1 = manual OFF, where the alarm indication remains even if the cause of the alarm disappears and it’s
cleared only by pressing .
In any case, by pressing the buzzer stops and turns on to state that the cause of the alarm still
exists. Muting the alarm buzzer by pressing once is valid until all alarms disappear.
DIGITAL INPUT –DOOR SWITCH
Door switch operation
0=OFF / 1=ΝC(normally close contact) / 2=NO (normally open contact)
If cabinet’s door is open during defrost (electrical or hot-gas) for more than timer tdo, then defrost relay turns
OFF and resumes once door is closed. Defrost duration based on timer dd2 stops counting as long as the
door is open and resumes once it closes.
Time delay in deactivating the compressor once the door opens
Time delay in activating door alarm “dor” once the door opens
If timer tAd is smaller than timer tdo, then the alarm “dor” is activated after timer tdo elapses.
Type of defrost
0 = electrical: compressor OFF, resistance ΟΝ
1 = hot gas: compressor ON, resistance ON
- - - - - - - - - - - -
Defrost with the evaporator’s temperature sensor ON
Automatic or manual defrost ends either with time adjusted from the parameter dd2 or with defrost end
temperature dE5, whatever comes first. Automatic or manual defrost does not start if the evaporator
temperature is greater than the defrost end temperature dE5.
Defrost with the evaporator’s temperature sensor OFF
Defrost end temperature is the room temperature.
Automatic defrost ends either with time adjusted from the parameter dd2, or with defrost end temperature
dE5, whatever comes first.
Manual defrost starts regardless of the room’s temperature and ends after time adjusted in parameter dd2
elapses.
Time between two successive defrost, where dFr = 0, defrost is deactivated.
Defrost duration (manual and automatic)
Defrost end temperature –evaporator temperature - sensor EVAP T2
In case of deactivated evaporator sensor, defrost end temperature is the room temperature.
In case of evaporator’s sensor malfunction (LF2), there is no check of defrost end temperature and defrosting
is completed after timer adjusted in parameter dd2 elapses.
Dripping time, where the compressor is OFF after defrost.
The fan starts based on the parameters Fd3 and Fd4.
Display indication during defrost
-2 = SPo + diF value is displayed when room temperature is greater than SPo + diF
-1 = “dFr” is displayed when room temperature is greater than SPo + diF
0 = room temperature is displayed
1 to 40 minutes = “dFr” is displayed from 1 to 40 minutes from the initiation of defrost
Time delay in restraining indication “dFr” (parameter dY4=-1) or indication SET POINT + diF (parameter
dY4=-2) on screen after defrost ends
Indication “dFr” disappears once room’s temperature is smaller than SET POINT + diF.
SMART DEFROST –more details at page 2
Smart defrost function
0 = OFF
1 = ΟΝ
A defrost cycle is executed once the device starts-up
0 = OFF
1 = ΟΝ
Minimum time between two successive smart defrosts
Time constant: a steady increase in the constant, delays more the start of the smart defrost and increases
the ice on the evaporator
Temperature constant: a steady increase in the constant, delays more the start of the smart defrost and
increases the ice on the evaporator
Compressor’s minimum time ON
Compressor’s minimum time OFF
Compressor’s operation in case of room’s sensor malfunction LF1
-1 = compressor OFF
0 = compressor ON while defrost starts based on timer dFr and ends based on timer dd2 or defrost end
temperature dE5, whichever comes first.
1 to 150 min = compressor time ON while defrost starts based on timer dFr and ends based on timer dd2 or
defrost end temperature dE5, whichever comes first.
Compressor time OFF in case of room’s sensor malfunction
Evaporator’s fan operation
-2 = continuously ON for evaporator’s temperature smaller than temperature Fo1
-1 = continuously ON
0 = parallel operation to the compressor
1÷15 min = parallel operation with the compressor and when the compressor is OFF, the fan stops after the
selected minutes
Evaporator’s temperature controlling the fan operation during defrost and normal operation.