
Page 3
CB(X)26UH SERIES
CB(X)26UH Series Air Handlers
All CB(X)26UH air handlers are designed for indoor
installation only. As shipped, the units are ready for
installation in either upflow or horizontal left−hand air
discharge applications. All units may be installed with
optional field−installed electric heat and a matched remote
outdoor unit.
SCBX26UH air handlers may be installed with a
matched HFC−410A remote outdoor unit. These units
are completely assembled, including a factory
installed check/expansion valve.
SCB26UH air handlers may be installed with a matched
HCFC−22 remote outdoor unit. These units are
completely assembled, including a factory installed
check/expansion valve.
Table 1. Orifice (RFC) Part Number (Sizes − in.)
Model
HCFC−22 NOTE 1HFC−410A NOTE 2
13HPD / HP13 XC13 / XP13
018 100484−08 (0.057)
Refer to orifice table in
outdoor unit installation
manual
024 100484−11 (0.061)
030 100484−21 (0.072)
036 100484−23 (0.074)
042 100484−30 (0.082)
037, 048 not supported
060 100484−44 (0.098)
Note 1 − Orifice ships
with Air Handler.
Note 2 − Orifice ships with
outdoor units.
SCB26UH−R (RFC) units may be installed with a
matched remote 13HPD/ HP13 outdoor unit. These
units are equipped with an HCFC−22 refrigerant flow
control device (see orifice table 1). Also, these units
can be used with HCFC−22 (13ACD/AC13), or
HFC−410A refrigerant provided the RFC shipped with
the outdoor unit is installed in place of the RFC device
shipped with the CB26UH−R unit.
Requirements
WARNING
Excessive Weight Hazard − Use two or more people
when moving and installing the unit. Failure to do so can
result in back or other type of injury.
These instructions are intended as a general guide and do
not supersede local or national codes in any way. Consult
authorities having jurisdiction before installation.
Compliance with all local, state, or national codes
pertaining to this type of equipment should be determined
prior to installation. Read this instruction manual, as well
as the instructions supplied in separate equipment, before
starting the installation.
In addition to conforming to manufacturer’s installation
instructions and local municipal building codes, installation
of Lennox air handler units (with or without optional electric
heat), MUST conform with National Fire Protection
Association (NFPA) standards: Standard for Installation
of Air Conditioning and Ventilation Systems" (NFPA No.
90A) and Standard for Installation of Residence Type
Warm Air Heating and Air Conditioning Systems" (NFPA
No. 90B).
IMPORTANT
The CB(X)26UH units are designed to match, and must
be used with, outdoor units as rated. The indoor sections
are manufactured with a check/expansion valve (TXV)
or refrigerant flow control (RFC) device to provide opti-
mum refrigerant control and system performance with a
variety of different capacities of outdoor units.
TXV unitsIn some cases, the rating of the outdoor unit
may require that the coil assembly installed TXV be
changed to obtain rated performance.
All models are designed for indoor installation only. The
installation of the air handler, field wiring, duct system, etc.
must conform to the requirements of the National Electrical
Code, ANSI/NFPA No. 70 (latest edition) in the United
States, and any state laws, and local ordinances (including
plumbing or wastewater codes). Local authorities having
jurisdiction should be consulted before installation is
made. Such applicable regulations or requirements take
precedence over the general instructions in this manual.
Install the conditioned air plenum, ducts and air filters (not
provided) in accordance with NFPA 90B Standard for the
Installation of Warm Air Heating and Air−Conditioning
Systems (latest edition).
The air handler is shipped from the factory completely
assembled. The unit is provided with flanges for the
connection of the duct system.
Do not remove the cabinet knockouts until it has been
determined which knockouts will need to be removed for
the installation.
Select the final air discharge position which best suits the
site conditions. Consider required clearances, space,
routing requirements for refrigerant line, condensate
disposal, filters, duct system, wiring, and accessibility for
service. Refer to the air handler rating plate on the air
handler for specific information.
WARNING
Danger of explosion. Keep flammable ma-
terials and vapors, such as gasoline, away
from air handler. Place air handler so that
heating elements are at least 18 inches (46
cm) above the floor for a garage installa-
tion. Failure to follow these instructions
can result in death, explosion, or fire.
NOTES
During cooling operation, excessive sweating may occur if
the air handler is installed in a very humid space.
If installed in an unconditioned space, sealant should be
applied around the electrical wires, refrigerant tubing, and
condensate lines where they enter the cabinet.
Electrical wires should be sealed on the inside where they
exit the conduit opening. Sealant is required to prevent air
leakage into, and condensate from forming inside of, the
air handler, the control box, and on the electrical controls.