
 
 
 
Page 4 of 10 
 
Operation and Maintenance Manual WKP-P
 ate: 19.07.19 
1. evice installation instructions 
 
Before installing t e fire damper c eck it for damage caused during transport or storage. 
C eck if t e damper is able to open and close (full open and close position). In t e case 
of  WKP dampers open t e damper wit   an  actuator  key.  Full opening and  closing  s all  be 
smoot  (not irregular). Do not pull t e damper baffle in order to open/close t e damper. Doing 
so can cause permanent damage to t e device, w ic  is not covered by t e warranty. 
Before installation, verify t e gap between t e bottom blade and t e inside part of t e body 
under t e blade and between upper blade and t e inside of t e body over t e blade. T e gap 
size can not be less t an 4 mm. 4 mm feeler gauge is supplied wit  t e order. 
Before installation secure t e damper wit  film or ot er covering material to protect it 
against dirt and damage to t e damper elements. 
To  maintain  EIS120,  EIS90  declared  resistance,  insulation  and  smoke  leakage,  t e 
dampers s ould be mounted in walls, w ic  were tested and rated as EI120 or EI90. 
It is acceptable to use WKP-P dampers in walls wit  ot er fire resistance rating, but in 
t is case it s ould be kept in mind t at EI fire resistance rating of t e w ole WKP-P damper 
installation is equal to t e fire resistance rating of t e lowest rated element of t e system. 
T e WKP-P fire dampers may be installed in vertical space dividers wit  bot   orizontal 
and vertical axis of rotation of blades. In vertical mounting t e recommended position of t e 
actuator is above t e damper.  
 
 
1.1 Installation Technology – Rigid Wall Structure 
 
1. Make a  ole in t e wall – 246 mm greater t an t e dimension B and 120 greater t an 
dimension H, i.e. B+246 and H+120. 
2. Insert t e closed damper into t e mounting  ole and support it or suspend in suc  a way 
t at  t e  axis  of  t e  damper  baffle  coincides  wit   t e  wall  axis,  and  to  maintain  t e 
coaxiality of t e damper and t e mounting  ole. 
3. Once t e damper is set as described above, fill in t e slot between t e damper and t e 
wall fully wit  mortar, cement mortar, lime-cement mortar or concrete. 
4. W en t e mortar is dry (after about 48  ours), remove t e supports or suspension used 
for mounting t e damper, c eck if t e damper operates properly and leave it in t e open 
position.