................................................................................132
Table 30 –WIEEX2 ...........................................................................................................................135
Table 31 –WIEEX2 Power Requirements..............................................................................................135
Table 32 –WIEEX2 Cables and Distances.............................................................................................135

Keyscan Inc. –Technical Guide (PC109x - 07.15)
11
Foreword
This technical guide outlines general information for installing Keyscan access control systems. The guide
assumes the installer has knowledge of electrical, electronic, mechanical, and computer concepts, as well as
having familiarity with access control systems and associated components. For reliable and safe operation of
the equipment, comply with stated cable, power, ground, and environment specifications.
Approved Standards
Keyscan CA250, CA4500, CA8500, EC1500 and EC2500 series control units conform to the following approved
standards:
UL STD 294 –Access Control Systems Units
CSA STD C22.2 No. 205-M1983 –Signal Equipment
CE Standards
EN 55022 RF Emissions
EN 55024 RF Immunity
EN 60950-1 Equipment Safety
FCC Subpart B RF Emissions
Industry Canada ICES 003 Emissions
Product Certification
The CSA/UL certification record can be viewed at http://directories.csa-international.org. Enter 110441_0_000
in the File Number box.
Electrical Precautions
Ensure all circuit breakers powering the system are off before commencing installation or modifying wiring
connections. Do not apply power before completing the installation; otherwise, you may damage the circuit
boards. Ensure all enclosures have earth ground connections for proper and safe system operation.
Tools
Keyscan recommends having the following tools on hand to install the access control system:
Digital voltmeter
Wire cutters & needle nose pliers
Soldering iron & tape
Set of screwdrivers
Drill & drill bits
Laptop computer (optional)

Keyscan Inc. –Technical Guide (PC109x - 07.15)
12
Cable Specifications
The following table outlines system cable specifications. Please be sure to review grounding guidelines for safe
system operation. Avoid running access control cables parallel with AC wires or across fluorescent light
fixtures. This can cause AC induction or transmission interference.
Table 1 –Cable Specificationss
Device / Circuit
Board
Signal
Protocol
Maximum Distance
Cable Type
Notes
Readers to ACU
(includes HID iClass
–Rev B & Rev C)
Wiegand
500 ft / 152.4 m
6 conductors
shielded 22 AWG
Overall shielded cable
accepted. CAT5 cable not
acceptable with Wiegand
signal protocol.
Exception Readers to
ACU –PX-620, HID-
5375, MR-10, MR-
20, HID-iClass (Rev
A), iClass KEYRK40
and elevator readers
Wiegand
500 ft / 152.4 m
6 conductors
shielded 18 AWG
Overall shielded cable
accepted. CAT5 cable not
acceptable with Wiegand
signal protocol.
Door strikes &
electro magnets to
ACU
n/a
500 ft / 152.4 m
1 pair 18 AWG
Shielded wire not required.
Contacts & exit
devices
n/a
500 ft / 152.4 m
1 pair 22 AWG
Shielded wire not required.
Motion sensors (PIR)
n/a
500 ft / 152.4 m
2 pairs 22 AWG
Shielded wire not required
CIM
CAN Bus 1
3280 ft / 1000 m @ 9600 BPS
3280 ft / 1000 m @ 19,200 BPS
984 ft / 300 m @ 57,600 BPS
262 ft / 80 m @ 115,200 BPS
CAT 5 –2
twisted pairs
Maximum overall distance
between first and last CIM
units
Direct serial
PC to ACU
NETCOM to ACU
RS-232
100 ft / 30 m @ 9600 BPS
49 ft / 14.9 m @ 19,200 BPS
26 ft / 8 m @ 57,600 BPS
9.8 ft / 3 m @ 115,200 BPS
5 conductors 22
AWG shielded
Overall shielded cable
accepted. CAT 5 cable not
acceptable with RS-232
signal protocol.
WIEEX2 (Wiegand
protocol extender)
n/a
4000 ft / 1219.2 m
CAT 5 –1
twisted pair
communication.
1 pair 18 AWG
power to TX.
If powering transmitter
locally, 18 AWG power
wiring is not required. Kit
includes 1 transmitter & 1
receiver.
Relay Floor Wiring
for floor control
n/a
500 ft / 152.4 m
1 pair 18 AWG
Shielded wire not required.
(Optional)
Floor Input Wiring
for floor reporting
n/a
1000 ft/304.8 m
1 pair 22 AWG
Shielded wire not required
Grounding
Ground all access control units and shielded cables to a cold water pipe. For multiple access control units, all
shields should be connected to a single point earth ground.

Keyscan Inc. –Technical Guide (PC109x - 07.15)
13
It is important to ground the shields of the readers and communication cables to a single point cold water pipe
at the access control unit. Failing to ground the shields or using incorrect cables may cause noise or
interference and result in improper card reads.
Important
Ensure the chassis ground (GND) on the DPS-15 is connected to the metal enclosure ground lug.
Grounding Communication Cable Shield
When terminating the communication cable in the metal enclosure, insulate the shield and connect it to the
ground lug. Keyscan suggests Alpha PVC 10516 –16 AWG clear tubing or a comparable tubing to insulate the
shield. Do not connect the shield to GND on a communication terminal block.
Note
Keep all shield wires and cables away from the control board.

Keyscan Inc. –Technical Guide (PC109x - 07.15)
14
Figure 1 - Grounding Access Control Units and Cables with CIMs
40-2322
Data Cable
Note
Connect ground lug
to single cold water
pipe ground point
Tape
back
shield
Reader
Wiegand
Reader
Signal
ACU 1
RS232
Control Board Control Board
ACU 2
Shield Shield
Green
Black
Red
ACU 3
Control Board
Shield
CIM 0
EGND EGND
CIM
CIM
EGND
Tape
back
shields
CAT 5
Ground
Lug
RS-232**
Common Ground Wire
CAT 5
Common Ground
Wire
Tape
back
shield
KEYSCAN KEYSCAN
KEYSCAN
Earth GND
on DPS15 Earth
GND
on
DPS15
Earth
GND
on
DPS15
KI-00470E-07-12
Shield*
* Insulate shield with
PVC tubing such as
Alpha (p/n PVC10516
16 AWG) or
comparable insulator.
** RS-232 connections at
CIM 0 do not apply when
using a NETCOM2P/6P.

Keyscan Inc. –Technical Guide (PC109x - 07.15)
15
Mount the Enclosure & Circuit
Boards
The following sub-sections review mounting metal enclosures, control boards, communication boards, output
control boards and power supplies.
UL STD 294, CSA STD C22.2 (No. 205), CE, FCC 15
Subpart B
To be compliant with UL STD 294, CSA STD C22.2, CE, or FCC 15 Subpart B standards, adhere to the following
practices:
use the Keyscan metal enclosure with the CSA, CE, FCC label on the inside of the panel cover
mount control boards with the standoffs supplied as instructed
secure the enclosure cover with the 4 screws supplied
connect the tamper switch to the TB3 terminal block on the control board
use the Keyscan DPS-15 to power the control board and readers
ensure 2 x 16V 40VA transformers or 2 x 16.5V 37VA transformers are connected to the Keyscan DPS-15
power supply
locate the transformers within 30 feet (9.144 m) of the Keyscan DPS-15 power supply - do not mount the
transformers inside the ACU metal enclosure
do not use the Keyscan DPS-15 power supply to power door strikes or auxiliary equipment
use a standby battery with sufficient amp hours (minimum is 12V 7.0 Ah) connected to the Keyscan DPS-
15 power supply
connect a proper ground wire from the ground lug inside the metal enclosure to a cold water pipe ground
(earth ground)
connect the enclosure ground strap to the designated studs on the metal enclosure and the enclosure
cover
Any deviations or alterations will result in non-compliance of these standards.

Keyscan Inc. –Technical Guide (PC109x - 07.15)
16
Mounting the Metal Enclosure
The metal enclosure has four (4) pre-drilled holes for mounting to the wall. Connect the ground lug to a true
earth ground. When locating mounting areas, ensure the metal enclosure is not close to high voltage
equipment and the cable lengths are within their maximum allowable distances.
For knockout and mounting hole locations/dimensions, see the diagram on the next page.
Figure 2 –Mounting the Metal Enclosure
Ground Lugs
The metal enclosure includes one ground lug pre-mounted near the top and one spare ground lug, which
mounts on one of the available ground lug studs. You can also re-locate the pre-mounted ground lug to
minimize the length of shield used.
Ground
Lug
Side ViewFront View –Cover removed (diagram not to scale)
Enclosure
Single locking CEMA/NEMA Type 1 box
Height - 20" (50.8 cm)
Width - 16" (40.64 cm)
Depth - 5 1/2" (13.97 cm)
Wall
Knockouts
Large - 1 3/4" (4.5 cm)
Small - 7/8" (2.0 cm)
Alternate
ground
lug
mounts
Alternate
ground
lug mount
Do not mount enclosure near
high-voltage equipment.
KI-00104E-07-11

Keyscan Inc. –Technical Guide (PC109x - 07.15)
17
Figure 3 –Enclosure Knockout & Mounting Hole Locations/Dimensions
1.45"
(3.683 cm)
1.45" (3.683 cm)
1.50"
(3.81 cm)
5.475"
(13.91cm)
2.50"
(6.35 cm)
1.50" (3.81 cm)
16.00" (40.64 cm)
1.45"
(3.683 cm)
1.50"
(3.81 cm)
14.55" (36.957 cm)
1.45"
(3.683 cm)
1.50"
(3.81 cm)
20.00" (50.80 cm)
0.188 " Dia.
0.750" Dia. Extrusion
0.218" Depth
4 Places
1.375"/1.750" Dia.
Knockout
7 Places
5.50" (13.97 cm)
1.50"
(3.81 cm)
3.75" (9.525 cm)
Front
1.50" (3.81 cm)
1.50"
(3.81 cm)
3.75" (9.525 cm)
1.50" (3.81 cm)
5.50" (13.97 cm)
1.50" (3.81 cm)
1.50"
(3.81 cm)
3.75" (9.525 cm)
Front 1.50"
(3.81 cm)
3.75" (9.525 cm)
1.50" (3.81 cm)
Front
Front
10.25" (26.035 cm)
11.75" (29.845 cm)
5.50" (13.97 cm)
13.75" (34.925 cm)
1.00" (2.54 cm) 1.50"
(3.81 cm)
10.25" (26.035 cm)
11.75" (29.845 cm)
13.75" (34.925 cm)
1.00" (2.54 cm)
5.50" (13.97 cm)
1.50"
(3.81 cm)
Front View Right Side ViewLeft Side View
Top View
Bottom View
0.875" Dia.
Knockout
8 Places
KI-00462E-06-12

Keyscan Inc. –Technical Guide (PC109x - 07.15)
18
Mounting the PC109x Control Board to Metal Standoffs
Use the eight (8) enclosed ¼” screws to secure the PC109x control board to the 3/8” metal standoffs mounted
inside the metal enclosure. Be sure the internal tooth star washers are placed between the control board and
the screw as shown in Figure 4 –Mount and Fasten PC109x Control Board to 3/8" Male/Female Standoffs.
Important
Finger-tighten the ¼” screws with a screwdriver. Do not use a power screwdriver or apply excessive force
tightening screws into the metal standoffs when mounting control boards. Ensure the control board is
disconnected from the power when mounting; otherwise, the control board may be damaged from a
potential short-circuit.
Rev 11, Rev 10 & Rev 9 Control Boards
If installing a Rev.11, Rev.10, or Rev. 9 control board in a metal enclosure with the pre-mounted metal
standoffs, you require an adaptor kit - P/N –AK2005.

Keyscan Inc. –Technical Guide (PC109x - 07.15)
19
Figure 4 –Mount and Fasten PC109x Control Board to 3/8" Male/Female Standoffs
Ground Lug
Side View
Self-clinching
nut on back of
enclosure. Split Ring
Lock-
washer
3/8" Male/
Female
Hex
Standoff
Internal
Tooth
Star
Washer
¼” Long Screw
Control Board
Stand-off
locations on
PC109x control
board
Ground Lug
Front View –
Cover removed
(diagram not to scale)
Alternate
Ground
Lug
Mounts
3/8" male/female hex
standoff locations for
mounting PC109x
control board.
Front View –
Cover removed
(diagram not to scale)
Alternate
Ground Lug
Mount
Alternate
Ground
Lug
Mounts
Alternate
Ground Lug
Mount
PC109x
Spacer
PC109x
KI-00105E-04-13

Keyscan Inc. –Technical Guide (PC109x - 07.15)
20
Mounting the DPS-15 Power Supply
The Keyscan DPS-15 is a 13.5 VDC dual linear regulated power supply for powering the ACU circuit boards and
the readers with the following outputs:
ACU output 12 VDC @ 1.2 Amperes
AUX/RDR output 12 VDC @ 1.2 Amperes
Maximum Current Draw
The total current draw on each output should not exceed one (1) Ampere with 200mA in reserve for
accommodating peak current operating demands. See page 120 and use the calculation tables to determine
the total current demand of the all the devices connected to the DPS-15.
CSA/UL Approved Transformers
The DPS-15 power supply requires either of the following class 2 CSA/UL approved transformers and a backup
battery with sufficient amp hours.
2 x 16 V 40 VA
2 x 16.5 V 37 VA
The purpose of two transformers is to comply with UL STD 294, CSA STD C22.2, and charge the battery
circuit. The transformers must be located within 30 feet of the Keyscan power supply. Do not mount the
transformers inside the ACU metal enclosure. Use of non-compliant transformers or deviation from the use of
two (2) approved transformers per access control unit or incorrect voltages void all Keyscan warranties. The
system may operate erratically if the voltage is lower than 12 VDC.
Mount the DPS-15 power supply as shown on page 21. For power supply connections, refer to Figure 85 on
page 124.
Important
Do not use the DPS-15 to power door strikes or auxiliary equipment.
Backup Batteries
Select a battery with enough amp hours to operate the system for the total hours specified. The following table
lists power duration times:
Table 2 –Battery Duration Times
Amp-hour Battery
Amps
Power Duration
8.0
1.4
5.71 hours
7.5 *
1.4
5.36 hours
7.0 *
1.4
5.00 hours
* Indicates the two most commonly used backup batteries.
Plastic Stand Offs
Plastic stand offs are pre-mounted on most power supplies, relay and communication boards. In cases where
stand offs are not pre-mounted, insert the double pronged end of the stand off in the metal enclosure hole
first. Then mount the circuit board to the stand offs.
Other manuals for CA250 Series
1
This manual suits for next models
10
Table of contents
Other Keyscan Control Unit manuals
Popular Control Unit manuals by other brands

i3-TECHNOLOGIES
i3-TECHNOLOGIES iMO-LEARN MDM quick start guide

Beninca
Beninca SA.03 Head operating instructions

Real Time Devices
Real Time Devices CMT106 user manual

Faulhaber
Faulhaber PRECIstep AD CM M1S user manual

Siemens
Siemens SIRIUS 3SB3 operating instructions

Advantech
Advantech AMAX-4800 Series user manual