INTRODUCTION:
The Model 091-134-025 AUTO INTERLOCK IIA is an automatic power transfer relay specifically
designed to isolate various battery charging systems such that ONLYone (1) charging system is
actively charging a battery at any time. Referring to Figure 1 the Model 091-134-025 AUTO
INTERLOCKIIAcanaccomodatethree(3)batterychargingsysteminputsandoutputsasfollows:
INPUTS
1. Conventional 115VAC High Powered or multi-step external battery charger (>10A) via
ShorePower 115VAC Input to High Power Charger.
2. 115VAC Generator equipped with DC output Alternator connected to common battery bank.
3. Low Power DC battery charger (<3A), i.e. Solar Panel, Float Voltage Charger.
OUTPUTS
1.115VAC to conventional high power charger.
2. Isolated DC battery charge circuit for Low Power Charger.
THEORYOFOPERATION:
The Model 091-134-025 AUTO INTERLOCK IIA senses the Generator 115VAC output and the
status of a 115VAC connected “ShorePower” and configures the battery charging isolation as
follows.
! With neither ShorePower connected nor the Generator running the AUTO INTERLOCK IIA
connects the Low Power Charger (LPC) DC circuit to the battery.
!With ShorePower connected the AUTO INTERLOCK IIA transfers the facility supplied power
to the AC input of a High Power Charger (HPC) and opens the DC circuit of the LPC to the
battery.
! With the Generator running the AUTO INTERLOCK IIA senses the generator 115VAC output
and disables the 115VAC ShorePower input (whether present or not) to the HPC and opens
the DC circuit of the LPC to the battery.
The AUTO INTERLOCK IIAprovides three (3) indicatorsfor“StateIndication”inaccordancewith
thefollowingTable
Battery Charging Circuit State and Indication Table
Generator Shorepower Battery Charge Circuit State Indication
OFF OFF LPC ALLOFF
OFF ON HPC Main&Output=ON,Auxiliary=OFF
ON OFF Generator Auxiliary=ON,Main&Output=OFF
ON ON Generator Main&Auxiliary=ON,Output=OFF