
PowerPost® EVSE Dual and Quad Post System Installation Manual Page 4
ElectricalRequirementsConfigurationA
Four separate electrical supply runs are required, one for each PowerPost EVSE unit.
Circuit Protection: See PowerPost EVSE installation manual.
Note: Requirements may vary per PowerPost EVSE model.
Conduit/Cable Penetration: Electrical supply cables enter from the bottom of the unit.
Supply wire size: 12 AWG min (75°C copper wire).
Free cable length: 52 inches minimum length beyond end of conduit.
ElectricalRequirementsConfigurationsBandC
Two separate electrical supply runs are required, one for each PowerPost EVSE unit.
Circuit Protection: See PowerPost EVSE installation manual.
Note: Requirements may vary per PowerPost EVSE model.
Conduit/Cable Penetration: Electrical supply cables enter from the bottom of the unit.
Supply wire size: 12 AWG min (75°C copper wire).
Free cable length: 52 inches minimum length beyond end of conduit.
Figure 1: Configuration A
Figure 2: Configuration B
Figure 3: Configuration C