KIOUR REF-FR Series User manual

KIOUR Type REF-FR Model REF-FR-SM V2.0
Electronic digital refrigerator controller (Compact) with ON-OFF function, level water
control, dfrost control (valve or resistance), fan, ON-OFF relay and buzzer ALARM.
Range -45 -+150 °C/°F.
Electronic controller REF-FR is a compact unit for refrigerator’s control. It is ideal for
ventilated refrigerator rooms of low temperatures with dfrost control. It is provided with 5
relays: compressor (30 A, 2HP), fan (5A), valve or resistance (12A), level control (5A), ON-
OFF relay and a buzzer ALARM.
It controls two temperatures with its two sensors in range of -45 - +150 °C/°F, while it has
an Off state, in which all relays are off and OFF is displayed. Also it is provided with one input
for level control (Patent No.1004976) and one input for open door. If the door opens the fan
stops. After four minutes the compressor also stops and the ALARM of the open door is
displayed, while the buzzer is ON.
MANAGING THE UNIT
↵: By pressing ↵the parameter’s menu is displayed.
df :By pressing df for five minutes, a dfrost cycle is forced.
T2 :By pressing Τ2,the temperature of the evaporator is displayed.
RESET
: By pressing for 1 sec, the setup °C or °F is displayed.
:By pressing RESET, the display of the ALARM and the buzzer stops.
:By pressing for 3 sec, the state changes from OFF to ON or from ON to OFF.
MANAGING THE PARAMETERS
1. By pressing ↵, the first parameter SPo (Set Point) is displayed and with the arrow buttons we can see the other parameters
as they appear in the table below.
2. By pressing SET, we can see the value of the parameter and with the arrow buttons we can change the value. We confirm
the new value with the enter (↵), while the name of the parameter is displayed. If we press SET, we cancel the new value and
the name of the parameter is displayed.
3. To exit the parameters, we press ↵.
NOTE: For security reasons, we can’t see all the parameters. To access them all, we enter the value 22 to the Cod parameter.
OPTICAL SIGNS - ALARMS
ALo
AHi
LF1
: Low temperature of room
:High temperature of room
: Malfunction of the room’s sensor
LF2
dor
:Malfunction of the evaporator’s sensor
: Open door. If the door remains open for 4 minutes, the
compressor stops, an ALARM is displayed and the buzzer is ON.
SERIAL INPUT
Via serial input the instrument is connected to the memory backup (key) or to a network.
1. Memory backup (key): With the key we save the setup of the parameters. We connect the key to the instrument and:
a. By pressing SET and the UP button, the instrument connects to the key and the message Eo is displayed.
b. By pressing UP button, the instrument reads the parameters from the key and the message ro = read O.K. or rF = read
Fail is displayed.
b. By pressing DOWN button the instrument writes the parameters to the key and the messages Yo = Write o.K. or YF =
Write Fail is displayed.The key can be connected to various types of instruments. If you try to read the parameters of a
different instrument, a message rF = read Fail is displayed.
At all instruments and at any time we can perform the write operation. After 10 sec, the key is disconnected automatically.
2. Connect to network: The device can be connected to the CAMIN net (RS485 Modbus protocol) though an interface, NET-IN-1.
CAMIN is an application designed to collect information, watch and fully control a net of devices. The maximum length of the
net can be 1000 meters.
TECHNICAL SPECIFICATIONS
•Power supply: 12 VAC/DC
•Accuracy: 0.5 % ±1 digit
•Connection: TAB 6,3 mm (DIN46247)
•Relay 250 VAC 30 A Resistive Load 2 HP
•Relay 250 VAC 12 A Resistive Load
•Two relay 250 VAC 5 A Resistive Load
•Operating temperature: -10 - 60°C
•Storage temperature: -20 - +80°C
•Mounted through panel hole
•Security power supply: 0,5 A
•Maximum power consumption: 3 Watt
•Connection for two sensors
ATTENTION: It is necessary to prevent electrostatic discharges at the ventilation openings. Also prevent insertion of pointed
elements.
CONNECTION DIAGRAMS - DIMENSIONS
28
mm
76 mm
28
mm
70 mm
21 34567 8910111213
POWER
SUPPL
12 15%
Y
V
AC/
±
DC
KIOUR
REFRIGERATOR CONTROLLER T
y
pe REF-FR
Model REF-FR-SM. Ran
g
e -50 - +150 C/ F
o
V2.0
o
COMP.30A
1HP 115
2HP 230 .
VAV
VAC
R.DOOR
5A R.L.
LEVEL
L.
FAN
HEATER
L.
MADE IN
GREECE
Patent No.
1004976
Common
C
5
5A
12
25
A R.
R.L.
A R.
0V A
KIOUR
o
C
REF-FR
ALARM RESET
T2
dF
PTC
dFros PTC
o
WATER
LEVEL
INPUT
DOOR
tRo m
SERIAL
SET

REF-FR-SM
A/A PARAMETERS - DESCRIPTION
1 Spo Set Point temperature control room, Values: LSP to HSP
2 Alo Alarm of low temperature room, Values: -45 - +20 °C
3 Ahi Alarm of high temperature room, Values: 0 - +60 °C
4 dr1 Repeat time of dfrost, Value: 1 - 100 hours
5 Cod Code Number. The number 22 permits scrolling into the other parameters
6 diF Differential working temperature of compressor, Value: 1 - +20 °C
7 dd2 dfrost duration, 0 - 120 min, in which 0 means that dfrost is OFF
8 dP3 Dripping time, 0 - 15 min and compressor’s time pause after the dfrost
Display Operation at dfrost
9 dY4
dY4 = -1
dY4 = 0
dY4 = 1-40 min
:If the temperature of the room is greater than SPo+dif, dFr is displayed
:Temperature is displayed continually
:dFr is displayed from the beginning of the dfrost, until time expires
10 dE5 Temperature of dfrost: 1 - +70 °C. Sensor’s malfunction of the evaporator doesn’t make temperature control
and dfrost finishes from expire of time.
11 dt6 dfrost’s working mode, Values 0 and 1. 0 = Electrical: Compressor OFF, Resistance ON
1 = Hot GAS: Compressor ΟΝ, Resistance ΟΝ.
12 AF1 Alarm’s working mode. Values 0 and 1. 0=Auto, 1=Manual. At the auto set up (0) the disappearance of
the ALARM stops the buzzer etc. At the manual set up (1), the disappearance of the ALARM does not stop the
buzzer and the indication of the ALARM is displayed. In any case by pressing the down button we stop the
buzzer and the indication of ALARM but the flashing line of the display of the hundreds indicates that there is still
an ALARM. The RESET is valid until the disappearance of the last ALARM.
13 At2 At2 = -1
At2 = 0
At2 = 1 - 120 min
: The alarms of the room’s temperature do not activate the buzzer
: The alarms of the room’s temperature activate the buzzer immediately
: The alarms of the room’s temperature are activated after the time of the parameter’s
value expires. The ALARMS of the sensor’s fault and of the open door are activated
immediately.
14 Fo1 Below this evaporator’s temperature, the Fan is activated after the dfrost, Values: -50 - +50 °C/°F
Normal working of FAN
15 Ft2
Ft2 = -1
Ft2 = 0
Ft2 = 1-15 min
: The fan works continually.
: The fan starts and stops at the same time with the compressor.
: The fan operates at the same time with the compressor and stops after specific time,
indicated by the parameter’s value.
Fan working mode at dfrost
16 Fd3
Fd3 = 0
Fd3 = 1
Fd3 = 2
: During the dfrost, the Fan is OFF. It turns ON after the compressor is ON and if the temperature
of the evaporator is lower than the parameter’s value, Fo1
: The fan is ON if the evaporator’s temperature is lower than Fo1
: The fan is ON in both types of dfrost (ELE - GAS)
17 Co1 Minimum working time of the compressor, Values: 0 - 15 min
18 CP2 Minimum stop time of the compressor, Values: 0 - 15 min
Working mode of the compressor with a room’s sensor malfunction
19 CF3
CF3 = -1
CF3 = 0
CF3 = 1-150 min
:The compressor stops working.
:The compressor is always ON. The dfrost works according to time.
: The compressor works with fixed times, ΟΝ and OFF, that are defined from
the parameters CF3 and CF4. The dfrost, also, works according to time.
20 CF4 Working mode of the compressor with a room’s sensor malfunction
CF4 = 1-150 min. Stop time of the compressor.
21 SE1 Zero adjustment of sensor No 1. (Room), Values: -20 - +20 °C/°F
22 SE2 Zero adjustment of sensor No 2. (Evaporator), Values: -20 - +20 °C/°F
23 SEr Doesn’t work
24 LSP Lower limit temperature of SET POINT, Values: -50 - +100 °C/°F
25 HSP Maximum limit temperature of SET POINT, Values: -50 - +100 °C/°F
26 C_F 0 = °C
1 = °F
ATTENTION! The changes between °C and °F do not change the value of the parameters. (ex. SET
POINT 10 °C is 10 °F )
27 br Baud Rate
28 trE time respond: the respond time of the instrument, Values in mSec with default 20 mSec
29 Add Address of instrument at the network operation, Values: 1 - 255
Guarantee of good operation: Two (2) years.
Guarantee terms. The guarantee is valid if the operating instructions are followed.
The repairing and the service of the instrument must be done by an authorized technician.
The guarantee covers only the repairing or the replacement of the instrument.