KOOLAIR FSD Series User manual

series
Fire and smoke dampers
UL Approval
FSD-FLD
www.koolair.com

Fire and smoke dampers UL Approval
FSD-B-U / FSD-A-U and FLD-S-U / FLD-S-UD
CONTENTS
Description FSD-B-U / FSD-A-U 2
Construction details FSD-B-U / FSD-A-U 3
Dimensions FSD-B-U / FSD-A-U 4
Operation FSD-B-U / FSD-A-U 5
Description FLD-S-U / FLD-S-UD 6
Construction details FLD-S-U / FLD-S-UD 7
Dimensions FLD-S-U / FLD-S-UD 7
Operation FLD-S-U / FLD-S-UD 8
Periodic inspection FLD-S-U / FLD-S-UD 9
Technical data 10
Series FSD-FLD 1

FSD-A-U
FSD-A-U
FSD-B-U / FSD-A-U Fire and smoke dampers.
UL Approval
Description
The FSD-B-U and FSD-A-U models are 3V type multi-blade
re and smoke dampers approved according to UL standards
(UL555 and UL555S).
Fire dampers close automatically to prevent re and smoke from
spreading to adjacent re compartments through HVAC
ventilation ductwork.
The dampers are approved to withstand re conditions for 90
minutes according to UL555 standard. The FSD-B-U model
achieves Class 1 leakage level according to UL555S at a
temperature of 177 °C. The FSD-A-U model achieves Class 3
leakage level according to UL555S at a temperature of 177 °C.
The FSD-B-U model re damper incorporates
elastomeric airtight seals along the edges of the closing blades.
The casings or frames of the dampers are manufactured with
reinforced corners. Where height H <425 mm, low prole lines
are used at the top and bottom of the frame. The blades are
reinforced with 3 lengthways structural sections called “Vee’s” to
provide them with greater rigidity and resistance.
Silicone sealant is applied to the joint between the frame and its
enclosure to prevent any air or smoke leakage.
An inspection hatch is required in the ductwork adjacent to the
damper to facilitate periodic inspection and maintenance.
The FSD-B-U / FSD-A-U models are installed vertically with the
blades in a horizontal position, regardless of the direction of the
horizontal air ow.
Series FSD-FLD
2

FSD-B-U / FSD-A-U Fire and smoke dampers.
UL Approval
Construction details:
Maximum levels of operation:
Design and manufacture details FSD-B-U / FSD-A-U dampers
Damper frame or casing material Galvanised steel
Damper frame or casing thickness 1.6 mm
Damper frame or casing prole type Omega prole – 123 mm thick
Closing blade material Galvanised steel
Closing blade thickness 1.6 mm
Closing blade type Type triple V
Sealing. Airtightness Integrated gasket in the casing or frame
Damper shaft bearings Bronze casing pressed into the casing or frame
Damper shaft material Sheet steel
Airtight seal in the interior of the damper Stainless steel - metal exible under compression
Airtight seals on blades Silicone (FSD-B-U model)
Thermal actuator + opening and
closing servomotor
Thermal actuator (thermoelectric fusible link) that operates at
temperatures above 74 ºC.
Electric servomotor 24V, with auxiliary changer (230 V option)
Damper exterior enclosure Minimum 432 mm, thickness 1 mm. Galvanised steel.
Levels of operation:
Description FSD-A-U/FSD-B-U models
UL 555S leak classication Class 1 (FSD-B-U) and Class 3 (FSD-A-U)
UL 555 re resistance classication 90 minutes (1.5 h)
Maximum velocity 10 m/s
Maximum pressure 1000 Pa
Series FSD-FLD 3

H / L 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800
150
300
450
600
750
900
1050
1200
H / L 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800
150
300
450
600
750
900
1050
1200
FSD-B-U / FSD-A-U Fire and smoke dampers.
UL Approval
Dimensions:
FSD-A-U
FSD-B-U
MIN. 432 mm
MIN. 432 mm
L
L
H
H
Dimensions
Simple selection (L x H) Multiple selection (L x H)
152 x 203 mm (minimum dimension) 1828 x 1371 mm (maximum dimension)
914 x 1220 mm (maximum dimension)
Series FSD-FLD
4

FSD-B-U / FSD-A-U Fire and smoke dampers.
UL Approval
Operation:
The FSD-B-U and FSD-A-U models are designed to be fail-safe, allowing the dampers to automatically
return to the desired position in the event of a re and smoke.
The damper operates (closes) if the power supply of 24 V (optionally 230 V) to the servomotor is
interrupted, whether as a result of a system failure, a command from the control system or by the
thermoelectric fusible link when the temperature exceeds 74º C. The damper is open while power is
supplied.
The damper automatically resets (opens) when 24 V (optionally 230 V) is supplied to the servomotor. If the damper is
closed due to high temperatures, i.e. by the thermoelectric fusible link, it is manually reset by a button installed on the
damper.
Remote damper status indication (limit switch) is also available.
Installation:
The dampers are designed for the lowest possible pressure drop. The technical department deals with each order
individually and supplies the client with a blade width for the desired height and ensures that the dampers have the
greatest free area when open and, therefore, the lowest pressure drop. Blade width may therefore differ and can protrude
outside the damper frame on one or more sides, up to a maximum of 69 mm.
MÁX. 69 mm
123
FLOW RATE
EJE INTERCONEXIÓN LAMAS
MURO
CORTAFUEGO
DAMPER
ENCLOSURE
ACTUATOR
BEARING
SUPPORT
SHAFT
FRAME
BLADE
FIXING ANGLES EXPANSION AREA (MINIMUM
6 MM, MAXIMUM CONSULT
MOUNTING INSTRUCTIONS)
RESETTABLE
THERMAL
ACTUATOR +
OPENING AND
CLOSING
ACTUATOR
Series FSD-FLD 5

Fire dampers with fusible link, FLD-S-U /
FLD-S-UD. Approval UL
Description
The re dampers are approved to withstand re conditions for 90
minutes (1.5 hours) in accordance with UL555. They are 3V type
multi-blade operated by the melting of a fusible link calibrated to
74º C.
Fire dampers close automatically to prevent re from
spreading to adjacent re compartments through HVAC
ventilation ductwork.
The FLD-S-U model is re rated under static conditions.
The FLD-S-U model is re rated under dynamic conditions. It is
designed for system speeds of up to 10 m/s and pressure of up
to 1000 Pa.
The damper frame is constructed with reinforced corners.
Frame sizes under 425 mm high use low prole thin line frames.
The blades are reinforced with 3 “Vee’s” structurally designed
lengthways.
The FLD-S-U / FLD-S-UD models are installed vertically, with
the blades in a horizontal position, regardless of the direction of
the horizontal air ow.
FLD-S-U / FLD-S-UD
Fire damper with fusible link
FLD-S-U / FLD-S-UD
Fire damper with fusible link
Series FSD-FLD
6

H / L 150 200 300 400 500 600 700 800 900
150
300
450
600
750
900
Fire dampers with fusible link, FLD-S-U /
FLD-S-UD. Approval UL
Construction details:
Dimensions:
Construction details
Damper frame or casing material Galvanised steel
Damper frame or casing thickness 1.6 mm
Damper frame or casing prole type Omega prole – 123 mm thick
Closing blade material Galvanised steel
Closing blade thickness 1.6 mm
Closing blade type Type triple V
Sealing. Airtightness Integrated gasket in the casing or frame
Damper shaft bearings Bronze casing pressed into the casing or frame
Damper shaft material Sheet steel
Actuation temperature Fuse calibrated at 74 ºC
Damper exterior cover Minimum length 432 mm, galvanized steel, 1 mm thickr
Dimensions
Simple selection (L x H) Larger sizes require to be provided
as individual dampers for on-site
assembly.
300 x 150 mm (minimum dimension)
914 x 914 mm (maximum dimension)
FLD-S-U
FLOW
L
H
Series FSD-FLD 7

Operation:
Complete with thermal fusible link set at 74ºC.
They are designed to be fail-safe, allowing the dampers to close automatically when the temperature in the duct reaches
the fuse design temperature..
Fire dampers with fusible link, FLD-S-U /
FLD-S-UD. Approval UL
Installation:
The dampers are designed for the lowest possible pressure drop. The technical department deals with each order
individually and supplies the client with a blade width for the desired height and ensures that the dampers have the
greatest free area when open and, therefore, the lowest pressure drop.
Blade width may therefore differ and can protrude outside the damper frame on one or more sides,
up to a maximum of 69 mm.
MÁX. 69 mm
123
FLOW
RATE
BLADE
INTERCONNECTI
ON AXIS
FIREWALL
DAMPER
ENCLOSURE
FUSIBLE
LINK
BEARING
SUPPORT
EJE
FRAME
BLADE
FIXING ANGLES
EXPANSION AREA
(MINIMUM 6 MM, MAXIMUM
CONSULT MOUNTING
INSTRUCTIONS)
BEARING
EXTENSION
Series FSD-FLD
8

Fire dampers with fusible link, FLD-S-U /
FLD-S-UD. Approval UL
Periodic inspection, testing and maintenance
The basic inspection, testing and maintenance procedures are described below.
Inspection:
Regular inspection, testing and maintenance are essential to ensure that the re and smoke dampers in an installation
operate as intended. Inspection and maintenance should include periodic testing of all equipment, including dampers,
fans, operating devices, controls, etc. Standards such as NFPA 92A, NFPA 80, NFPA105 and local codes must be
consulted for guidance with respect to the intervals of damper inspection, testing, and maintenance. The intervals of
inspection, testing and maintenance vary widely depending on the system’s length of operation, the condition of the air
and other factors.
Maintenance:
• Check the electric servomotor and tighten the coupling if necessary.
• Check the damper blades and other parts as necessary.
• Lubricate the latch, bearings and other moving parts with a silicone lubricant. Petroleum-based products should not be
used as they may accumulate dust.
• Activate the damper using the electric servomotor.
• Check the blades to make sure they close and reopen completely.
• Check the damper to make sure it is perpendicular and the blade channel is not obstructed.
Test:
• Use a moderate heat source and heat the thermal disk inside the damper.
• Once the required temperature has been reached, the power supply to the servomotor will be switched off and the
motor spring will close the damper blades.
• The damper must be tested under normal air ow conditions.
Series FSD-FLD 9

150
400
500
1000
750
4500
1500
2000
3000
150
400
500
1000
750
4500
1500
2000
3000
0,01
0,10
1,00
110
A
L
(m
2
)
V
eff
(m/s)
Q (m
3
/h)
1,040
0,200
30
25
40
45
50
35
0,540
55
60
1
10
100
1000
110
∆P (Pa)
V
eff
(m/s)
k
p
L
wA
[dB(A)]
2
3
4
5
6
7
8
9
0,54
1,80
Fire damper FSD-B-U / FSD-A-U FLD-S-U /
FLD-S-UD. Technical data
Selection chart FSD-B-U / FSD-A-U FLD-S-U / FLD-S-UD
Selection example:
For the given duct dimensions and technical data, we select a 1200 x 200 mm FSD-B-U damper. We use the table on the
previous page to nd the following data:
AL = 0,24 m2 k
p = 1,8 kdB(A)= -2
The technical data to achieve a ow rate of 3500 m3/h is required.
Referring to the diagram above using this ow rate and the area o 0,24 m2, we obtain a Veff of 4 m/s. With this veocity
and taking into account the value of kp, we obtain:
Differential pressure: 30 Pa
Sound pressure level: 45 dB(A)
Applying LwA- dB(A) = 45+ (-2) = 43 dB(A)
Series FSD-FLD
10

L \ H 200 300 400 500 600 700 800 900 914
150
0,030 0,045 0,060 0,075 0,090 0,105 0,120 0,135 0,137 AL(m2)
1,80 1,80 1,80 1,80 1,80 1,80 1,80 1,80 1,80 kp
-6 -5 -5 -4 -4 -4 -3 -3 -3 kdB(A)
200
0,040 0,060 0,080 0,100 0,120 0,140 0,160 0,180 0,183 AL(m2)
1,80 1,80 1,80 1,80 1,80 1,80 1,80 1,80 1,80 kp
-6 -5 -4 -4 -3 -3 -3 -2 -2 kdB(A)
300
0,060 0,090 0,120 0,150 0,180 0,210 0,240 0,270 0,274 AL(m2)
1,80 1,80 1,80 1,80 1,80 1,80 1,80 1,07 1,06 kp
-5 -4 -3 -3 -2 -2 -2 -2 -2 kdB(A)
400
0,080 0,120 0,160 0,200 0,240 0,280 0,320 0,360 0,366 AL(m2)
1,80 1,80 1,80 1,80 1,80 1,04 0,94 0,84 0,82 kp
-4 -3 -3 -2 -2 -1 -1 -1 -1 kdB(A)
500
0,100 0,150 0,200 0,250 0,300 0,350 0,400 0,450 0,457 AL(m2)
1,80 1,80 1,80 1,12 0,99 0,86 0,74 0,64 0,62 kp
-4 -3 -2 -2 -1 -1 -1 0 0 kdB(A)
600
0,120 0,180 0,240 0,300 0,360 0,420 0,480 0,540 0,548 AL(m2)
1,80 1,80 1,80 0,99 0,84 0,70 0,58 0,47 0,46 kp
-3 -2 -2 -1 -1 -1 0 0 0 kdB(A)
700
0,140 0,210 0,280 0,350 0,420 0,490 0,560 0,630 0,640 AL(m2)
1,80 1,80 1,04 0,86 0,70 0,56 0,44 0,33 0,32 kp
-3 -2 -1 -1 -1 0 0 0 0 kdB(A)
800
0,160 0,240 0,320 0,400 0,480 0,560 0,640 0,720 0,731 AL(m2)
1,80 1,80 0,94 0,74 0,58 0,44 0,32 0,23 0,22 kp
-3 -2 -1 -1 0 0 0 1 1 kdB(A)
900
0,180 0,270 0,360 0,450 0,540 0,630 0,720 0,810 0,823 AL(m2)
1,80 1,07 0,84 0,64 0,47 0,33 0,23 0,20 0,20 kp
-2 -2 -1 0 0 0 1 1 1 kdB(A)
914
0,183 0,274 0,366 0,457 0,548 0,640 0,731 0,823 0,835 AL(m2)
1,80 1,06 0,82 0,62 0,46 0,32 0,22 0,20 0,20 kp
-2 -2 -1 0 0 0 1 1 1 kdB(A)
Table FSD-A-U / FSD-B-U/ FLD-S-U / FLD-S-UD
Key:
L width in mm
H height in mm
AL free area in m2
veff effective velocity in relation to the free surface in m/s
ΔP pressure loss in Pa
LwA sound pressure level in dB(A)
kp pressure loss correction factor
kdB(A) sound-level correction factor
Fire damper FSD-B-U / FSD-A-U FLD-S-U /
FLD-S-UD. Technical data
Series FSD-FLD 11

H \ L 200 300 400 500 600 700 800 900 914
1000
0,20 0,30 0,40 0,50 0,60 0,70 0,80 0,90 0,91 AL(m2)
1,80 0,99 0,74 0,54 0,37 0,25 0,20 0,20 0,20 kp
-2 -1 -1 0 0 1 1 1 1 kdB(A)
1100
0,22 0,33 0,44 0,55 0,66 0,77 0,88 0,99 1,01 AL(m2)
1,80 0,91 0,66 0,45 0,29 0,20 0,20 0,20 0,20 kp
-2 -1 0 0 0 1 1 1 1 kdB(A)
1200
0,24 0,36 0,48 0,60 0,72 0,84 0,96 1,08 1,10 AL(m2)
1,80 0,84 0,58 0,37 0,23 0,20 0,20 0,20 0,20 kp
-2 -1 0 0 1 1 1 1 2 kdB(A)
1300
0,26 0,39 0,52 0,65 0,78 0,91 1,04 1,17 1,19 AL(m2)
1,09 0,77 0,50 0,31 0,20 0,20 0,20 0,20 0,20 kp
-2 -1 -1 0 0 1 1 1 1 kdB(A)
1371
0,274 0,411 0,548 0,686 0,823 0,960 1,097 1,234 1,253 AL(m2)
1,06 0,72 0,46 0,26 0,20 0,20 0,20 0,20 0,20 kp
-2 -1 -1 0 0 1 1 1 1 kdB(A)
Table FSD-A-U / FSD-B-U
Fire dampers FSD-B-U / FSD-A-U FLD-S-U /
FLD-S-UD. Technical data
Series FSD-FLD
12

L \ H 1000 1100 1200 1300 1400 1500 1600 1700 1800 1828
150
0,150 0,165 0,180 0,195 0,210 0,225 0,240 0,255 0,270 0,274 AL(m2)
1,80 1,80 1,80 1,80 1,80 1,80 1,80 1,11 1,07 1,06 kp
-3 -3 -2 -2 -2 -2 -2 -2 -2 -2 kdB(A)
200
0,200 0,220 0,240 0,260 0,280 0,300 0,320 0,340 0,360 0,366 AL(m2)
1,80 1,80 1,80 1,09 1,04 0,99 0,94 0,88 0,84 0,82 kp
-2 -2 -2 -2 -1 -1 -1 -1 -1 -1 kdB(A)
300
0,300 0,330 0,360 0,390 0,420 0,450 0,480 0,510 0,540 0,548 AL(m2)
0,99 0,91 0,84 0,77 0,70 0,64 0,58 0,52 0,47 0,46 kp
-1 -1 -1 -1 -1 0 0 0 0 0 kdB(A)
400
0,400 0,440 0,480 0,520 0,560 0,600 0,640 0,680 0,720 0,731 AL(m2)
0,74 0,66 0,58 0,50 0,44 0,37 0,32 0,27 0,23 0,22 kp
-1000000011kdB(A)
500
0,500 0,550 0,600 0,650 0,700 0,750 0,800 0,850 0,900 0,914 AL(m2)
0,54 0,45 0,37 0,31 0,25 0,20 0,20 0,20 0,20 0,20 kp
0000111111kdB(A)
600
0,600 0,660 0,720 0,780 0,840 0,900 0,960 1,020 1,080 1,097 AL(m2)
0,37 0,29 0,23 0,20 0,20 0,20 0,20 0,20 0,20 0,20 kp
0011111112kdB(A)
700
0,700 0,770 0,840 0,910 0,980 1,050 1,120 1,190 1,260 1,280 AL(m2)
0,25 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 kp
1111112222kdB(A)
800
0,800 0,880 0,960 1,040 1,120 1,200 1,280 1,360 1,440 1,462 AL(m2)
0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 kp
1111222222kdB(A)
900
0,900 0,990 1,080 1,170 1,260 1,350 1,440 1,530 1,620 1,645 AL(m2)
0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 kp
1112222222kdB(A)
914
0,914 1,005 1,097 1,188 1,280 1,371 1,462 1,554 1,645 1,671 AL(m2)
0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 kp
1122222222kdB(A)
1000
1,00 1,10 1,20 1,30 1,40 1,50 1,60 1,70 1,80 1,83 AL(m2)
0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 kp
1222222233kdB(A)
1100
1,10 1,21 1,32 1,43 1,54 1,65 1,76 1,87 1,98 2,01 AL(m2)
0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 kp
2222223333kdB(A)
1200
1,20 1,32 1,44 1,56 1,68 1,80 1,92 2,04 2,16 2,19 AL(m2)
0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 kp
2222233333kdB(A)
1300
1,30 1,43 1,56 1,69 1,82 1,95 2,08 2,21 2,34 2,38 AL(m2)
0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 kp
1222222233kdB(A)
1371
1,371 1,508 1,645 1,782 1,919 2,057 2,194 2,331 2,468 2,506 AL(m2)
0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 kp
1222222233kdB(A)
Table FLD-S-U / FLD-S-UD
Fire dampers FSD-B-U / FSD-A-U FLD-S-U /
FLD-S-UD. Technical data
Series FSD-FLD 13

THIS CATALOG IS INTELLECTUAL PROPERTY.
The partial or total reproduction of its contents is forbidden without the express and authoritative authorisation of KOOLAIR, S.A.
CEN-FSD-FLD-1117-00
Series FSD-FLD
14

KOOLAIR, S.A.
Calle Urano, 26
Poligono industrial nº 2 – La Fuensanta
28936 Móstoles - Madrid - (España)
Tel: +34 91 645 00 33
Fax: +34 91 645 69 62
e-mail: info@koolair.com
www.koolair.com
This manual suits for next models
5
Table of contents
Other KOOLAIR Fire And Smoke Damper manuals
Popular Fire And Smoke Damper manuals by other brands

Schako
Schako BSK-RPR-EU Installation, mounting and operating instructions