Kingspan Klargester 1002510 User manual

Kingspan Klargester 1011026
Domestic
Wastewater
Control Panel
USER MANUAL

1011026 User Manual Issue 01 (26.10.2021) 2
Contents
1. Health and Safety...........................................................................................................................................3
Health & Safety at Work, etc. ACT 1974 ...............................................................................................3
2. Declaration of Conformity .............................................................................................................................3
3. General Description .......................................................................................................................................3
4. General Operation .........................................................................................................................................3
5. Applicable Firmware ......................................................................................................................................3
6. Technical Support ..........................................................................................................................................3
7. Installation .....................................................................................................................................................4
General Electrical ..................................................................................................................................6
General Installation...............................................................................................................................6
Installation of Integral Discharge Pump (where applicable) .......................................................6
Installation of High-Level Alarm –HLA (where applicable) ..........................................................6
Beacon units - P.No. 1009254 (where applicable) ........................................................................7
Installation of High-Level Alarm –HLA (where applicable) ..........................................................7
For Biotec, Bioficient or BioSafe Applications.......................................................................................7
For Biodisc Applications ...............................................................................................................7
Completing the Installation...................................................................................................................8
Ancillary Equipment ..............................................................................................................................8
8. Configuration Programming ..........................................................................................................................8
Start Up .................................................................................................................................................8
Detailed Operation................................................................................................................................9
Alarms ...................................................................................................................................................9
Service.................................................................................................................................................10
Telemetry Relays Outputs...................................................................................................................10
Menu...................................................................................................................................................10
9. Technical Information..................................................................................................................................13
Control Unit.........................................................................................................................................13
LED Beacon 1009254...........................................................................................................................14
10. Default Timetables ..................................................................................................................................15
De-sludge Pump ..................................................................................................................................15
Motor/Blower .....................................................................................................................................15
Chemical Dosing Pump........................................................................................................................15

1011026 User Manual Issue 01 (26.10.2021) 3
1. Health and Safety
These warnings are provided in the interest of safety. You must read them carefully before installing or using
the equipment.
It is important that this document is retained with the equipment for future reference. Should the equipment
be transferred to a new owner, always ensure that all relevant documents are supplied in order that the new
owner can become acquainted with the functioning of the equipment and the relevant warnings.
To ensure that the equipment described is safe both for personnel and property it should be installed,
inspected, and maintained by or under the supervision of qualified persons (Electrician)
Covers must be kept locked. Observe all hazard labels and take appropriate action to avoid exposure to the
risks indicated. Ensure that you are familiar with the safe working areas and accesses. Ensure that the working
area is adequately lit.
The power supply to the equipment should be isolated at the main RCD before lifting the blower cover.
Take care to maintain correct posture, particularly when lifting. Use appropriate lifting equipment when
necessary. Always keep proper footing and balance. Avoid any sharp edges.
Health & Safety at Work, etc. ACT 1974
Regard should be taken of IEE Wiring Regulations, Codes of Practice, Statutory Requirements, and any specific
instructions issued by the supplier of these details.
Earthing - All equipment must be earth bonded in accordance with the latest IEE Wiring Regulations. For
clarity this has not been shown.
We reserve the right to alter these details without prior notice.
2. Declaration of Conformity
This product meets all the essential safety requirements of the relevant European Directives.
The full text of the Declaration of Conformity can be provided upon request.
3. General Description
The DTP control Panel is used to control and monitor the Kingspan Klargester Domestic Wastewater Treatment
Units. It is capable of operating multiple pump/motor outputs at set times in accordance with pre-determined
timetables.
4. General Operation
The control unit continuously monitors the internal timetables and operates the appropriate pump/motor
outputs according to a timetable entry. The status is shown on the display. The current time continues to be
updated internally by battery backup when the mains fail, and the control unit continues normally upon mains
being restored.
5. Applicable Firmware
The operation described in this manual refers to control units with the following firmware:
Firmware ID
Description
Version
FMW-1112
Kingspan 1002510
RV1.22
6. Technical Support
Technical support & PIN may be obtained from:
Kingspan Water & Energy –Service
College Road,
Aylesbury
HP22 5EW
Phone UK: 03332406868
Phone ROI: 04838362400
Or
Contact Kingspan Area Sales Manager

1011026 User Manual Issue 01 (26.10.2021) 4
7. Installation
Figure 1 1002510 Lid & Cover
Figure 2 Enclosure & Mounting Dimensions
Figure 3 Control Panel Wiring (1)

1011026 User Manual Issue 01 (26.10.2021) 5
Figure 4 DTP Control Panel Wiring (2)

1011026 User Manual Issue 01 (26.10.2021) 6
General Electrical
7.1.1. General Notes on Outside Electrical Installation
Only qualified and competent persons should carry out any electrical installation. Outside electrical
installations can present dangers that are not usually encountered in internal electrical wiring. External
equipment is subjected to the elements and attention must be made to the suitability of the cable, glands,
connection units etc. for outside use. All cable glands should be IP66, or better. The possibility of attack by
vermin should also be considered and adequate precautions taken.
These notes are not intended to replace the latest I.E.E. Wiring Regulations.
7.1.2. Electrical Supply
The electrical feed should be dedicated to the equipment and not used for any other purpose. The supply
should be via a suitable RCD unit backed up by either a motor rated fuse, or preferably a motor rated MCB of
suitable rating.
Ensure that the blower housing is protected by a suitable RCD to BS 4293 and MCB to BS 3871. Cable
installation below ground should be SWA to BS 6346, unless otherwise stipulated.
The RCD must be of the two-pole type rated at 25A/30mA. (If nuisance tripping is experienced then a
sensitivity of 100mA should be used, but this does reduce the personnel protection capability).
7.1.3. Cable Installation
The type and size of cable depends upon site conditions and distance. If conduit/ducting is possible then
providing mechanical and vermin attack protection is provided, single cables of adequate size can be used.
However, the preferable method would be to use steel wire armoured (SWA) cable. This should be buried in
the ground at a depth of 600mm laid on sand with warning tapes on the cable and an additional tape at a
depth of 150mm.
For loads up to 0.75kW and runs of less than 100 metres, 2.5mm² 3 core SWA is adequate. For loads up to
1.55kW and runs of less than 100 metres, 4.0mm² 3 core SWA should be used. It is a requirement to use the
unused core in the cable for the earth conductor and this should be sleeved with earth sleeving at both
connection points.
General Installation
The control panel must not be adjacent to the plant. It can be mounted in the blower housing (supplied with
Biotec / BioFicient / Biosafe Units), wall mounted or fixed to the mounting frame (available separately). It
should be positioned so it cannot be reached by someone standing in or on the unit. It would be advisable to
situate the control panel and beacon in a frequently viewed position, so if a fault alarm appears it will be seen.
7.2.1. Mounting Frame Installation (where applicable)
Set the frame legs in a concrete base, minimum 250mm thick and prop the frame to prevent movement until
the concrete has set.
Allow 350mm minimum clearance from finished ground level to the bottom of the panel.
7.2.2. Retrofit of Control Panel
This Panel can replace the Kingspan Panel (P.No. 010086 - Green Panel). The existing beacon (P.No. 010332)
will have to be replaced with the New Beacon (P.No. 1009254) which is provided with Control panel (P.No.
1002510) as it is not compatible with the new control panel.
Installation of Integral Discharge Pump (where applicable)
Using a suitable M20 gland, feed the pump power cable through Gland Hole and terminate to connections 1 &
2 (J6) according to Figure 3 & Figure 4.
Installation of High-Level Alarm –HLA (where applicable)
Fix the black plastic bracket to the side wall of the baffle (the exact position is on the drawing included with
the HLA kit). Secure the float cable in the cable gland as shown on the drawing in the HLA kit. Pull the float
cable through any installed ducting into the blower housing. Complete wiring according to Figure 3 & Figure 4.

1011026 User Manual Issue 01 (26.10.2021) 7
Beacon units - P.No. 1009254 (where applicable)
The Beacons provides an external visual indication which is used to indicate Failure & Service Reminders and
may be included in the Power and Pressure Failure Detection System (PPFDS). The beacon is provided with a
5m cable which can be extended to 30m. As supplied, the unit is protected against rain to IP65 and is supplied
ready to mount on a suitable surface. Complete wiring according to Figure 3 & Figure 4.
This unit is designed to be simple to install and safe in operation. Any modification may adversely affect its
weather resistance in operation. If in any doubt, please consult us for advice. This is a sealed unit and not
serviceable.
Installation of High-Level Alarm –HLA (where applicable)
Fix the black plastic bracket to the side wall of the baffle (the exact position is on the drawing included with
the HLA kit). Secure the float cable in the cable gland as shown on the drawing in the HLA kit. Pull the float
cable through any installed ducting into the blower housing. Complete wiring according to Figure 3 & Figure 4.
For Biotec, Bioficient or BioSafe Applications
7.7.1. Power & Pressure Failure Detection System –PPFDS (where applicable)
The panel is designed to be used in conjunction with the Beacon unit to provide warning of either loss of
power or air pressure failure.
For panels mounted outside the blower housing, additional tubing can be purchased, contact your local sales
team for details. The panel can be mounted up to 30m away from the blower with no effect on the
performance of the pressure failure detection system.
To prevent damage to the PPFDS hole is fitted with a nylon bolt and nut. If the PPFDS is to be used, replace the
bolt with the air inlet bulkhead fitting supplied inside the control unit. A short length of 4mm silicone tubing
and a cable tie is also supplied. Connect the tubing from the bulkhead fitting to the Top Port of the pressure
switch, SW2, see Figure 5. Tie the cable tie on the pressure switch to prevent the tubing slipping off as it is not
barbed.
Figure 5 - Pressure switch tubing
For Biodisc Applications
Using a suitable M20 gland, feed the motor power supply cable through Gland Hole and terminate to
connections according to Figure 3 & Figure 4.
7.8.1. Installation of Sludge Return Pump (where applicable)
Using a suitable M20 gland, feed the integral discharge pump power cable through Gland Hole and terminate
to connection according to Figure 3 & Figure 4.

1011026 User Manual Issue 01 (26.10.2021) 8
7.8.2. Installation of Chemical Dosing System (where applicable)
Using a suitable M20 gland, feed the chemical dosing pump power cable through Gland Hole and terminate to
connection according to Figure 3 & Figure 4.
Connect the other end of the chemical dosing pump power supply cable to the junction box in the plant
(marked CHEMICAL DOSING).
Set the run and pause times for the chemical dosing pump as described in 10. 10Default Timetables
Completing the Installation
Complete all wiring according to Figure 4 DTP Control Panel Wiring (2)
Plug the lead from the battery into the small white socket below the battery on the PCB marked J3. After
finishing wiring, replace the isolator cover and screw. Turn the mains supply on at the source. Turn on the
panel using the isolation switch. It should now be illuminated RED. The display should now show text.
Replace the top cover and screws carefully so as not to damage buttons, ensuring the lid is fixed correctly.
Follow Guide in Section 8 Configuration Programming to enable programming.
Ancillary Equipment
Ancillary items should be installed in accordance with the Installation Guide supplied e.g. Sewage Pump
Station/Effluent Pump Station/Effluent Sample Chamber.
8. Configuration Programming
Start Up
When the control unit is powered up for the first time, the display will prompt for the country to be selected.
Figure 6 Keys for Configuration
Figure 7 Initialisation

1011026 User Manual Issue 01 (26.10.2021) 9
Detailed Operation
Once the initialisation is complete the operating screen will appear as follow. Page 1 to 6 can be navigated
using ◄& ►key.
Figure 8 Main Screen Page 1
Figure 9 Main Screen Page 2
Page 3 to 6 are like the above, for Motor / Blower & Chemical Dosing Pump.
Press down key to show the date and time when the next service is due.
If only the pin is used this will show an upcoming date. If not activated, this will show a 2021 date.
Figure 10 Next Service Due
Press down arrow again to return to the initial screen showing the now activation time.
Alarms
The conditions shown below cause an alarm message to appear on the display, the beeper sounds, the beacon
flashes, and the common alarm telemetry relay is de-energised. Some alarm conditions are recorded in the
event log, along with the date and time. The display will cycle through messages if multiple alarms exist at the
same time. The alarm message(s) will disappear when the alarm condition(s) have been cleared.
•Mains failure
•Low battery
•Loss of rotation
•High level float probe
•Auxiliary input
•Blower pressure
•Pumped outlet fuse
•De-sludge pump fuse
•Motor/blower fuse
•Chemical dosing pump fuse
•Service due
The beeper can be muted by pressing the ‘’ button. The beeper will sound again after SIX HOURS if any
alarm condition still exists.
Date 2022-05-17
Time 13:14:15

1011026 User Manual Issue 01 (26.10.2021) 10
Service
8.4.1. Service Due Date
The Service Due Date can be viewed on main screen by pressing ‘▼’until the date and time are shown.
8.4.2. Service Alarm
If the service alarm is activated using PIN, service alarm is reported on the display every 360 days, by default.
The beacon flashes and message “Contact Service Provider” pops every few seconds.
The beacon will stop flashing by pressing the ‘’button. A service symbol appears on the screen until the next
service is done & a contract renewed.
Telemetry Relays Outputs
There are three volt-free contacts available for alarm reporting to external systems. Follow Guide on Figure 4
for wiring.
Menu
Menu allows timetable entries to be edited, event log to be viewed, date/time, settings, service, battery and
setting factory defaults.
This menu is intended for use by installation & Service engineers only.
The menu is entered by simultaneously pressing then releasing the three buttons ‘◄, ►& ▲’.
On entry to the menu all outputs and telemetry relays are switched off.
Figure 11 Menu - Edit Timetable
The current option is shown on the bottom row and is selected by ‘▲’ and ‘▼’. Press the ‘’ button to
proceed with the current option.
Pressing ‘’ or ‘◄’ will return to normal operation.
8.6.1. Edit Timetables
Use ‘◄’ and ‘►’ to select between Start, Stop, Run, and Pause times for the current timetable entry.
Use the ‘’ button to edit the entry. A flashing cursor will appear over the first digit of the hour. Use ‘▲’ and
‘▼’ to increment and decrement the digit, respectively. Use ‘◄’ and ‘►’ to move to the previous or next digit
in the time, respectively. Once the entry has been edited, press the ‘’ button to save changes and exit edit
mode, or press the ‘’ button to cancel changes and exit edit mode.
Use ‘’ or ‘◄’ to return to the menu.
Figure 12 Editing Timetable
Menu
Edit Timetable

1011026 User Manual Issue 01 (26.10.2021) 11
8.6.2. Event Log
This option shows the last ten alarm conditions that have occurred along with the date/time. An event is also
recorded when the alarm clears. The message “Log is Empty” will appear if no alarms have been recorded yet.
Use ‘▲’ and ‘▼’ to move through the events. Use ‘◄’ and ‘►’ to alternate between the event message and
the date/time the event occurred.
Use ‘’ to return to the main menu.
8.6.3. Set Date & Time
This option allows the current date and time to be set in the 24-hour format. The display will show:
Figure 13 Date & Time
Use ‘▲’ and ‘▼’ to move between date and time. Pressing the ‘’ button will freeze display of the clock and
enter edit mode to allow the date or time to be set. A flashing cursor will appear. Use ‘▲’ and ‘▼’ to
increment and decrement the digit, respectively. Use ‘◄’ and ‘►’ to move to the previous or next digit,
respectively. Once the desired date or time has been set, press the ‘’ button to save changes. Use ‘’ to
return to the main menu.
8.6.4. Settings
Setting can be used to amend inputs such as Loss of Rotation or Loss of Pressure, High Level Alarm & Beeper.
LOR or LOP & High-Level Alarm will be enabled / disabled during the initialisation.
Figure 14 Settings
Date 2021-05-17
Time 13:14:15

1011026 User Manual Issue 01 (26.10.2021) 12
8.6.5. Service
This allows setting the interval between which service alarms occur. The default is 360 days.
Figure 15 Service
8.6.6. Battery
This displays the battery charger status. The display shows “Not Charging” when mains power is absent. The
charging countdown is paused.
“Standard charge”is displayed when the control unit first has power applied or the internal reset switch is
pressed. This last for 16 hours and a countdown is shown on the display. “Intelligent Charge”is displayed
when power is interrupted and shows the amount of time until the battery is fully charged. “Trickle Charge”
indicates that the unit is fully charged and maintaining the battery.
8.6.7. Factory Defaults
This option allows the control unit to be set back to the defaults as they were when the unit left the factory.
The following will be reset with defaults shown in brackets.
•Unit not activated
•Country (GB & IRE (Eng.))
•Timetables (see 10. Default Timetables)
•Event log (empty log)
•Service interval (360 days)
•Inputs (disabled)
•Blower/motor (blower)
Figure 16 Factory Default
Initially the “No”option will be highlighted to prevent accidentally setting factory defaults if this was not
intended.
Use the ‘◄’ button to move to the Yes option and press the ‘’ button to confirm. The display will show:
A few seconds later the unit will restart and prompt for the country to be selected. See section 8.1 Start Up
Factory Defaults
Yes <No>
Restarting...

1011026 User Manual Issue 01 (26.10.2021) 13
9. Technical Information
Control Unit
Model
1002510
Enclosure
Dimensions: 255mm (W) x 180mm (H) x 88mm (D)
Ingress Protection: IP65
Material: ABS
Lid Screws: Torque: 1.2Nm, Size: PH 2
Operating Environment
Operating temperature: -20°C … +50°C
Relative humidity: 100%
Altitude: 2,000m
Pollution degree: 2
Intended for use indoors or outdoors, and in wet locations
Power Source
230VAC ±10% 50Hz
Mains isolator switch internal to unit
Power Consumption
(Control unit only)
6.4W, 10.1VA, cos φ = 0.63
All relays energised, battery
charging, beacon off, J6 - J9
disconnected
11.3W, 17.8VA, cos φ = 0.63
All relays energised, battery
charging, beacon on continuously
(not flashing), J6 - J9 disconnected
Power Consumption
(Control unit and
pumps/motors and beacon)
1.6kW, 1.8kVA, cos φ = 0.89
All relays energised, battery charging, beacon on continuously (not
flashing)
J6 –Pumped outlet
J7 –De-sludge pump
J8 –Blower
J9 –Chemical dosing pump
Grundfos KP 350
Grundfos KP 250
Secoh JDK-250
Kingspan 404390
Fusing
F1 (De-sludge pump, terminals
3&4)
T 5A H 250V
F2 (Internal power supply unit)
T 2A H 250V
F3 (Motor/blower, 5&6)
T 3.15A H 250V
F4 (Chemical dosing pump, 7&8)
T 250mA H 250V
F5 (Pumped outlet, 1&2)
T 5A H 250V
F6 (Beacon output, 21&22)
500mA resettable fuse
Electrical Safety
IEC/EN 61010-1:2010+A1:2019, Class I, CAT II
Battery Backup
6V 1200mAh NiMH battery pack kept charged by on-board charger.
Backup time at least 12 hours.
Inputs
3 x inputs from volt-free contacts (rotation arm, float switch and external
alarm condition such as pressure switches in series)
1 x blower pressure sensor (alarms below 15mB, 4mm inlet)
Mains Outputs
Relays only energised when mains power is present.
Pumped outlet (1&2)
Constant mains output,
fused T 5A H 250V
De-sludge pump (3&4)
SPST relay switched,
fused T 5A H 250V
Motor/blower (5&6)
SPST relay switched,
fused T 3.15A H 250V
Chemical dosing pump (7&8)
SPST relay switched,
fused T 250mA H 250V
Telemetry Relay Outputs
3 x volt-free SPST contacts. De-energised in alarm condition.

1011026 User Manual Issue 01 (26.10.2021) 14
Use only with 30V, 3A AC/DC max.
Unfused
Relays only energised when mains power is present.
Terminals 15&16
Mains failure
Terminals 17&18
Motor or blower failure
Terminals 19&20
Common alarm
Beacon Output
Output suited for use with 1009254 LED beacon.
Flashes continuously on alarm when mains present, 12 hours in battery
backup mode.
Mains Outputs Voltage Sensing
Pumped outlet, de-sludge pump, motor/blower, chemical dosing pump.
The voltage is monitored on these outputs to determine if a fuse has
blown. An alarm is raised in such a condition.
PPFDS Input
4mm barbed air inlet for pressure sensing. Alarm below 15mB.
Audible Alarm
Internal sounder sounds in bursts at intervals on alarm.
Can be muted for 6 hours by pressing enter key on front panel.
Can de disabled from on-screen menu.
Keypad
Left, right, up, down, back and enter.
Display
16 x 2 character LCD
Green power LED
Real-Time Clock
Event log timestamps and controlling the operation of the
motors/blowers according to a timetable
LED Beacon 1009254
Only the LED beacon 1009254 should be used with the 1002510 control unit as it has been specifically
designed for this product. Although a 12V beacon could be used when the control unit has mains power
available, in battery backup mode the voltage available is only nominally 6V and the 12V beacon would
probably fail to operate and 6V beacons are not commonly available. For these reasons and to keep the
beacon brightness constant on mains power and battery backup, the 1009254 has internal constant current
circuitry to maintain a constant 400mA consumption.
Model
1009254
Enclosure
73mm (Diameter)
48mm (Height)
11.5mm (Base mounting plate height)
Ingress Protection: IP65
Material: ABS
Operating Temperature
-20°C … +50°C
Operating Voltage
6 –12V
Current Consumption
400mA constant current
Static/Flash
Flash rate and duration controlled by firmware in 1002510 control unit
Lens Colour
Red
Cable Length
5m

1011026 User Manual Issue 01 (26.10.2021) 15
10. Default Timetables
De-sludge Pump
10.1.1. UK, Germany, France & Poland
Function
Default
Bioficient
BioFicient + 1
BioFicient + 2
Start Time
00:00:00
00:00:00
00:00:00
00:00:00
Stop Time
23:59:59
23:59:59
23:59:59
23:59:59
Run Time
00:00:20
00:05:00
00:01:00
00:01:30
Pause Time
02:00:00
01:00:00
01:00:00
01:00:00
Table 1 De-Sludge Default (GB & IRE, DE, FR, PL)
10.1.2. Norway
Start Time (Time of Day where Unit is started)
:
00:00:00
Stop Time (Time of Day where Unit is stopped)
:
23:59:59
Run Time (Time for the components to Run)
:
00:00:20 (20 Sec)
Pause Time (Time for the components to Stop)
:
02:00:00 (2 hours)
Table 2 De-Sludge Default (Norway)
Motor/Blower
Start Time (Time of Day where Unit is started)
:
00:00:00
Stop Time (Time of Day where Unit is stopped)
:
23:59:59
Run Time (Time for the components to Run)
:
23:59:59 (24 hours)
Pause Time (Time for the components to Stop)
:
00:00:00 (0 minutes)
Table 3 Motor / Blower Default
Chemical Dosing Pump
10.3.1. UK, Germany, France & Poland
Start Time (Time of Day where Unit is started)
:
00:00:00
Stop Time (Time of Day where Unit is stopped)
:
23:59:59
Run Time (Time for the components to Run)
:
00:00:03 (3 Sec)
Pause Time (Time for the components to Stop)
:
00:25:00 (25 minutes)
Table 4 Chemical Dosing Default (GB, DE, FR, PL)
10.3.2. Norway
Function
BA (Default)
BB
BC
BD
Start Time
06:00:00
00:00:00
00:00:00
00:00:00
Stop Time
22:00:00
23:59:59
23:59:59
23:59:59
Run Time
00:00:02
00:00:03
00:00:04
00:00:03
Pause Time
01:00:00
00:12:00
00:12:00
00:06:00
Table 5 Chemical Dosing Default (Norway)

1011026 User Manual Issue 01 (26.10.2021) 16
This Page Intentionally Left Blank
Table of contents
Other Kingspan Control Panel manuals
Popular Control Panel manuals by other brands

Marco
Marco SCS 165 20 415 Instructions for use

Rosslare
Rosslare AC-020 Hardware installation and user's guide

Ikegami
Ikegami OCP-399 Operation manual

Masterbuilt
Masterbuilt GF34G1M instruction sheet

Steamist
Steamist TC-135 Installation and operating instructions

EasiWise
EasiWise Standard Quick start user guide