Kioto Solar SL 50 e User manual

InstallatIon and operatIng manual Stratified Charging Station
1
Typesetting, printing errors and technical modications reserved
Installation and operating manual
STRATIFIED CHARGING STATION EN
SL 50 E
March 2016

2
Typesetting, printing errors and technical modications reserved
Table of content
General 3
Use 3
Application example 3
Description 3
Warning 3
Warranty 3
Structure of the stratied charging station 4
Technical Data 5
Installation and Commissioning 6
Installation 6
Positioning 6
Wall mounting 6
Drilling plan 7
Buffer mounting 8
Hydraulic connections 9
Electrical connections 9
Commissioning 9
Fillingandushingofcollectorcircuit 10
Regulations 11
Pump characteristic lines 11

InstallatIon and operatIng manual Stratified Charging Station
3
Typesetting, printing errors and technical modications reserved
General
Beforeyouinstallyournewstratiedchargingstation,pleasereadallchaptersthoroughlyandpayspecialattentiontowar-
nings provided in chapter "Warning". Incorrect handling can result in damage to the installation.
Use
TheSL50Estratiedchargingstationenablestheloadingofabuffertankdependingonthetemperature.
Stratiedlayerloadingisspeedregulated,energyefcientandsuitableforlargebuffertanks.
Application example
S3
S1
S5
S7
Speicher 1
V1
(P2)(P1)
R4
R3R1
S2
S1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
S2 S3 S4 S5 S6 S7 S8
R4
R5
IP20
R5
N
R1-R4
100 ... 240 V~
50-60 Hz
T4A
1 (1) A (100 ... 240) V~
4 (1) A 240 V~
4 (1) A 24V
R5
R3
R2
R1
L' L
Temp. Sensor
RPD
N
Isolate mains before removing cover!
Vor Öffnen Gerät spannungslos schalten!
Use ground common terminal block
Masse-Sammelklemme benutzen
Use neutral conductor common terminal block
Neutralleiter-Sammelklemme benutzen!
Use PE Common terminal block
Schutzleiter-Sammelklemme benutzen
VFD
DeltaSol®BX PlusV2
KIOTO Clear Energy AG
A - 9300 St.Veit a.d. Glan
S9
V40 S10
V40
PWMA
0-10V
PWMB
0-10V
PWMC
0-10V
PWMD
0-10V
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
CS10 VBus
Description
TheSL50Estratiedchargingstationisusedforconnectingasolarcollectorsystemofupto50m²toabuffertank.
Thesolarheatfromthecollectorsystemistransferredtothebuffersystemwithhighly-efcientheatexchangers.Thereby,it
providesanintelligentcontrolsystem,dependentonsunlight,foroptimuminteractionbetweenthesolarandbufferloading
pumpandguaranteeshighheattransfercapacity.Thestationisspeedregulatedfromthebuffersideanddependentonthe
temperatureoftherespectivetanktemperaturezone.
Warning
• Installationandoperationshouldbeexecutedinaccordancewiththelocallyapplicablespecicationsandstandardpractices.
• Onlyqualiedtechnicalpersonnelmaycarryoutinstallation,maintenanceandcleaningofthelayerloadingstation.
• Unauthorisedmodicationsorchangesarenotpermittedforsafetyreasonsandwillinevitablyleadtothevoidingofthe
warranty for the machine.
• Theoperatingpressuresprovidedmaynotbeexceeded!
• Ifanyerrorsoccur–nomatterofwhattype–pleasecontactyourinstaller.Pleasedonotcarryoutanyrepairsyourself,
sincethesearenotpermittedbylawandyoucanexposeyourselftohazardsasaresult.
Warranty
The manufacturer provides a warranty of 2 years from the date of delivery on the supplied products and components.
Unauthorisedmodicationsorchangesarenotpermittedforsafetyreasonsandwillinevitablyleadtothevoidingofthewarrantyforthemachine.
Forfurtherinformationseewww.kiotosolar.com

4
Typesetting, printing errors and technical modications reserved
3
7
5
8
9
4
1
2
6
FG
E
D
C
A
B
H
10
11
12
13
14
1 Temperaturesensorbufferow
2Actuator (electrical)
3Plate heat exchanger
4Resetvalvebuffercircuit
5High-efciencypumpbuffercircuit
6Flowmeterbuffercircuit(electronic)
7Pressurereliefvalve6bar
8Resetvalvesolarcircuit,returnow
9 Manometer
10 High-efcientpumpsolarcircuit
11 Flow meter solar circuit (mechanical)
12 Solar vent
13 Valvesolarow
14 Temperaturesensorsolarowline
Connections
AKFEvalveAllingnozzlesolar
BKFEvalveBdrainingnozzlesolar
CBuffer return
DBufferowlinecentre
EBufferowlinetop
FSolarowline
GSolar return line
HExpansiontank
Structure of the stratied charging station
Duetotechnicaladvancements,wereservetherighttomakeconstructionalchangesonourproducts.Eachofthese
changesaretakenintoconsiderationintheoperatingmanualbyreplacingtherespectivepages.
Thestationappearancemaysometimesvaryfromtheillustration!

InstallatIon and operatIng manual Stratified Charging Station
5
Typesetting, printing errors and technical modications reserved
Technical Data
Stratied charging Station SL 50 E
Width x Height x Depth [mm] 496 x 930 x 325
Cover EPP black
Solar piping [mm] Copper pipe - Ø 22 x 0,8
Buffer piping [mm] Metal hose stainless steel 1.4404 - Ø 26,2 x 0,18
Weight [kg] 25
Connections
AKFEvalvellingnozzle G ¾" AG
BKFEvalvepurgingnozzle G ¾" AG
CBufferreturnlinecoldballvalve G1" AG
DBufferinowlinewarmballvalve G1" AG
EBufferinowlinehotballvalve G1" AG
FSolarinowline G1" AG
G Solar return line G1" AG
HExpansiontank G¾" AG
Maximum operating pressure
Collectorcircuit[bar] max. 6
Buffercircuit[bar] max. 3
Solar pump Yonos Para HU 25/7.0
Nominalvoltage[VAC/Hz] 230 / 50
Nominaloutput[W] 3 - 45
max.deliveryheight[m] max. 7
Buffer charging pump Yonos Para HU 25/7.0
Nominalvoltage[V/Hz] 230 / 50
Nominaloutput[W] 3 - 45
max.deliveryheight[m] max. 7
Plate heat exchanger (glycol/water)
Power[kW] 26
Inlettemperature[°C](glycol/water) 60 / 29
Outlettemperature[°C](glycol/water) 35 / 54
Flowrateamount[l/h] 1000

6
Typesetting, printing errors and technical modications reserved
Installation and Commissioning
Installation
Theerectionandinstallationmustbedonebyanapprovedtechnicalfacility.Thisfacilitywillalsotakeontheresponsibility
forcorrectinstallationandcommissioning.Adry,frost-freeroomthatprovidessufcientspaceformaintenancework
is requried as the installation site.
Thestratiedchargingstationmustbeinstalledsothatitisprotectedfromsplashingwaterandmayonlyberunatroom
temperaturesbelow40℃.
Positioning
Itisrecommendedthatinstallationtakeplacenearthebuffertankinordertopreventheatloss.
Thisshouldtakeplaceonalevelandstructurallysuitablesurfacethatisprovidedforlevelingadjustablestandfeet.
Pulling too hard on the installation screws damages the isolation.
Wall installation
Wallinstallationtakesplaceasfollowswiththeincludedattachmentmaterial
(3xM8stairbolts,M8nutsand3M8washers):
• Drill at least 8 cm deep on the designated drill points with a ø 10 mm drill according to the drillling template included.
• Afterwards,insertthewallplugintotheholeandscrewthestairboltsintothewalluntilthewallplugthreadsarenolongervisible.
• Now,hangthestratiedchargingstationonthethreadedstudsandinstallitwithnutsandwashers.

InstallatIon and operatIng manual Stratified Charging Station
7
Typesetting, printing errors and technical modications reserved
Drillling template for wall installation
496
930
154
745
591
120
35,7
31,8

8
Typesetting, printing errors and technical modications reserved
Tank installation
Thebuffersensorinthebufferterminalblockismountedbeforethestationisassembled.
• Step 1
Beforemountungthestratiedstationthebuffersensorshavetobemounted.
• Step 2
Installandtightenthe3threadedboltsandthe3corrugatedtubeincl.sealsontotherespectivetankconnectors.
• Step 3
Slidethestratiedchargingstationoverthecorrugatedtubesandthethreadedboltsandfastenthestationtothetank
using washers and nuts.
• Step 4
Tightenthe3corrugatedtubestothestationwiththeseals.
max. 70 Nm
max. 10 Nm
max. 70 Nm
Dichtung immer zwischen
Kugelhahn und Ringwellschlauch
1
3
2
4
Schnitt C-C
M1 : 6
C
S7
S2
TRENNBLECH

InstallatIon and operatIng manual Stratified Charging Station
9
Typesetting, printing errors and technical modications reserved
Hydraulic connection
Lineconnectiontakesplaceaccordingtotheinstallationlayoutinthismanual,(see"Applicationexample")
• Thelinepathstothebuffershouldbeasshortaspossible!
• We recommend steel or copper piping as line material.
Theinstallationorderhastobefollowedforalllinesandttingsinordertopreventelectro-chemicalcorrosion.
• Installationofagravitationalheatingsystemisnotpermitted!
• Connectionofthecollectioncircuitexpansiontankmusttakeplaceasadirectconnection.
• Installationofshut-offvalves(exceptforsuitablemaintenancemoduleslikecapvalves)isnotpermitted!
• Connectionshavetobetightenedonlyafterthetubinghasbeensealed.Tighteningtorqueand/orforceeffectson
preinstalledstationcomponentsandjointsmustbeavoided!
Additionally,checkallatsealingscrewsforproperswivelnuttighteningtorque(screwscanbecomelooseduringtransport!).
Electrical connections
Internalwiringofelectricalequipmentisconductedonsite.Connectiontothepowersupply(230V/AC,50Hz)takesplaceby
meansofthepreclampedsupplycable.
Thebuffersensorsincludedareinstalledontherespectivebuffertankmeteringpointsandconnectedtotheaffectedcontrol
clampsaswellasthecollectorsensorincludedinthescopeofdelivery.Detailledinformationabouttheintegratedcontrolin
thestationcanbefoundinthecontrollermanual.
Workonlivestationpartsmustonlytakeplaceunderconsiderationfortherespectiveguidelinesofthepowercompanyand
valid,correspondingstandards.
Commissioning
Onlyusewaterpreparedaccordingtothestandards(e.g.ÖNORMH5195-1:2010).Alllinesmustbediffusionresistant.
Fillingandcommissioningmustbedonebyanapprovedtechnicalfacilityandconcessionarypersonnel.Here,thefunctionand
tightnessagainstleaksoftheentireplantincludingthepartsassembledinthemanufacturingworksshouldbechecked.Safety
valvefunctionalityhastobecheckedatregularintervals.Annualmaintenancebyanapprovedtechnicalfacilityisrecommended.
Slowlyopeningtheballvalveonthestationinletsandoutletspreventspressureblowsduringcleaningmode.Usethecleaning
connectionsprovidedforllingthecollectorcircuit.See"Stucture".
Thellingandrinsingmustbecarriedoutuntilitisensuredthatthesystemiscompletelyde-aerated.Flownoisesduringbuf-
ferpumpoperationindicatethatthereisstillairinthemachinethatcanberemovedviathepumpandmanualprimer.
Closethecollectorreturnlineattheendofthellingprocessandadjustthesystempressuretoapprox.3bar(thisappliesto
expansiontankswithasystempressureof2.5bar,thestaticheightofthemachinemustbetakenintoconsiderationaswell).
Beforeopeningthecontrolboxhousing,ensurethatitisdisconnectedfromthepowersupply!
Donotllindirectsunlight,becausethiscanleadtosteamhammering!

10
Typesetting, printing errors and technical modications reserved
Cleaning and lling the collector circuit
Thellingandrinsingmustbecarriedoutuntilitisensuredthatthesystemiscompletelyde-aerated.Flownoisesduring
collectorpumpoperationindicatethatthereisstillairinthemachinethatcanberemovedviathemanualprimer
Beforestartingwiththecleaningand/orllingprocess,pleasereadcarefullythroughthefollowingpointsthoroughly!
Solar-side (collector side)
• Onlyglycolwatermixtures(frost-resistanttoatleast-25°)maybeusedforllingthesolarcircuit
• Beforestartingwithcleaningandlling,ensurethatallconnections(solarforward/returnows,etc.)
are provided with correct seals and are tightly connected.
• ConnectthellpumpforwardowtoKFEvalveA(llingnozzle).
• ConnectthellpumpreturnowtoKFEvalveB(purgingnozzle).
• First,openKFEvalveA(handleinowdirection).
• Now,openKFEvalveB(handleinowdirection).
• Startthecleaningprocessofthesolarcircuitbyswitchingonthellingpump.
• Letthepumprununtiltheglycolwatermixtureowsbackintothetankwithoutbubbles.
• CloseKFEvalveB(handleagainstowdirection).
• Pay attention to the gauge.
• Whenthegaugehasreachedthedesiredoperatingpressure,closeKFEvalveA(handleagainstowdirection).
• Now,thepumpcanbeswitchedoffandthellingpumpconnectionscanbedisconnectedfromtheKFEvalvesAandB.
• Thesolarcircuitisnowcompletelylledandreadyforuse.
• Shouldairnoisebediscoveredinthecircuitduringoperation,thenbeginwithpoint1again.
Buffer-side
• OnlyheatingwatermustbeusedaccordingtonormÖNORMH5195-1:2010forllingthebuffercircuitandbuffertank.
• Beforestartingtoconnecttheconnectionlinesfromthestationtothebuffertank,
closeballvalvesC,DandE(handleagainstowdirection)onthestation
• Beforestartingthelling,makecertainthatallconnectionsareprovidedwithcorrectsealsandaretight.
• Now,openallvalvestotheconnectionlinesonthebuffertank.
• Now,openvalveC,thenvalveDandnallyvalveEonthestation.
• Ifnowaternoiseisheard,switchthebuffercircuitpumponmanually.
• Letthisprocessrunforseveralminutes.Afterwards,switchthepumpoff.
• Ventthebuffertankandtop-offwithheaterwaterifnecessary.
• Thebuffercircuitisnowcompletelylledandreadyforuse.

InstallatIon and operatIng manual Stratified Charging Station
11
Typesetting, printing errors and technical modications reserved
Pump characteristic lines
Regulations
Thestationistobeconnectedwithconsiderationtothefollowingnorms,country-specicguidelines
and local water company regulations.
• DINEN12828 Heatingsystemsinbuildings
• DIN1988 Technicalrulesfordrinkingwatersupplyinstallation
• DIN 4708 Central heat water installations
• DIN 4751 Heating system safety equipment
• DIN4753 Waterheaterandwaterheatingsystemfordrinkingwaterandservicewater
• DIN 4757 Solar heating and solar-thermal systems
• DIN 18380 Central heating systems and service water systems
• DIN18381 Gas,wateranddrainageinstallationworks
• DIN18382 Electricalcableandwiringsystemsinbuildings
• DIN EN 12975 Thermal solar systems and their components
• VDE 0100 Setting up electrical operating equipment
• VDE 0185 General notes for setting up lightning protection systems
• VDE 0190 Main potential equalisation of electrical systems
• ÖNORMENISO9488 Solarenergy–Vocabulary(ISO9488:1999)
• ÖNORM ENV 12977-1 Thermal solar system and their components – customised systems
• ÖNORMM7700 Solarenergy-termswithdenitions
• ÖNORM M7701 Solar engineering systems - approximation methods for measuring
• atcollectorsinhotwatertreatmentsystems
• ÖNORM M7731 Solar heating plants for heating water – requirements and tests

12
Typesetting, printing errors and technical modications reserved
Contact: