15
ALARM CODES
E05
E06
E07
E11
E12
E13
E21
E22
Anti-freeze alarm
Indicates the outlet water temperature is
lower than +3ºC.
Outlet water probe alarm
Outlet water probe open or without
connecting.
Alarm of the refrigerant piping probe:
Refrigerant piping probe open or
without connecting
Second compressor and fan thermal
protection alarm:
- Compressor and fan thermal protection
open
- Faulty power supply
VIS. RE
MAN
AUTO
AUTO
AUTO
AUTO
MAN
MAN
MAN
High presostat alarm, circuit 2
This alarm may indicate the following
problems:
- High presostat protection
- Compressor electrical protection opens
- Indoor fan electrical protection opens
- Fuses of the fan burn out
Low presostat alarm, circuit 2
This alarm may indicate the following
problems:
- Low amount of refrigerant
- Low water flow in cooling cycle
- Blocked coil in heating cycle
- Fuses of the fan burn out
After two automatic resets in one hour, it
comes to be a manual reset
Press the ON/OFF button, until the alarm
disappear, if the alarm shows up again
check:
•Coil clean and no blocked.
• Water flow on the cooling cycle
•Check fuses of the fan
When this alarm shows up repeteally,
and the alarm keeps on, make a electrical
reset and check:
•Coil clean and no blocked.
• Water flow on the cooling cycle
•Check fuses of the fan
•Check refrigerant charge.
These protection are automatic reset, if
alarm shows up again check:
•Connection of outlet water temperature
probe (ST2), (see electrical diagram),
Check continuity and change the faulty
component.
Press the ON/OFF button until the
alarm disappeared, if alarm shows up
again
•Check the water filter
•Check water flow
•Check that the water pump is
connected to power supply of the unit.
High pressure/High temperature alarm.
Is activated when refrigerant piping probe
(St3) detect a temperature higher than 65ºC
and the high pressostat has not activated.
This alarm may activated the following
problems:
-Faulty high pressostat.
Press the ON/OFF" button , until the
alarm disappeared, if alarm shows up
again, check:
• Working of high pressostat.
• Coil clean and no blocked.
• Water flow on the cooling cycle
• Check fuses of the fan
• Check low pressostat working.
• Coil clean and no blocked.
• Check water flow on the cooling cycle
• Check fuses of the fan
• Check refrigerant charge.
DESCRIPTION EFFECT ACTION
These protection are automatic reset, if
alarm shows up again check:
•Connection of refrigerant piping probe
(ST2), (see electrical diagram), Check
continuity and change the faulty
component.
Low pressure/Low temperature alarm.
Is activated when refrigerant piping probe
(St3) detect a temperature lower than -30ºC
and the low pressostat has not activated.
This alarm may activated the following
problems:
-Faulty low pressostat.
Press the ON/OFF button until the alarm
disappeared, of alarm shows up again
check continuity and change the faulty
component
•Check refrigerant charge
•Check the refrigerant circuit is not
blocked
•Check connections and fusses
•Check power supply
Unit
stops
Unit
stops
Unit
stops
Unit
stops
Unit
stops
Compressor
2 stops
Compressor
2 stops
Compressor
2 stops