1. USE
This PIR (passive infrared) presence detector provides automatic control
of lighting loads with optional manual control.
It is a high sensitivity PIR detector suitable for high bay applications,
such as warehouses and factories, and where high detection sensitivity
is needed.
The unit detects movement using a PIR sensor and turns the load on.
When an area is no longer occupied, the load will switch off after an
adjustable timeout period.
The output channel includes a mains voltage switching relay for ON/OFF
control of lighting.
The unit can turn lights on when a room is occupied and off when
the room is empty. Optional settings allow lights to be turned off in
response to ambient daylight.
These units come complete with accessories that allow changes to the
detection area and surface mounting
All functionality is fully programmable using an infrared configurator.
2. TECHNICAL CHARACTERISTICS
PIR sensor
Detects movement within the unit’s detection range, allowing load
control in response to changes in occupancy.
IR receiver
Receives control and programming commands from the infrared
configurator.
Light level sensor
Measures the overall Lux level in the detection area.
LED status
The LED flashes red to indicate the following:
Walk test LED active When movement is detected
Valid setting received
2. TECHNICAL CHARACTERISTICS CONTINUED
Dimensions See dimensions section
Weight 0.2 kg (complete unit)
Power supply 230 VAC +/-10%
Frequency 50 Hz
Maximum load
6 A resistive and incandescent lighting
6 A fluorescent lighting
6 A compact fluorescent lighting
6 A low-energy lighting
6 A low-voltage lighting (switches
transformer primary)
6 A fans and ventilation equipment
Power consumption ON 822 mW, OFF 847 mW
Terminal capacity 2.5 mm2
Operating temperature -30°C to +35°C
Operating humidity 5 to 95% non-condensing
Material Flame-retardant ABS and PC/ABS
Type Class 2
Protection class IP40 without gasket and IP65 with
gasket