Wiring
ConnectingthismodeltoaKMCcontrollerrequires
aspecialcablewith(onthesensorend)anRJ-45
connectorand(onthecontrollerend)anRJ-11
connectorwithanadditionalthreewires(asrelevant
tothemodel)forcontrollerinputs.Purchasing
preassembledcablesfromKMCismorecost-
eectiveandreliablethancreatingcustomcablesin
theeld.Useoneofthefollowingcables:
• KMD-5693=25feet
• KMD-5694=50feet
• KMD-5695=75feet
Thethreeadditionalwireconnectionstothecontrol-
lerare:
• Orangeisthethermistor (temperature voltage)
signaltothecontroller’sappropriateinput
• Orange/whiteisthesetpointsignaltothecon-
troller’sappropriateinput
• Greenisthesupply voltageof7.5/12VDCfrom
anoutputofthecontrollerpress
KMD–5693 = 25 feet; KMD–5694 = 50 feet; KMD–5695 = 75 feet
1 8
Orange Wire = Thermistor Input to Controller
Orange/White Wire = Setpoint Signal Input to Controller
(for STE-6014/6016/6017/6018 only; clip or tape when not used)
12 inches
52
RJ-11 and
Wire Leads
to Controller
RJ-45
to STE
Sensor
Green Wire = Aux. Supply Voltage to STE-6015/6018
(10 VDC) or STE-6016 (7.5/12 VDC) (clip or tape when not used)
RJ-11 RJ-45 Color
(Lead) 8 Orange
7 N.C.
(Lead) 6 Green
3 5 Blue
4 4 Blue/White
5 3 Green/White
2 N.C.
(Lead) 1 Orange/White
(Cables crossed, 20 AWG)
Common (“Ground”)
0–5 VDC Temperature Signal and (during a Button Press)
SENSOR-ON (0 VDC on ) or SENSOR-OFF (> 5 VDC on )
D
B
C
A0–5 VDC Setpoint Signal
7.5 VDC (Setback/Setup) or
12 VDC (Normal) Supply (from Controller)
{
{
{
{
© 2012 KMC Controls, Inc. 866-019-05C
More Information
Forgeneralproductinfor-
mation,seetheSTE-6000
Series Room Temperature
Sensors/Transmiers Data
SheetontheKMCControls
website.
Formountingconsider-
ations,networkconnection,
controllerconguration,
programming,troubleshoot-
ing,andotherinformation,
seetheSTE-6012/6016
Application Guide.
Maintenance
Carefulinstallationwillalsoensurelong-term
reliabilityandperformance.Removedustasneces-
saryfromholesintopandboom.Cleanwithaso,
dampclothandmildsoap.
KMC Controls, Inc.
19476IndustrialDrive
NewParis,IN46553
574.831.5250
Connectwiresasshownfortherelevantmodel.
Important Notices
Thematerialinthisdocumentisforinformation
purposesonly.The contents and the product it
describes are subject to change without notice.
KMCControls,Inc.makesnorepresentationsor
warrantieswithrespecttothisdocument.Innoevent
shallKMCControls,Inc.beliableforanydamages,
directorincidental,arisingoutoforrelatedtothe
useofthisdocument.
Up (Toward Ceiling at Installation)
NOTE: IntheSTE-6012/6016,pressingthe
Down buonmomentarilysends0 VDC
tothecontrollerforaSENSOR-ONsignal;
pressingtheUp buonsendsgreater
than 5 VDCforaSENSOR-OFFsignal.
Wheninnormal/overridemode,pressing
theDownorUpbuonraisesorlowersthe
setpointvoltage.Wheninsetback/setup
mode,pressingeitherbuonalsoselects
overridemode.