
C2. Lower analog output voltage. Compressor C2 of the 2nd circuit. The analog signal 0-10 Volt
corresponds consistently to C2. Values from 0 to 4.0 Volts. The analog output will be between C2U -
C2d in a temperature range defined by the parameter C2H or C2C. For example, C2U - C2d = 7 and
C2H = 3 and SHt =45°C, the voltage will change 10-3Volt from 42 ÷ 45°Con heating (see figure 5B).
C2. Higher voltage at the analog output.
C2. In the heating. Temperature / pressure range to which the analog output voltage corresponds.
C2. In the cooling. Temperature / pressure range to which the analog output voltage corresponds.
C2. Reverse analog signal at the output
C2. Increasing the value reduces the oscillation of the 0-10 Volt signal.
FAN 2. Lower analog output voltage. 2nd circuit. Values from 0 to 4.0 Volt. The analog output will
range between F2U - F2d in a temperature range defined by parameter F2H or F2C. For example,
F2U - F1d = 7 and F2H = 3 and SHt = 45 °C, the voltage will change 10-3 Volt from 42 ÷ 45 °Con
heating (see figure 6B). When the relays C2, C2b are OFF then the analog output is zero.
In the DRIPING_TIME phase it produces the maximum voltage.
FAN 2. Higher voltage at the analog output.
When the relay of FAN 2 is OFF then the analog output is 0 Volt
FAN 2. In the heating.
Temperature / pressure range to which the analog output voltage corresponds.
FAN 2. In the cooling.
Temperature / pressure range to which the analog output voltage corresponds.
FAN2. Reverse analog signal at the output
FAN 2. Increasing the value reduces the oscillation of the 0-10 Volt signal
In case the machine is OFF. Time OFF of the valves after the minutes specified by the parameter
(See EOV parameter).
If EOV = 0 and the system is OFF, then the valves are OFF after the time specified by parameter VtO.
If EOV = 1 the valves remain in the state specified by the GSu parameter.
PREVENT. In case the pressure of circuit 1 becomes higher than the value of the parameter, the
ALARM PREVENT (Pr1) is activated and turns OFF the 2nd compressor or CAPACITIVE of the 1st
circuit. The same applies to the second circuit. (Pr2). Activated if PEn = 1 and with the parameters
SH1 = 1 and SH2 = 1 respectively for circuit 1 and 2. With itY = 3 (1 compressor / circuit) PREVENT
is deactivated. PrE Set Point works without differential.
In case the pressure of circuit 1 becomes higher than the value of the parameter, the high pressure
ALARM is activated by the transmitter (P1H), and turns OFF the compressors of the 1st circuit. The
same applies to the second circuit, called ALARM P2H. Activated if HEn = 1 and with the parameters
SH1 = 1 and SH2 = 1 respectively for circuit 1 and 2.
The SET POINT of HPA works without differential.
Value=0 Deactivate the parameter PrE. Value =1 activate the PrE parameter.
Value=0 Deactivate the parameter HPA. Value =1 activate the HPA parameter.
Reverse operation of CAPACITIVE, C1b and C2b relays. Value = 0 => ON the relay on the thermostat
ON. Value = 1 => OFF the relay on the thermostat ON.
ALARM Operation of Low Pressure when the compressor is OFF.
Value=0 => Blocks ALARM. Value = 1 => ALARM is free
ALARM TABLE Display flashes when the alarm messages are displayed
ALARM HIGH PRESSURE C1: Stops the operation of compressor C1. By adjusting parameter GAL = 0, alarm reset is manual.
ALARM LOW PRESSURE C1: Stops the operation of compressor C1. By adjusting parameter GAL = 0, alarm reset is manual.
ALARM COMPRESSOR C1: Stops the operation of compressor C1. Alarm is only automatically deactivated when the cause of the alarm disappears.
ALARM FLOW SWITCH: ALARM from the FLOW SWITCH. By adjusting parameter GAL = 0, alarm reset is manual.
ALARM HIGH PRESSURE C2: Stops the operation of compressor C2. By adjusting parameter GAL = 0, alarm reset is manual.
ALARM LOW PRESSURE C2: Stops the operation of compressor C2. By adjusting parameter GAL = 0, alarm reset is manual.
ALARM COMPRESSOR C2: Stops the operation of compressor C2. Alarm is only automatically deactivated when the cause of the alarm disappears.
ALARM SENSOR 1: ALARM analog input Νο 1. Safety thermostat. (Water input). Sensor malfunction. Alarm is only automatically deactivated when the cause
of the alarm disappears.
ALARM SENSOR 2: ALARM analog input Νο 2. Safety thermostat. (Water output). Circuit 1. Sensor malfunction. Alarm is only automatically deactivated
when the cause of the alarm disappears.
ALARM SENSOR 3: ALARM analog input Νο 3. Defrost Sensor malfunction. Alarm is only automatically deactivated when the cause of the alarm disappears.
ALARM SENSOR 4: ALARM analog input Νο 4. Safety thermostat. (Water output). Circuit 2. Sensor malfunction. Alarm is only automatically deactivated
when the cause of the alarm disappears.
ALARM SENSOR 5: ALARM analog input Νο 5. Defrost. Sensor malfunction. Alarm is only automatically deactivated when the cause of the alarm disappears.
ALARM FROST: ALARM from the Safety Thermostat Circuit 1. At compressor’s start-up, the thermostat is deactivated based on parameter timer tAF. By
adjusting GAL = 0, alarm reset is manual.
ALARM FROST: ALARM from the Safety Thermostat Circuit 2. At compressor’s start-up, the thermostat is deactivated based on parameter timer tAF. By
adjusting GAL = 0, alarm reset is manual.
ALARM Sensor No 3 - Sen3 (dFrost) –in Safety Thermostat mode. See parameter No 34 t3E
ALARM Sensor No 5 –Sen5 (dFrost) –in Safety Thermostat mode. See parameter No 34 t3E
HP1 transmitter failure. HIGH PRESSURE circuit 1
HP2 transmitter failure. HIGH PRESSURE circuit 2
ALARM HP1 from the transmitter 4-20 mA of the 1st circuit. OFF the compressors. RESET manual optional.
ALARM HP2 from the transmitter 4-20 mA of the 1st circuit. OFF the compressors. RESET manual optional.
ALARM PREVENT 4-20 mA high pressure sensor of the 1st circuit. When the circuit pressure becomes greater than the value of the PrE parameter the
ALARM PREVENT (Pr1) is activated and OFFs the second compressor or CAPACITIEVE of the 1st circuit
ALARM PREVENT 4-20 mA high pressure sensor of the 2nd circuit. When the circuit pressure becomes greater than the value of the PrE parameter the
ALARM PREVENT (Pr2) is activated and OFFs the second compressor or CAPACITIEVE of the 2nd circuit
The alarms are automatically deactivated when the cause of the alarm disappears.