GB-6
PFA 70 in conjunction with PFU 780..L
Parameter 43 = 3
4 Press the Reset/Information button for 1 s.
▷The display indicates step
01
.
▷The PFUs start the burner pre-purge procedure.
WARNING
The pre-purge duration is not included in the program.
Pre-purge until the combustion chamber has been ad-
equately ventilated.
5 Press the Reset/Information button for 1 s.
▷The display indicates step
02
.
▷The PFUs start the pilot burners.
6 Press the Reset/Information button for 1 s.
▷The display indicates step
03
.
▷
The PFUs start the main burners, the pilot burners
remain switched on.
7 Press the Reset/Information button for 1 s.
▷The display indicates step
00
.
▷The PFUs switch off all the burners.
▷By pressing the Reset/Information button repeatedly,
the PFUs are activated to switch between pre-purge
(the display indicates step
01
), pilot burner start (the
display indicates step
02
), main burner start (the
display indicates step
03
) or burner off (the display
indicates step
00
).
High/Low operating mode
PFA 700 in conjunction with PFU 760..L
Parameter 43 = 4
4 Press the Reset/Information button for 1 s.
▷The display indicates step
01
.
▷The PFUs start the burner pre-purge procedure.
WARNING
The pre-purge duration is not included in the program.
Pre-purge until the combustion chamber has been ad-
equately ventilated.
5 Press the Reset/Information button for 1 s.
▷The display indicates step
03
.
▷The PFUs start the burners.
6 Press the Reset/Information button for 1 s.
▷The display indicates step
04
.
▷The PFUs 760..L activate the external air valves, the
burners switch to high-fire rate.
7 Press the Reset/Information button for 1 s.
▷The display indicates step
03
.
▷
The PFUs 760..L deactivate the external air valves,
the burners switch to low-fire rate.
▷
Each time the Reset/Information button is pressed, the
air valves are opened (the burners switch to high-fire
rate, the display indicates
04
) or closed (the burn-
ers switch to low-fire rate, the display indicates
03
).
PFA 70 in conjunction with PFU 780..L
Parameter 43 = 4
4 Press the Reset/Information button for 1 s.
▷The display indicates step
01
.
▷The PFUs start the burner pre-purge procedure.
WARNING
The pre-purge duration is not included in the program.
Pre-purge until the combustion chamber has been ad-
equately ventilated.
5 Press the Reset/Information button for 1 s.
▷The display indicates step
02
.
▷The PFUs start the pilot burners.
6 Press the Reset/Information button for 1 s.
▷The display indicates step
03
.
▷
The PFUs start the main burners, the pilot burners
remain switched on.
7 Press the Reset/Information button for 1 s.
▷The display indicates step
04
.
▷The PFUs 780..L activate the external air valves, the
main burners switch to high-fire rate.
8 Press the Reset/Information button for 1 s.
▷The display indicates step
03
.
▷
The PFUs 780..L deactivate the external air valves,
the main burners switch to low-fire rate.
▷
Each time the Reset/Information button is pressed, the
air valves are opened (the burners switch to high-fire
rate, the display indicates
04
) or closed (the burn-
ers switch to low-fire rate, the display indicates
03
).
Faults
DANGER
Electric shocks can be fatal! Before working on possible
live components, ensure the unit is disconnected from
the power supply.
Fault-clearance must only be undertaken by authorized,
trained personnel.
▷
Faults may be cleared only using the measures de-
scribed below.
▷
If the PFA does not respond even though all faults
have been remedied: remove the unit and return it to
the manufacturer for inspection.
? Faults
! Cause
• Remedy
? The 7-segment display does not light up.
! Mains voltage is not applied.
• Check the wiring, apply mains voltage (see type label).