CAUTIONS:
• ESD Sensitive Device: Use safe handling procedures when installing.
• For indoor applications ONLY.
Before Installation
• Requires installation into a 2 7/8 in. to 3 1/4 in. diameter (73.03 mm to
82.55 mm) mounting hole.
• Requires 4 in. (102 mm) of vertical clearance.
• When installation requires conduit for Class 2 LumaCAN wiring, drill a
2 7/8 in. opening into the side of the junction box, and install the junction
box in the ceiling, directly above the sensor.
• LumaCAN wiring requires a Category-rated cable for power and data.
Use Category 6 or better cable with quality RJ-45 connections. Wire
per TIA-568B standards.
• For compliance with Chicago Plenum requirements, install in a metal box
in the ceiling. See the 3rd bullet point above.
• All LumaCAN wire segments must be tested and validated prior to
powering up the system.
• The end of each LumaCAN network must be terminated for proper data
flow. A termination plug is pre-installed into one of the RJ-45 receptacles. If
this is the end of the network, only one of the RJ-45 receptacles are used.
Leave the termination plug in the unused RJ-45 receptacle. If this is in the
middle of the network, both RJ-45 receptacles are required. Remove and
discard the termination plug.
GreenMax®DRC Sensor
Cat. No. OSR05-ICx
INSTALLATION INSTRUCTIONS ENGLISH
DI-000-OSR05-00C
Specifications
Input Voltage +12-24VDC, 70-35mA
IP Rating IP30
Network
Connections
• (2) RJ-45 Cat. 6 or better to connect to a
LumaCAN network.
• 1,600’ maximum length per Daisy-Chain Segment.
• Home-Run topology supported when using
repeaters, which may extend the network's length.
NOTE: Pass-Through RJ-45 connectors are prohibited
from use. Use of these connectors, voids all warranties,
and any promise of product suitability of operation.
Operating
Temperature
32°F to 131°F (0°C to 55°C),
0% to 85% relative humidity
Storage
Temperature 14°F to 185°F (-10°C to 85°C)
Sensor Range 450 sq. ft.
Sensor Technology PIR + Photocell
Warm-Up Time 15 seconds
Product Description
The GreenMax DRC Sensor is a direct network-connected device, which
can detect both Occupancy and Light levels within a specified range. It
reports data with LumaCAN™ Sensor messages over the network for
receipt by any Sapphire or GreenMAX DRC Room Controller.
Reference
A. LumaCAN Connections
B. Reset Switch - Push and hold down for 5 seconds to reset the
sensor's settings to their factory default settings.
For Application Reset: If your device is "bricked" and you power
up the device by pushing and holding down the reset switch for 10
seconds, the current application is deleted. As a result, the device
becomes inoperable, and you must perform a software update.
C. LumaCAN Communication Indicator Light - Normal Operation: Stays
solid Green when there is power, but no communication. Blinks Green
when communicating.
D. Occupancy Detector, Light Level Sensor, and Occupancy
Indicator Light:
• Blinks Red when PIR detects occupancy.
• Blinks Green when the photocell detects occupancy.
• Blinks White rapidly when a firmware update is in process.
• Blinks White slowly when in boot loader.
• Cycles colors when an address assignment is pending from a DRC
or other compatible controller.
A
C
D
WARNINGS:
• TO AVOID FIRE, SHOCK, OR DEATH, TURN OFF POWER AT CIRCUIT
BREAKER OR FUSE, AND TEST THAT THE POWER IS OFF BEFORE WIRING!
• To be installed and/or used in accordance with electrical codes and regulations.
• If you are not sure about any part of these instructions, consult an electrician.
Occupancy Sensor Technology and Application Notes:
• The OSR05-ICx sensor uses PIR (Passive InfraRed) detection
technology. This technology uses a lens to establish dozens of detection
zones. The sensor is sensitive to the heat emitted by the human body. To
trigger the sensor, the source of the heat must move from one detection
zone to another. The device is effective in sensing motion across its field-
of-view, and be conscientious of this when you select an
installation location.
• Occupancy sensors respond to rapid changes in temperature, and hot or
cold drafts look like body motion to the device if it mounted to close to a
climate control source. Make sure to mount this device approximately
6 ft away from a climate control source, such as radiators, air exchanges,
and air conditioners.
• Do NOT mount the Occupancy Sensor directly under a high-wattage light
source. High-wattage bulbs (greater than 100 W incandescent) give off a
lot of heat and switching the bulb may cause a temperature change that
can be detected by the device. Mount the Occupancy Sensor at least 6 ft
away. If you must mount the device closer, lower the bulb's wattage.
B