KSolare KSY-30KW User manual

5G PRO INVERTER
KSY-30KW/33KW/35KW/40KW/50KW60KW
3-Phase Grid-tied Solar Inverter

1. SYMBOLS ON THE LABEL
2. SAFETY AND WARNINGS
3. 3UNPACKING
3. 1 Scope of Delivery .......................................... .................................................... 5
3. 2 Product Overview ................................................................................... ......... 5
4. 4INSTALLING
4.1 Installation Requirement ............................................................................. 6
4. 2 Mo unting Location ........................................................................................ 7
4. 3 Mounting ................................................................................... ....................... 7
4. 4 Installing the secondary PE cable ........................................................ 8
5. 5COMMISSIONING
5.1 Safety Instructions ........................................................................................... 10
5.2 AC Wire Assembly and Connection ....................................................... 10
5.2.1 AC Commissioning ........................................................................................ 10
5. 3 DC Wire Assembly and Connection ...................................................... 13
DC Commissioning :
insert it into the corresponding terminal
Positive cold-pressed
terminal
Negative cold-press
terminal
Diameter
Step 2 : Use a suitable crimping pliers to crimp the
corresponding wire
Step 3: Insert the crimped terminal into the corresponding
plastic shell
Step 6: Connect the wired client and machine
Step 4: Check whether the polarity of the connecting cables of the PV string is
correct, and ensure that the open circuit voltage does not exceed the upper
limit of the inverter input
Step 5: Pull out the dustproof cap on the DC terminal of the machine
Note: Please keep the dustproof cap of the unused terminal
5. 4 Residual Current Protection ................................................................ 13
6. 6 COMMUNICATION
6.1 System monitoring via Datalogger -RS485/Wi-Fi/GPRS (Optional) .... 14
1
Table Of Content
3
3
5
14
6

7. 7START UP AND OPERATION
7.1 Safety Check Before Start Up ................................................................ 15
7.2 Inverter LED Indicators .......................................................................... 16
7.3
Fault Finding
8. SYSTEM MAINTENANCE
2
15
15
15
........................................

1. SYMBOLS ON THE LABEL
DANGER, WARNING AND
CAUTION
RECYCLABLE AND REUSABLE
HIGH VOLTAGE
AVOID CONTACT
AVOID DAMP AND MOISTURE
HIGH TEMPERATURE
AVOID CONTACT
SHIPMENT STACK LIMIT: 8
CE MARKS
DO NOT DISPOSE WITH
HOUSEHOLD WASTE
PROCEED OPERATIONS
AFTER 5 MINUTES
DISCHARGE
BREAKABLE ITEM
PLACE UPWARDS
USER MANUAL IN PACK
2. SAFETY AND WARNINGS
1. All persons who are responsible for mounting, installation, commissioning,
maintenance, tests, and service of KSOLARE inverter products must be suitably
trained and quali ed for corresponding operations. They MUST be experienced and
have knowledge of operation safety and professional methods. All installation
personnel must have knowledge of all applicable safety information, standards,
directives, and regulations.
2. The product must ONLY be connected and operated with PV arrays of protection
class II, in accordance with IEC 61730 , application class A. The PV modules must also
be compatible with this product. Power resources other than compatible PV arrays
MUST not be connected and operate with the product.
3

3. When designing or constructing a PV system, all components MUST remain in their
permitted operating ranges, and their installation requirements MUST always be
ful lled.
4. Under exposure to sunlight, the PV array may generate dangerous output in DC
voltage. C ontacts with the DC wires, conductors and live components in the inverter
may result in lethal shocks.
5. High voltages in inverter could cause lethal electrical shocks. Before proceeding any
work, including maintenance and/or service, on the inverter, fully disconnect it from
all DC input, AC grid and other voltage sources. There MUST be a 5 -minute waiting
time after the full disconnection.
6. The DC input voltage of the PV array MUST never exceed the maximum input
voltage of the inverter.
7. DO NOT touch parts of the inverter during operation as heat will be induced and
these parts will exceed 60 0.
4

Diameter
3. 3UNPACKING
3.1 Scope of Delivery
Please inspect and check for completeness in the scope of delivery. Con rm with
purchase order.
1. DC Connector
KSY -30K/33K/36KW 6 pairs
KSY -40K/50K/60KW 8 pairs
2. Wi-Fi/GPRS optional
Inverter × 1 Wall hanging board × 1 AC junction box x1
DC connector M
RS485/METER/DRED
connector x2
Wall Mounting Kit x2 Wi-Fi/GPRS 21
3.2 Product Overview
1. LED& LCD or LED
2. DC Switch
3. PV Terminal (s)
4. COM1: Wi- Fi/GPRS /RS485 port
5. COM2: Smart Meter port
6. COM3: RS485
7. AC Terminal
8. Secondary PE Terminal
5
Optional

4. 4INSTALLING
4.1 Installation Requirement
1. Please install the inverter(s) in places that can avoid inadvertent contact.
2. Installation method, location and surface must be tting for the inverter’s weight and
dimensions.
3. Please install the inverter in an accessible location for operation, future maintenance
and service.
4. The inverter performance peaks at ambient temperature lower than 450.
5. When installing in residential or domestic environment, it is recommended to install
and mount the inverter on a solid, concrete wall surface. Mounting the inverter on
composite or plaster boards or walls with similar materials would induce noise during
its operation and is therefore not recommended.
6. DO NOT cover the inverter NOR place any objects on top of the inverter.
7. To ensure su ient room for heat dissipation and maintenance, the clearing space
between inverter(s) and other surroundings is indicated below for reference:
8. Avoid direct exposure to sunlight and rain and snow layup.
No sun No Rain No Snow
6

4.2 Mounting Location
1. DO NOT mount the inverter near any ammab le materials.
2. DO NOT mount the inverter near any explosive materials.
3. DO NOT mount the inverter on tilting surface over 15° backwards. Please mount the
inverter on a vertical wall surface.
4. DO NOT mount the inverter on any surfaces tilting forward or to either sides.
5. DO NOT mount the i nverter on a horizontal surface.
6. For easy installation and operation, please mount the inverter on a height that the
display could match eye level.
7. The bottom side where all commissioning terminals are equipped MUST always point
downwards.
4.3 Mounting
Wall - mounting the inverter
1. Use the mounting bracket as a template and drill holes of 10mm diameter and
70mm depth.
2. Fix the mounting bracket with the screws and expansion bolts packed in mounting
accessories.
3. Hold onto the handles on the inverter and tilt it slightly forward. Hang up the invert
er
and attach it to the mounting bracket. Check both sides of the heat sink to ensure its
stably attached.
4. Observe from above, ensure the inverter has been securely attached to the bracket.
5. Use M5 screws (T25 screwdriver, torque 2.5 Nm) to attach the heat sink s to the
mounting bracket.
It is recommended to attach the anti - theft lock to the inverter. Lock diameter φ4- 5.5m m
recommended .
7

Racket - mounting the inverter:
In the same way as wall- mounting the inverter, only replace the expansion bolts and screws with
M10*45 Stainless steel full thread screw assembly (The assembly incl. bolt, nut, t washer, spring
washer is not included in the package)
4. 4 Installing the secondary PE cable
1. Insert the grounding conductor into the suitable OT terminal lug and crimp the
contact.
2. Align the terminal lug with the grounding conductor and the ground washer on the
screw. The teeth of the ground washer must be facing the housing.
3. Tighten it rmly into the housing ( M6 PE terminal, screwdriver type: Pan head ,
torque: 4.5Nm).
Step 1 Step 2 Step 3
Step 5Step 4
8

Information on grounding components:
Note: PE cable requirements
Object Description
1 Housing
2 M6 terminal lug with protective conductor
3 M6×12 pan head screw
Diameter Cross- section
16<S ≤35mm216mm2
Only suitable when the material of PE
cable is aligned with other AC phase
cables. In case the materials are
erent, please ensure the resistance is
equivalent to the ure mentioned in
the table.
S>35mm 2S/2
Please install the secondary PE before connect any other cables.
Secondary PE cannot replace the connection of PE terminal in AC wiring . Both PE and
secondary PE should be properly installed.
KSOLARE will not take account for any consequences caused by violating the
requirement.
Danger
9

5. 5COMMISSIONING
5.1 Safety Instructions
1. Measure the frequency and voltage of grid connection and make sure they follow the
inverter’s grid connection speci ations.
2. An external circuit - breaker on the AC side (or a fuse) at 1.25*AC rated current is
strongly recommended.
3. Reliability of all earth connections must be tested and valid .
4. Before commissioning, disconnect the inverter and the circuit - breaker or fuse, and
prevent accidental reconnection.
5.2 AC Wire Assembly and Connection
5.2.1 AC Commissioning
:
:
(
(
荐用
: 表要求
、 、
Copper wire recommended 35~50mm²
70mm² is recommended for aluminum wire
PE line: see the requirements in the table below
KSY-30KW/KW-33KW/35KW:22 30mm
KSY-40KW/KSY-50KW-60KW:30 50mm
(KSY-30KW/KSY-33KW/KSY35KW):
(KSY-40KW/KSY-50KW/KSY60KW):
(KSY-40KW/KSY-50KW/KSY60KW):
10
Five core flexible copper recommended,& strip the
cable in Such way :

AC phase cable
cross- section
PE cable cross -
section Note
16<S ≤35mm216mm2
Insert the grounding conductor into the OT terminal lug in the accessory pack and
crimp the contact , ensure the insulation protection has been done properly.
S>35mm 2S/2
Only suitable when the material of PE
cable is aligned with other AC phase
cables. In case the materials are erent,
please ensure the resistance is equivalent
to the re mentioned in the table.
Danger due to high voltage electricity
Danger
11
Cable cross

5. 2.2 AC Switch Types
Please install an individual 2 - stage miniature circuit breaker according to the following
speci cations:
Model
Maximum output
current(A)
AC Breaker Rated current
(A)
KSY- 30KW 50A 63
KSY- 33K W 55 A 63
KSY- 35K W 60 A 80
KSY-40K W 66.7 A 80
KSY- 50K W 8
88A 108A
0 A 100
KSY-60KW
Danger
12

5. 3 DC Wire Assembly and Connection
1. PV modules of the connected strings must be of: the same time, identical alignment
and tilting angle.
2. Before commissioning and connecting the PV arrays, the DC switch MUST be open.
3. Parallel strings must have the same number of modules.
4. It is mandatory to use the DC connectors within package for the connection of PV
arrays.
5. The polarity of the PV arrays MUST be compatible to the DC connectors of the
inverter.
6. The DC input voltage AND DC input current of the PV array MUST never exceed the
maximum input allowance of the inverter.
DC Commissioning :
5.4 Residual Current Protection
This product is equipped with residual current protection device internally, in accordance
with IEC 60364 - 7- 714. An external residual current protection device is not needed.
If the local regulation demands otherwise, it is reco mmended to install a 30mA Type B
residual current protection device. 。
Step 1: Peel off the insulation layer of the cable &
insert it into the corresponding terminal
Step 2: Use a suitable crimping pliers to crimp
the corresponding wire
Step 5: Pull out the dustproof cap on the DC
terminal of the machine Note: Please keep the
dustproof cap of the unused terminal
Step 4: Check whether the polarity of the connecting
cables of the PV string is correct, and ensure that the
open circuit voltage does not exceed the upper limit
of the inverter input
Step 3: Insert the crimped terminal into the
corresponding plastic shell
Step 6: Connect the wired client and machine
Positive cold-pressed
terminal
Negative cold-pressed
terminal
Diameter
13

6. 6 COMMUNICATION
6.1 System monitoring via Datalogger - RS485/ Wi- Fi /GPRS
(Optional)
Wi - Fi /GPR S Datalogger Installation
Unpack the Datalogger from package.
Unscrew the cap in COM1 port and plug the Datalogger in and tighten.
For user guidance and con ration of Datalogger, please refer to the corresponding KSOLARE
Wi - Fi Stick Guide manual, which is available in printed form inside Documents pack,or an
online manual on KSOLARE
website at
www.ksolare.com
RS485 Installation
location description
The guide groove
Insert the wire end into the European terminal (DIN46228-4)
and crimp it
Step 1
Step 2
Step 3
Insert the crimped conductors into the corresponding terminals, and
tighten the screws with the screwdriver in the attached packaging bag.
Insert the wired connector into the AC output port and tighten. When
operating, first align the groove on the head of the terminal block with
the rib on the inner ring of the output port.
Step 4
14

7. 7START UP AND OPERATION
7.1 Safety Check Before Start Up
Please check before switching on any v oltage resources connected to the inverter and
closing inverter’s DC switch:
1. Grid Voltage: Check the grid voltage at point of connection at the inverter complies
with permitted range of the inverter.
2. Mounting Bracket: Check if the mounting bracket is properly and securely installed.
3. Mounting of the inverter: Check if the inverter is properly mounted and attached to
the mounting bracket.
4. DC Connectors: Check if the DC connectors are installed correctly on terminals.
5. AC C onnectors and Wire Assembly: Check if wires are assembled correctly on the AC
side and if the AC connector is properly and securely installed. Check if the AC
connector is rmly plugged into AC terminal.
6. Cables: Check if all cables are reliably connected. Check if the connections are
eective, while the insulations are undamaged.
7. Groundings: Check all groundings using multimeter and if all exposed metal parts of
the inverter are properly grounded.
8. DC Voltage: Check if the largest open - circuit voltage of PV arrays complies with the
permitted range.
9. DC Polarity: Check if the wires from DC voltage resource are connected to terminals
with correct polarity.
10. Grounding Resistance: Check if the grounding resistance of PV strings >1MOhm using
a multimeter.
After all installation and checks, close the AC circuit - breaker, then the DC switch. The
inverter will start to operate when DC input voltage and grid conditions meet the
requirements of inverter startup.
15

7.2 Inverter LED Indicators
When the inverter operates, LED symbols on display have the following meanings:
16

17
7.3 Fault Finding
Classifications of Fault Information
Fault
Location
Fault Type
Error Message
DC Side Fault
Failures caused by PV side wiring
F5
- PV voltage too high
F6
- Surface insulation resistance
error
F7
- GFCI exceeds the permissible
range
AC Side Fault
Various faults caused by abnormal
power grid or AC side wiring
F0
- 10min average voltage over
the protection range
F9 - No gird
F10
- The grid voltage is out of
range
F11
- The grid frequency exceeds
the range
F19
- The voltage of N-PE is too
high
Inverter Fault
Fault code caused by inverter itself
F1 - MCU fault
F2 - Current sensor fault
F3 - GFCI sensor fault
F4 - Relay fault
F12 - Dc component out of range
F13 - EEPROM fault
F14
- Master and slave DSP
communicationfailure
Others
It may be caused by external
installation environment, PV side
and inverter itself. Further
Diagnoses needed.
F8
- Temperature is out of range
F15 - BUS voltage is too high
F16 - BUS voltage is too low
F17
- DRM S9 fault
F18
- DRM S0 fault

Log complaint on hps://bit.ly/3eRZba9
Contact 8530111222 / 7888009282 / 7030955507 /01
Fault code
Fault
Solution
Fault 9
No Grid
Fault 10
The grid voltage is out
of range
Fault 19
The voltage of N-PE is
too high
Waiting
-
Fault code
Fault
Solution
Fault 5
PV voltage too high
Fault 6
Surface insulation
resistance
error
Display Off
-
Faults & Troubleshooting
Grid (AC) Side faults
( Panel ) DC Side faults
1. Check Ac (grid) Voltage In Connector
2. Phase to Neutral voltages 200V-250V
3. Phase to Phase Voltage 400V - 450V
1. Check Grid Voltages
2. Phase to Neutral voltages 200V-250V
3. Phase to Phase Voltage 400V - 450V
2. Grid voltages in inverter
3. Check Version & make Online system
1. Check AC side Neutral to Ground Voltage less
than 15V
1. Check DC Side Voltages
2. For single phase voltage under 500V
3. For Three phase voltage under 1000V
1. Check String polarity
2. Check DC Voltage
voltage 80V - 500V
voltage 100V - 550V
voltage 200V - 1100V

This manual suits for next models
5
Table of contents
Other KSolare Inverter manuals