1
Communicating Thermostat
Installation Instructions
No: IS-0685– rev. 2 5/23
CC-STAT
Country of Origin: Made in China
FEATURES AND OPERATION OVERVIEW
OVERVIEW
The CC-STAT Vantage Communicating Thermostat provides the comfort and energy
efciency your customers expect with easy installation and full InFusion integration.
The CC-STAT may function as a stand-alone HVAC thermostat; however, the system
user will experience enhanced and simplied control when the CC-STAT is integrated
with the InFusion system. LCD interfaces and touchscreens provide the interface and
the CC-STAT, installed near the HVAC system, provides the control.
When combined with the Thermostat Interface Station, this multi-function thermostat
is compatible with most residential HVAC systems, including single stage, heat pump,
multi-stage and control of humidier and dehumidier systems.
• One thermostat for all applications - works with single-
stage, heat pump, multi-stage and control of humidier and
dehumidier systems
• On-board relative humidity sensor congurable to control
humidier and dehumidier
• Communicates with InFusion controller, Vantage
touchscreens, and mobile apps for remote operation and
feedback
• Direct connection of outdoor or indoor sensors
• Allows for temporary override of Vantage System without
altering initial programming
• Automatic set points controlled through the Vantage System
• Backward compatible
Description Specication
Dimensions 4.9375” H x 6” W x 1.3125” D (125.4mm H x 98.4mm W x 49.2mm D)
Model CC-STAT
Power Draw Maximum 86.4 mA rms – This value is with 24 VAC input voltage and backlight ON
Power Draw Typical 21.6 mA rms – This value is with 24 VAC input voltage and backlight OFF
Power Input 18-30 Vac (24VAC nominal), 50/60Hz
Maximum Load Per Terminal 1 Amp
Maximum Load All Terminals 2.5 Amp
DC Power 3.0 Volts DC (2 “AA” Alkaline batteries included
Compatible Systems Standard gas, oil, electric, single stage/heat pump/multi-stage
Terminal Designations Rc, R, W, Y, G, C, S1, S2, O, B, L, W2, Y2, T1, T2, C, B, O, Y, Y2, G, RC, R, W2, WL, S2,
S1, T1, T2, A-, B-, A+, B+, RSA, RSB
Rated Output Current 0.001 A to 1 A continuous per output with up to 5 A surge (half cycle)
Control Range 45º to 99ºF (7º to 32ºC)
SPECIFICATIONS