KIOUR REF-DF-SM User manual

REFRIGERATOR CONTROLLER Model REF-DF-SM Version 4.2
DESCRIPTION
REF-DF-SM Version 4.2 is a compact controller for refrigerator’s control with defrost. Via one PTC sensor, it controls room’s temperatures with temperature range -19÷+99°C
(-2÷+210°F). It has defrost control and three relays (compressor, water level, ON-OFF). Also it has an OFF state, in which all relays are OFF and it has one input for level
control and one input for open door. The controller has a serial input and can connect to the KIOUR CAMIN modbus network for full monitoring and data logging of the device.
INDICATIONS AND BUTTON OPERATIONS
PROGRAMMING THE PARAMETERS
By pressing at the same time [ SET ] and [], [ ] we access the parameters menu.
The first parameter “SP” is displayed and with [ ], [ ] we scroll into the parameters with the order they appear to parameters table below .
By pressing [SET] the value of the parameter is displayed and with the [ ], [ ] we change the value.
By pressing [ ] we confirm the new value and the name of the parameter is displayed.
By pressing [SET] we cancel the new value and the name of the parameter is displayed.
By pressing [ ] we exit the parameters menu.
SWITCHING ON/OFF THE DEVICE
By pressing [ ] more than 3 sec. we switch ON or OFF the device.
TECHNICAL SPECIFICATIONS
Power supply: 230VAC 50/60Hz / Maximum power consumption: 3W
It is recommended to use a power supply safety switch: fuse 0,5A (not included)
Cabinet’s temperature sensor PTC 1Κ25°C / Ακρίβεια: 0.5°C
Serial Input
Relay compressor 250VAC 30A resistive load 2HP
Relay water level and relay ON/OFF 250VAC 10A
Operating temperature: -15÷+55°C / Storage temperature: -20÷+80°C
The device is mounted through panel hole 29x71mm and is restrained with two plastic side brackets / Connection with terminal blocks 18A
SERIAL INPUT
REF-DF-SM can connect to the key programmer or to the data logger Mini Logger or to the KIOUR CAMIN network or to any modbus network.
Key programmer: controller’s parameter values can be saved or retrieved from the programming key. Plug in the programming key to the controller and press at the same
time [SET]+[ ]. The device connects to the key and the message “Eo”is displayed. By pressing [ ] the device downloads the parameters from the key and the message
“ro”= read O.K. or “rF” = read Fail is displayed. By pressing [ ] the device uploads the parameters to the key and the message “Yo”= Write O.K. or “YF”= Write Fail is
displayed. In case of failure (rF or YF) reenter the key to the serial input and repeat the procedure from the beginning. The key can connect to all KIOUR devices. If you try
to read the parameters of a different device, message “rF”is displayed. At any time, we can perform the aforesaid operation. After 10sec the key is disconnected.
Data logger Mini Logger: the controller is connected to the data logger via cable and by programming the parameter Add = 1. Automatically, based on selected minutes,
the data logger writes to a microSD memory card the controller’s temperatures, status and alarms.
CAMIN network: the controller can connect to the CAMIN network via an interface NET-INS-485. CAMIN is an PC software application designed to collect information,
watch and fully control a net of KIOUR devices while sending SMS and email in case of an alarm. The maximum length of the net can be 1000 meters.
CONNECTIONS - DIMENSIONS
button
Operations
pressed once
pressed more than 3 sec
pressed together
SET POINT indication
confirm new value
-
-
indicates temperature sensors °C/°F
ON/OFF controller
enter parameter’s menu
-
-
df
cancel new value
start manual deFrost
Indications
relay ON
deFrost ON

PARAMETER TABLE
#
description
min
max
DF-SM
UOM
1
SΡ
SET POINT: temperature control of the cabinet
SL
SΗ
0
°C/°F
2
SL
minimum temperature limit of SP
-18
+80
-2
°C/°F
3
SH
maximum temperature limit of SP
0
99
8
°C/°F
4
di
differential relay function
1
50
3
°C/°F
5
Cr
minimum pause time of the compressor
0
4
0
min
6
CF
In case of sensor’s malfunction (F1), the compressor operates as follows:
0 = 40% ΟΝ compressor’s operation (3min ΟΝ, 4min OFF),
1 = compressor is ΟΝ continuously.
0
1
0
-
7
dF
frequency of defrosts per 24h, where:
0 = the deFrost is deactivated and
for ex. if put dF=6 →24h / 6 = 4h, which means every 4 hours the defrost starts
0
12
4
hours
8
dT
maximum duration of deFrost (automatic and manual)
1
90
18
min
9
dL
temperature limit of deFrost: above this temperature the automatic defrost stops.
The manual defrost does not stop according to “dL” temperature limit.
1
70
10
°C/°F
10
do
type of deFrost: compressor OFF (not programmable)
-
-
-
-
11
dr
dripping time. After the defrost, the compressor remains OFF according to dripping time.
0
10
0
min
12
td
during defrost the indication “dF” is displayed,
with 0 = the room’s temperature is displayed during defrost.
0
99
20
min
13
AJ
zero adjustment of the sensor
-9
+10
0
°C/°F
14
tS
refresh delay of temperature indication at display.
0
20
0
sec
15
FC
switch °C/°F (0=°C, 1=°F) ATTENTION: changes between °C/°F do not apply on SPo
0
1
0
°C/°F
16
Br
baud rate (9600mbps)
-
-
-
-
17
tr
time response of the device to the CAMIN network
5
100
20
msec
18
FF
operation mode of relay ON-OFF (1=ON continuously, 0=ΟΝ when compressor is ON)
0
1
1
-
19
Ad
address of the device in the network.
0
250
2
-
ALARM TABLE
1
F1
cabinet sensor malfunction
The alarms are automatically deactivated when the cause of the alarm disappears.
Made in Greece.
ATTENTION according to safety standards, the device must be properly positioned and protected from any contact with electrical parts. All parts that provide protection must
be fastened in such a way that they cannot be removed without the use of tools. ATTENTION: disconnect the power supply of the device before proceeding to any kind of
maintenance. ATTENTION: do not place the device near heat sources, equipment containing strong magnets, in areas affected by direct sunlight or rain. ATTENTION: prevent
electrostatic discharges at the side slots of the device and sharp objects from been inserted. ATTENTION: separate the signal's cables from the power supply's cables to
prevent electromagnetic disorders. Signal cables must never be in the same pipe with the power supply cables. Use the device only as described in this document, not to
use itself as a security device. The device must be disposed of in accordance with local standards for the collection of electrical and electronic equipment. Read
and keep these instructions. The device is under two year's guarantee of good operation. The guarantee is valid only if the manual instructions have been applied. The
control and service of the device must be done by an authorized technician. The guarantee covers only the replacement or the service of the device.
.
preserves the right to adjust its products without further notice.