KIOUR FA3F User manual

1
FREEZER CONTROLLER Model FA3F
ATTENTION Firmware V8
Read carefully these instructions before installing and using this device and keep them for future reference. Attention to installation and electrical wiring. Use this device
only as described in this document and never use itself as a security device. The device must be disposed of in accordance with local standards for the collection of
electrical and electronic equipment.
DESCRIPTION
FΑ3F is a temperature controller for freezer cabinets with defrost control; room and evaporator temperatures are controlled with NTC/PTC sensors; 3 indication digits with
resolution 0.5°C and 4 buttons; one digital input for controlling the cabinet’s door; 3 relays: compressor 30Α 250VAC, fan 10Α250VAC, defrost 10Α250VAC; defrosting may
be electric or hot gas, a buzzer in case of an alarm. Smart defrost is also available for power saving and better control of the defrost procedure. The device is mounted on a
panel hole and it is restrained with plastic side brackets. Through the serial input it can be connected to a network either through Cloud IoT on the CORTEX platform or through
a local computer with the CAMIN program for complete local recording and monitoring of the device.
INDICATIONS AND BUTTONS FUNCTION
For more indications regarding the alarms please see the alarm’s table at page 4.
1. Press to display the first parameter SPo.
2. Press to display its value. With
or change SPo value.
3. Press to save the new value. The device is working with the new adjustment.
1. Press to display SPo. Press and the parameter Cod is displayed.
2. Press to display its value and press
to enter the value 31. Press to store the value to parameter Cod.
3. Press again to exit the parameter menu, ‘YES’ is displayed on the screen. All appropriate factory settings are now stored in the device.
To activate or deactivate the device, press for 3 seconds .
Press for 3 seconds to start a manual defrost with duration based on the parameter dd2.
For more information regarding the defrost check the description of parameter dt6 (parameter Νο 20 - page 3).
PROGRAMMING A PARAMETER
ATTENTION: to gain full access to the parameter’s menu, the 2nd parameter Cod must be adjusted to 22 (see parameter table page 2).
1. Press to enter the parameter menu.
2. Choose the parameter you want to adjust by pressing or and press to display its value.
3. Press or to change its value and then press to store the new value.
4. Press to exit the parameter menu.
Model FA3F power supply: 230VAC 50/60Hz / Maximum power consumption: 3W. Model FA3FW switching power supply 100-264VAC 50/60Hz 5W
It is recommended using a power supply safety fuse: 0.5Α(not included)
Room and evaporator temperature sensors NTC 10K 1% 25°C ΙΡ68 and temperature range -37÷+110°C (-34÷+230°F) (or PTC 1Κ 25oC and temperature range
-50÷+110°C (-58÷+230°F) not included) / Accuracy: ±0.5°C
Alarm buzzer / Serial input with 5pin connector / Digital input door
Compressor relay 30Αres. 250VAC normally open contact / Fan and defrost relays 10A res. 250VAC normally open contact / Max current load 16Α
Connections: cable cross section 2.5 mm² for all relays / cable cross section from 0.25 to 1.0 mm² for the sensors and door switch
Connections with terminal blocks 18A using cable with cable cross section up to 2.5 mm² / It is recommended using a torque wrench with maximum torque 0.4Nm
Operating temperature: -15÷+55°C / Storage temperature: -20÷+80°C
Dimensions 37x79x81mm / The device is mounted on panel hole 29x71mm and restrained with plastic side brackets / Protection IP65 front
Firmware: V8
Display indications
compressor ON
fan ON
defrost ON
alarm ΟΝ
malfunction ON
Keyboard
enter/exit the parameter’s menu
display the parameter’s value
enter parameter’s value
manual defrost
up arrow
display evaporator temperature Τ2
down arrow
mute buzzer
ON/OFF device (check below)
ADJUSTING TEMPERATURE –SET POINT
INDUSTRIAL FACTORY SETTINGS
ON/OFF DEVICE
MANUAL DEFROST
TECHNICAL SPECIFICATIONS

2
FA3F connects via serial input to the following options:
Cloud IoT CORTEX platform: connection to the cloud and the CORTEX platform for monitoring - recording and managing the thermostat from your mobile, tablet or any
computer, notifications via email and Viber SMS
CAMIN program: local connection and monitoring - recording and management of the thermostat through the CAMIN program installed on a local computer.
Mini Logger recorder: the thermostat can be connected to the recorder and record based on selected minutes on a microSD memory card, its temperatures and the state
of the relays and alarms. It is connected via a cable to the serial input and we program the parameter Add = 1.
Memory key: the parameter values are stored in the memory key or recorded by it in the thermostat.
Smart defrost operates in parallel and independently from the conventional defrost. Both defrost modes can operate at the same time based on the respective settings. By
enabling smart defrost, it is recommended to adjust conventional defrost to operate in safe mode - for example once every 48 hours: parameter No 22, dFr = 48. If smart
defrost is not executed, then the conventional defrost will start after 48 hours from the last successful defrost. Each time a smart defrost is executed, the timer of the
conventional defrost is renewed.
Smart defrost is activated from parameter No 29, dSE = 1.
It is recommended during the start-up of the temperature controller, to execute a smart defrost cycle, parameter No 30, dSb = 1.
ATTENTION: according to safety standards, the device must be properly positioned and protected from any contact with electrical parts. The device must be fastened in such a way that it cannot
be removed without the use of tools. Disconnect the main safety switch of the installation before proceeding to any maintenance. Disconnect the power supply of the device before proceeding to
any maintenance. Do not place the device near heat sources, equipment containing strong magnets, in areas affected by direct sunlight or rain. Prevent electrostatic discharges and sharp objects
from been inserted to the device. Separate signal cables from power supply cables to prevent electromagnetic disorders. Signal cables must never be in the same pipe with the power supply cables.
ATTENTION: Read carefully the technical specifications and make sure that the working conditions are appropriate. According to safety standards, the device must be fastened in such a way that
it cannot be removed without the use of tools.
Dimensions are in mm. The device is mounted on panel hole with cut 29x71mm and restrained with plastic side brackets.
PARAMETER’S TABLE
Νο
description
min
max
FA3F
UOM
1
SΡo
SET POINT: room temperature setting
LSP
HSP
-21.0
°C/°F
2
Cod
Enter password Cod = 22 and press to access all parameters menu
0
255
0
-
ANALOG INPUTS - TEMPERATURE
3
diF
Differential of room temperature SPo (thermostat delay)
0.1
25.5
3.0
°C/°F
4
LSP
Lower setting limit of SPo
-50.0
+110
-21.0
°C/°F
5
HSP
Maximum setting limit of SPo
-50.0
+110
-10.0
°C/°F
6
dEC
Temperature indication as integer or decimal, where 0 = integer / 1 = decimal
0
1
1 =
decimal
-
7
SEn
Sensor type NTC/PTC
0 = PTC / 1 = NTC
0
1
1=NTC
-
8
SE1
Room sensor offset
-10.0
+10.0
0.0
°C/°F
9
SE2
Evaporator sensor offset
-10.0
+10.0
0.0
°C/°F
10
tdS
Delay in displaying the actual room temperature on the screen when the door opens
0
255
0
minutes
11
oS2
Evaporator’s sensor operation
0 = OFF sensor
1 = ON sensor
When the sensor is OFF, by pressing it is displayed “---”.
For more information regarding the defrost without the evaporator’s sensor, check parameters dE5, dt6 and
Fd3.
0
1
1= ON
-
12
C_F
Temperature measurement unit: toggling between °C/°F does not adjust the SPo automatically, it must be
changed by the user : 0 = °C / 1 = °F
0
1
0=°C
°C/°F
ALARMS
13
ΑLο
Low room temperature
-50.0
+110
-25.0
°C/°F
14
AHi
High room temperature
-50.0
+110
0.0
°C/°F
15
At2
Time delay in activating “AΗi”, “ΑLo” and the buzzer among them.
This setting does not apply to sensor failure and door alarm.
-1 = OFF buzzer
0 = immediately buzzer is ON
1 to 120 min = delay in buzzer activation
-01
120
20
minutes
16
ΑF1
Alarm setting
0 = automatic OFF, where the alarm stops once the cause of the alarm disappears.
0
1
0 = auto
-
SERIAL INPUT
SMART DEFROST
ELECTRICAL DIAGRAM - DIMENSIONS

3
1 = manual OFF, where the alarm indication remains even if the cause of the alarm disappears and it’s
cleared only by pressing .
In any case, by pressing the buzzer stops and turns on to state that the cause of the alarm still
exists. Muting the alarm buzzer by pressing once is valid until all alarms disappear.
DIGITAL INPUT –DOOR SWITCH
17
dLd
Door switch operation
0=OFF / 1=ΝC(normally close contact) / 2=NO (normally open contact)
If cabinet’s door is open during defrost (electrical or hot-gas) for more than timer tdo, then defrost relay turns
OFF and resumes once door is closed. Defrost duration based on timer dd2 stops counting as long as the
door is open and resumes once it closes.
0
1
1= NC
-
18
tdo
Time delay in deactivating the compressor once the door opens
1
250
120
sec
19
tAd
Time delay in activating door alarm “dor” once the door opens
If timer tAd is smaller than timer tdo, then the alarm “dor” is activated after timer tdo elapses.
0
250
0
minutes
DEFROST
20
dt6
Type of defrost
0 = electrical: compressor OFF, resistance ΟΝ
1 = hot gas: compressor ON, resistance ON
- - - - - - - - - - - -
Defrost with the evaporator’s temperature sensor ON
Automatic or manual defrost ends either with time adjusted from the parameter dd2 or with defrost end
temperature dE5, whatever comes first. Automatic or manual defrost does not start if the evaporator
temperature is greater than the defrost end temperature dE5.
Defrost with the evaporator’s temperature sensor OFF
Defrost end temperature is the room temperature.
Automatic defrost ends either with time adjusted from the parameter dd2, or with defrost end temperature
dE5, whatever comes first.
Manual defrost starts regardless of the room’s temperature and ends after time adjusted in parameter dd2
elapses.
0
1
0 =
electrical
-
21
dFr
Time between two successive defrost, where dFr = 0, defrost is deactivated.
0
100
6
hours
22
dd2
Defrost duration (manual and automatic)
1
120
30
minutes
23
dE5
Defrost end temperature –evaporator temperature - sensor EVAP T2
In case of deactivated evaporator sensor, defrost end temperature is the room temperature.
In case of evaporator’s sensor malfunction (LF2), there is no check of defrost end temperature and defrosting
is completed after timer adjusted in parameter dd2 elapses.
0.0
100
30.0
°C/°F
24
dP3
Dripping time, where the compressor is OFF after defrost.
The fan starts based on the parameters Fd3 and Fd4.
0
15
2
minutes
25
dY4
Display indication during defrost
-2 = SPo + diF value is displayed when room temperature is greater than SPo + diF
-1 = “dFr” is displayed when room temperature is greater than SPo + diF
0 = room temperature is displayed
1 to 40 minutes = “dFr” is displayed from 1 to 40 minutes from the initiation of defrost
-1
40
-1
minutes
26
dt5
Time delay in restraining indication “dFr” (parameter dY4=-1) or indication SET POINT + diF (parameter
dY4=-2) on screen after defrost ends
Indication “dFr” disappears once room’s temperature is smaller than SET POINT + diF.
0
150
0
minutes
SMART DEFROST –more details at page 2
27
dSE
Smart defrost function
0 = OFF
1 = ΟΝ
0
1
0
-
28
dSb
A defrost cycle is executed once the device starts-up
0 = OFF
1 = ΟΝ
0
1
1
-
29
dS2
Minimum time between two successive smart defrosts
1
255
60
minutes
30
dS1
Time constant: a steady increase in the constant, delays more the start of the smart defrost and increases
the ice on the evaporator
1
20
3
minutes
31
dSt
Temperature constant: a steady increase in the constant, delays more the start of the smart defrost and
increases the ice on the evaporator
0.5
3.0
1.0
°C/°F
COMPRESSOR
32
Co1
Compressor’s minimum time ON
0
15
0
minutes
33
CΡ2
Compressor’s minimum time OFF
0
15
3
minutes
34
CF3
Compressor’s operation in case of room’s sensor malfunction LF1
-1 = compressor OFF
0 = compressor ON while defrost starts based on timer dFr and ends based on timer dd2 or defrost end
temperature dE5, whichever comes first.
1 to 150 min = compressor time ON while defrost starts based on timer dFr and ends based on timer dd2 or
defrost end temperature dE5, whichever comes first.
-1
15
3
minutes
35
CF4
Compressor time OFF in case of room’s sensor malfunction
1
150
3
minutes
FAN
36
Ft2
Evaporator’s fan operation
-2 = continuously ON for evaporator’s temperature smaller than temperature Fo1
-1 = continuously ON
0 = parallel operation to the compressor
1÷15 min = parallel operation with the compressor and when the compressor is OFF, the fan stops after the
selected minutes
-2
15
-1= ΟΝ
continuo
usly
minutes
37
Fo1
Evaporator’s temperature controlling the fan operation during defrost and normal operation.
-50.0
+100
-2.0
°C/°F

4
If the evaporator’s sensor is OFF, the parameter does not operate.
For more information check the parameters Ft2, Fd3 and Fd4.
38
Fd3
Evaporator’s fan operation during defrost the with evaporator’s sensor ON (parameter οS2 = 1)
0 = OFF and starts with the compressor if the evaporator’s temperature is smaller than Fo1
1 = ON when the evaporator’s temperature is smaller than Fo1
2 = always ON in both types of defrost (electrical / hot gas)
If the evaporator’s sensor is OFF (parameter οS2 = 0), the fan is OFF during defrost and starts after timer
Fd4 elapses.
0
2
0
-
39
Fd4
Time delay in activating the fan after defrost ends
and only if the evaporator’s temperature is smaller than temperature Fo1 (check parameter Fd3).
0
255
0
minutes
NETWORK - GENERAL SETTINGS
40
tPE
Unique product number –no access
-
-
229
-
41
Add
Device address on network
0
255
1
-
42
trE
Response time of the device on network
5
100
40
msec
43
bAU
Baud rate: 0 = 2400 / 1 = 4800 / 2 = 9600 / 3 = 19200
Enter the new value, exit the parameter menu by pressing and toggle the power supply of the device
0
3
3
-
44
Pro
Cabinet’s program (factory settings) is displayed –no access
-
-
31
-
45
SrU
Room service: after the end of the selected time, ‘SrU’ is displayed and informs that the room needs service.
The thermostat continues to operate normally and its functions are not suspended.
-1 = disabled function
0 to 150 weeks = remaining time to activate the ‘SrU’room service notification. The countdown starts once
a new value is stored. Whenever we enter the parameter, the remaining time until the activation of ‘SrU’
notification is displayed. To deactivate the notification, insert SrU = -1.
-1
150
-1
weeks
46
UEr
Firmware version –no access
-
-
8.X.X
-
ALARM’S TABLE
1
LF1
Room sensor malfunction
2
LF2
Evaporator sensor malfunction
3
ΑLo
Low room temperature
4
ΑHi
High room temperature
5
dοr
Open door alarm (when the cabinet’s door opens, the fan stops)
6
SrU
room service notification: timer has elapsed and the cabinet needs a service (see parameter 45, SrU)
7
EEr
Error in memory RAM: re-enter the SPo (see ADJUSTING TEMPERATURE –SET POINT page 1)
The alarms are automatically deactivated once the cause of the alarm disappears.
Made in Greece.
The device is under two year’s guarantee. The guarantee is valid only if the manual instructions have been applied. The control and service of the device must be done by an authorized technician.
The guarantee covers only the replacement or the service of the device. KIOUR PC implements a Quality Management System according to EN ISO 9001:2015 Standard with registration number
01013192. KIOUR preserves the right to adjust its products without further notice.
392 Mesogeion Avenue Agia Paraskevi 153 41 Τ: 210 6533730 F: 210 6546331 [email protected] www.kiour.com
V8.0.9
Table of contents
Other KIOUR Controllers manuals