LG ARUN040GSS0 User manual

LG participates in the ECP programme for EUROVENT VRF program.
Check ongoing validity of certification : www.eurovent-certification.com
Heat Pump 380-415V + 380V
R410A(50Hz/60Hz)
0CVM0-01A
P/No. : MFL67474080

General information
MULTI V S
Outdoor Unit
1.Model Line-up &External Appearance
2.Nomenclature

2
MULTI V S Outdoor Unit General information
1. Model Line-up & External Appearance
1 Phase
3 Phase
Chassis Model Name External Appearance
Standard Compact
U4 ARUN040GSS0 ARUN050GSL0
U3 ARUN050GSS0
ARUN060GSS0 -
Chassis Model Name External Appearance
Standard
U3
ARUN040LSS0
ARUN050LSS0
ARUN060LSS0
ARUN080LSS0
U7 ARUN100LSS0
ARUN120LSS0

3
MULTI V S Outdoor Unit General information
2. Nomenclature
Model
Name ARU N 100 L S S 0
No.1234567
No. Signification
1MULTI V System Outdoor Unit using R410A
2
Combination of Inverter Type and Cooling Only or Heat Pump
N: Inverter and H/P, V: Inverter and C/O
3
Total Cooling Capacity in Horse Power (HP) unit
EX) 8HP → '080', 10HP → '100'
4
Electrical Ratings
L : 3Ø, 380-415V, 50Hz / 3Ø, 380V, 60Hz
G : 1Ø, 220-240V, 50Hz / 1Ø, 220V, 60Hz
5
Air Discharge Type
S : Side Discharge
6
Model Type
S : Standard
L : Compact
7Serial number

Product Data
MULTI V S
Outdoor Unit
1.List of Functions
2.Specifications
3.Dimensions
4.Electric Characteristics
5.Indoor Unit and Outdoor Unit Capacity Index
6.Capacity Tables
7.Capacity Correction Factor
8.Operation Limits
9.Piping Diagrams
10.Wiring Diagrams
11.Field Wiring
12.Sound Levels

2
MULTI V S Outdoor Unit Product Data
1. List of Functions
■Basic functions
Note
1. O : Applied X : Not applied
■Network solution Accessory List
Note
1. O : Applied, X : Not applied
Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
Accessory line-ups varies by region, so check your local catalogue or local sales material.
Category Functions Multi V S
1 Phase 3 Phase
Reliability
Defrost / Deicing O O
High pressure switch O O
Phase protection X O
Restart delay (3-minutes) O O
Self diagnosis O O
Soft start O O
Test Run function X X
Convenience Night Low Noise Operation O O
CAC network function Network solution(LGAP) O O
Device Accessory Model Name
Central Controller
AC Ez (Simple Controller) PQCSZ250S0
AC Ez Touch PACEZA000
AC Smart IV PACS4B000
AC Smart 5 PACS5A000
ACP(Advanced Control Platform) IV PACP4B000
ACP(Advanced Control Platform) 5 PACP5A000
AC Manager 5 PACM5A000
ACS IO Module PEXPMB000
DO(Digital Output) Kit PQNFP00T0
BNU
(Building Network Unit)
ACP Lonworks PLNWKB000
ACP BACnet PQNFB17C0
Installation Refrigerant Charging Kit O (Logical operation)
PDI
(Power Distribution Indicator)
Standard PPWRDB000
Premium PQNUD1S40
Cool / Heat Selector PRDSBM
Low Ambient Kit PRVC2
IO Module (ODU Dry Contact) PVDSMN000
Cycle Monitoring Device LGMV PRCTIL0
Mobile LGMV PLGMVW100
DS(Data Saving) Module PVADTN000

3
MULTI V S Outdoor Unit Product Data
2. Specifications
■1 Phase / Heat Pump
HP 45
Model Name ARUN040GSS0 ARUN050GSL0
Capacity
Cooling
kW 12.1 14.0
kcal/h 10,400 12,000
Btu/h 41,300 47,800
Heating
kW 12.5 15.0
kcal/h 10,800 12,900
Btu/h 42,700 51,200
Input (Rated) Cooling kW 4.03 5.34
Heating kW 3.10 3.98
EER 3.00 2.62
SEER 5.63 6.19
COP 4.03 3.77
SCOP 3.97 4.21
Power Factor Rated - 0.93 0.93
Exterior Color Warm Gray Warm Gray
RAL (Classis) RAL 7044 RAL 7044
Heat Exchanger Wide Louver Plus Wide Louver Plus
Compressor
Type BLDC Inverter Twin Rotary BLDC Inverter Twin Rotary
Piston Displacement cm3/rev 44.2 44.2
Number of Revolution rev/min 3,600 3,600
Motor Output W 4,000 4,000
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Oil Charge 1,300 1,300
Fan
Type Axial Flow Fan Axial Flow Fan
Motor Output x Number W 124 x 1 124 x 1
Air Flow Rate(High) m³/min 60 60
ft³/min 2,119 2,119
Drive DC INVERTER DC INVERTER
Discharge Side / Top Side Side
Pipe Connections Liquid mm(inch) Ø 9.52(3/8) Ø 9.52(3/8)
Gas mm(inch) Ø 15.88(5/8) Ø 15.88(5/8)
Dimensions(W x H x D) mm 950 × 834 × 330 950 × 834 × 330
inch 37-13/32 × 32-27/32 × 13 37-13/32 × 32-27/32 × 13
Net Weight kg 70 73
lbs 154 161
Sound Pressure
Level
Cooling dB(A) 50 52
Heating dB(A) 52 58
Sound Power
Level
Cooling dB(A) 72 72
Heating dB(A) 75 75
Protection
Devices
High pressure protection - High pressure sensor High pressure sensor
Comperssor/ Fan - Over-heat protection /
Fan driver overload protector
Over-heat protection /
Fan driver overload protector
Inverter - Over-heat protection /
Over-current protection
Over-heat protection /
Over-current protection
Communication Cable (VCTF-SB) No. x mm² 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5
Refrigerant
Refrigerant name R410A R410A
Precharged Amount kg 1.8 2.4
lbs 4.0 5.3
t-CO2eq. 3.758 5.010
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 220 - 230 - 240 , 1 , 50/60 220 - 230 - 240 , 1 , 50/60
Running Current Cooling A 19.70 - 18.84 - 18.06 26.10 - 24.96 - 23.92
Heating A 15.15 - 14.49 - 13.89 19.45 - 18.61 - 17.83
Number of maxmum connectable indoor units 8 8*
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Performances are based on the following conditions :
• *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
5. EUROVENT Test Condition :
• Performance values in this PDB are based on Ceiling mounted cassette combination.
• Refer to EUROVENT web site(www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
6. The maximum combination ratio is 160%.
7. This product contains Fluorinated greenhouse gases.
9. * : In case of ARUN050GSL0, maximum combination ratio is 130%.

MULTI V S Outdoor Unit
2. Specifications
4
Product Data
HP 56
Model Name ARUN050GSS0 ARUN060GSS0
Capacity
Cooling
kW 14.0 15.5
kcal/h 12,000 13,300
Btu/h 47,800 52,900
Heating
kW 16.0 18.0
kcal/h 13,800 15,500
Btu/h 54,600 61,400
Input (Rated) Cooling kW 4.59 5.17
Heating kW 4.18 5.00
EER 3.05 3.00
SEER 7.40 7.53
COP 3.83 3.60
SCOP 4.16 4.35
Power Factor Rated - 0.93 0.93
Exterior Color Warm Gray Warm Gray
RAL (Classis) RAL 7044 RAL 7044
Heat Exchanger Wide Louver Plus Wide Louver Plus
Compressor
Type BLDC Inverter Twin Rotary BLDC Inverter Twin Rotary
Piston Displacement cm3/rev 44.2 44.2
Number of Revolution rev/min 3,600 3,600
Motor Output W 4,000 4,000
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Oil Charge 1,300 1,300
Fan
Type Axial Flow Fan Axial Flow Fan
Motor Output x Number W 124 x 2 124 x 2
Air Flow Rate(High) m³/min 110 110
ft³/min 3,885 3,885
Drive DC INVERTER DC INVERTER
Discharge Side / Top Side Side
Pipe Connections Liquid mm(inch) Ø 9.52(3/8) Ø 9.52(3/8)
Gas mm(inch) Ø 15.88(5/8) Ø 19.05(3/4)
Dimensions(W x H x D) mm 950 × 1,380 × 330 950 × 1,380 × 330
inch 37-13/32 × 54-11/32 × 13 37-13/32 × 54-11/32 × 13
Net Weight kg 94 94
lbs 207 207
Sound Pressure
Level
Cooling dB(A) 51 52
Heating dB(A) 53 54
Sound Power
Level
Cooling dB(A) 72 72
Heating dB(A) 76 77
Protection
Devices
High pressure protection - High pressure sensor High pressure sensor
Comperssor/ Fan - Over-heat protection /
Fan driver overload protector
Over-heat protection /
Fan driver overload protector
Inverter - Over-heat protection /
Over-current protection
Over-heat protection /
Over-current protection
Communication Cable (VCTF-SB) No. x mm² 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5
Refrigerant
Refrigerant name R410A R410A
Precharged Amount kg 3.0 3.0
lbs 6.6 6.6
t-CO2eq. 6.263 6.263
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 220 - 230 - 240 , 1 , 50/60 220 - 230 - 240 , 1 , 50/60
Running Current Cooling A 22.43 - 21.46 - 20.56 25.27 - 24.17 - 23.16
Heating A 20.43 - 19.54 - 18.73 24.44 - 23.38 - 22.40
Number of maxmum connectable indoor units 10 13
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Performances are based on the following conditions :
• *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
5. EUROVENT Test Condition :
• Performance values in this PDB are based on Ceiling mounted cassette combination.
• Refer to EUROVENT web site(www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
6. The maximum combination ratio is 160%.
7. This product contains Fluorinated greenhouse gases.
9. * : In case of ARUN050GSL0, maximum combination ratio is 130%.

2. Specifications
5
MULTI V S Outdoor Unit Product Data
■3 Phase / Heat Pump
HP 45
Model Name ARUN040LSS0 ARUN050LSS0
Capacity
Cooling
kW 12.1 14.0
kcal/h 10,400 12,000
Btu/h 41,300 47,800
Heating
kW 12.5 16.0
kcal/h 10,800 13,800
Btu/h 42,700 54,600
Input (Rated) Cooling kW 3.39 4.59
Heating kW 2.75 4.18
EER 3.57 3.05
SEER 7.42 7.40
COP 4.55 3.83
SCOP 4.30 4.16
Power Factor Rated - 0.93 0.93
Exterior Color Warm Gray Warm Gray
RAL (Classis) RAL 7044 RAL 7044
Heat Exchanger Wide Louver Plus Wide Louver Plus
Compressor
Type BLDC Inverter Twin Rotary BLDC Inverter Twin Rotary
Piston Displacement cm3/rev 44.2 44.2
Number of Revolution rev/min 3,600 3,600
Motor Output W 4,000 4,000
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Oil Charge 1,300 1,300
Fan
Type Axial Flow Fan Axial Flow Fan
Motor Output x Number W 124 x 2 124 x 2
Air Flow Rate(High) m³/min 110 110
ft³/min 3,885 3,885
Drive DC INVERTER DC INVERTER
Discharge Side / Top Side Side
Pipe Connections Liquid mm(inch) Ø 9.52(3/8) Ø 9.52(3/8)
Gas mm(inch) Ø 15.88(5/8) Ø 15.88(5/8)
Dimensions(W x H x D) mm 950 × 1,380 × 330 950 × 1,380 × 330
inch 37-13/32 × 54-11/32 × 13 37-13/32 × 54-11/32 × 13
Net Weight kg 96 96
lbs 212 212
Sound Pressure
Level
Cooling dB(A) 50 51
Heating dB(A) 52 53
Sound Power
Level
Cooling dB(A) 72 72
Heating dB(A) 76 76
Protection
Devices
High pressure protection - High pressure sensor High pressure sensor
Comperssor/ Fan - Over-heat protection /
Fan driver overload protector
Over-heat protection /
Fan driver overload protector
Inverter - Over-heat protection /
Over-current protection
Over-heat protection /
Over-current protection
Communication Cable (VCTF-SB) No. x mm² 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5
Refrigerant
Refrigerant name R410A R410A
Precharged Amount kg 3.0 3.0
lbs 6.6 6.6
t-CO2eq. 6.263 6.263
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 220 - 230 - 240 , 1 , 50/60 220 - 230 - 240 , 1 , 50/60
Running Current Cooling A 5.54 - 5.26 - 5.07 7.50 - 7.12 - 6.87
Heating A 4.49 - 4.27 - 4.11 6.83 - 6.49 - 6.25
Number of maxmum connectable indoor units 8 10
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Performances are based on the following conditions :
• *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
5. EUROVENT Test Condition :
• Performance values in this PDB are based on Ceiling mounted cassette combination.
• Refer to EUROVENT web site(www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
6. The maximum combination ratio is 160%.
7. This product contains Fluorinated greenhouse gases.
9. * : In case of ARUN050GSL0, maximum combination ratio is 130%.

MULTI V S Outdoor Unit
2. Specifications
6
Product Data
HP 68
Model Name ARUN060LSS0 ARUN080LSS0
Capacity
Cooling
kW 15.5 22.4
kcal/h 13,300 19,300
Btu/h 52,900 76,400
Heating
kW 18.0 24.5
kcal/h 15,500 21,100
Btu/h 61,400 83,600
Input (Rated) Cooling kW 5.17 8.45
Heating kW 5.00 6.96
EER 3.00 2.65
SEER 7.53 7.13
COP 3.60 3.52
SCOP 4.35 4.53
Power Factor Rated - 0.93 0.93
Exterior Color Warm Gray Warm Gray
RAL (Classis) RAL 7044 RAL 7044
Heat Exchanger Wide Louver Plus Wide Louver Plus
Compressor
Type BLDC Inverter Twin Rotary Hermetically Sealed Scroll
Piston Displacement cm3/rev 44.2 43.8
Number of Revolution rev/min 3,600 3,600
Motor Output W 4,000 4,200
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Oil Charge 1,300 2,400
Fan
Type Axial Flow Fan Propeller fan
Motor Output x Number W 124 x 2 124 x 2
Air Flow Rate(High) m³/min 110 140
ft³/min 3,885 4,944
Drive DC INVERTER DC INVERTER
Discharge Side / Top Side Side
Pipe Connections Liquid mm(inch) Ø 9.52(3/8) Ø 9.52(3/8)
Gas mm(inch) Ø 19.05(3/4) Ø 19.05(3/4)
Dimensions(W x H x D) mm 950 × 1,380 × 330 950 × 1,380 × 330
inch 37-13/32 × 54-11/32 × 13 37-13/32 × 54-11/32 × 13
Net Weight kg 96 115
lbs 212 254
Sound Pressure
Level
Cooling dB(A) 52 57
Heating dB(A) 54 57
Sound Power
Level
Cooling dB(A) 72 78
Heating dB(A) 77 81
Protection
Devices
High pressure protection - High pressure sensor High pressure sensor
Comperssor/ Fan - Over-heat protection /
Fan driver overload protector
Over-heat protection /
Fan driver overload protector
Inverter - Over-heat protection /
Over-current protection
Over-heat protection /
Over-current protection
Communication Cable (VCTF-SB) No. x mm² 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5
Refrigerant
Refrigerant name R410A R410A
Precharged Amount kg 3.0 3.5
lbs 6.6 7.7
t-CO2eq. 6.263 7.306
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380 - 400 - 415, 3, 50/60 380 - 400 - 415, 3, 50/60
Running Current Cooling A 8.45 - 8.02 - 7.73 13.8 - 13.11 - 12.64
Heating A 8.17 - 7.76 - 7.48 11.37 - 10.80 - 10.41
Number of maxmum connectable indoor units 13 13
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Performances are based on the following conditions :
• *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
5. EUROVENT Test Condition :
• Performance values in this PDB are based on Ceiling mounted cassette combination.
• Refer to EUROVENT web site(www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
6. The maximum combination ratio is 160%.
7. This product contains Fluorinated greenhouse gases.
9. * : In case of ARUN050GSL0, maximum combination ratio is 130%.

2. Specifications
7
MULTI V S Outdoor Unit Product Data
HP 10 12
Model Name ARUN100LSS0 ARUN120LSS0
Capacity
Cooling
kW 28.0 33.6
kcal/h 24,100 28,900
Btu/h 95,900 114,700
Heating
kW 30.6 36.7
kcal/h 26,300 31,600
Btu/h 104,400 125,200
Input (Rated) Cooling kW 12.44 15.27
Heating kW 8.50 12.23
EER 2.25 2.20
SEER 6.28 6.50
COP 3.60 3.00
SCOP 4.21 4.32
Power Factor Rated - 0.93 0.93
Exterior Color Warm Gray Warm Gray
RAL (Classis) RAL 7044 RAL 7044
Heat Exchanger Wide Louver Plus Wide Louver Plus
Compressor
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 62.1
Number of Revolution rev/min 3,600 3,600
Motor Output W 5,300 5,300
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Oil Charge 2,600 3,400
Fan
Type Propeller fan Propeller fan
Motor Output x Number W 250 x 2 250 x 2
Air Flow Rate(High) m³/min 190 190
ft³/min 6,710 6,710
Drive DC INVERTER DC INVERTER
Discharge Side / Top Side Side
Pipe Connections Liquid mm(inch) Ø 9.52(3/8) Ø 12.7(1/2)
Gas mm(inch) Ø 22.2(7/8) Ø 28.58(1 1/8)
Dimensions(W x H x D) mm 1,090 × 1,625 × 380 1,090 x 1,625 x 380
inch 42-29/32 × 63-31/32 × 14-31/32 42-29/32 × 63-31/32 × 14-31/32
Net Weight kg 142 155
lbs 312 340
Sound Pressure
Level
Cooling dB(A) 58 60
Heating dB(A) 58 60
Sound Power
Level
Cooling dB(A) 77 78
Heating dB(A) 79 82
Protection
Devices
High pressure protection - High pressure sensor High pressure sensor
Comperssor/ Fan - Over-heat protection /
Fan driver overload protector
Over-heat protection /
Fan driver overload protector
Inverter - Over-heat protection /
Over-current protection
Over-heat protection /
Over-current protection
Communication Cable (VCTF-SB) No. x mm² 2C x 1.0 ~ 1.5 2C x 1.0 ~ 1.5
Refrigerant
Refrigerant name R410A R410A
Precharged Amount kg 4.5 6.0
lbs 9.9 13.2
t-CO2eq. 9.394 12.525
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380 - 400 - 415, 3, 50/60 380 - 400 - 415, 3, 50/60
Running Current Cooling A 20.32 - 19.31 - 18.61 24.95 - 23.7 - 22.84
Heating A 13.89 - 13.19 - 12.72 19.98 - 18.98 - 18.30
Number of maxmum connectable indoor units 16 20
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Performances are based on the following conditions :
• *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
5. EUROVENT Test Condition :
• Performance values in this PDB are based on Ceiling mounted cassette combination.
• Refer to EUROVENT web site(www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
6. The maximum combination ratio is 160%.
7. This product contains Fluorinated greenhouse gases.
9. * : In case of ARUN050GSL0, maximum combination ratio is 130%.

8
MULTI V S Outdoor Unit Product Data
3. Dimensions
3.1 Dimensional Drawings
ARUN040GSS0 / ARUN050GSL0
Chassis : U4
TBW35046501_Rev.01

3. Dimensions
9
MULTI V S Outdoor Unit Product Data
ARUN050GSS0 / ARUN060GSS0
ARUN040LSS0 / ARUN050LSS0 / ARUN060LSS0 / ARUN080LSS0
Welding joint
Welding joint
Chassis Code : U3
TBW34666901-1_Rev.01

MULTI V S Outdoor Unit
3. Dimensions
10
Product Data
ARUN100LSS0 / ARUN120LSS0
Chassis : U7
TBW35746501_Rev.01

3. Dimensions
11
MULTI V S Outdoor Unit Product Data
3.2 Center of Gravity
ARUN040GSS0 / ARUN050GSL0
ARUN050GSS0 / ARUN060GSS0
ARUN040LSS0 / ARUN050LSS0 / ARUN060LSS0 / ARUN080LSS0
Model Name X
[mm]
Y
[mm]
Z
[mm]
ARUN040GSS0
ARUN050GSL0 740 340 170
Model Name X
[mm]
Y
[mm]
Z
[mm]
ARUN050GSS0
ARUN060GSS0
ARUN040LSS0
ARUN050LSS0
ARUN060LSS0
ARUN080LSS0
440 657 233
X
Y
Z
X
Y
Z

MULTI V S Outdoor Unit
3. Dimensions
12
Product Data
ARUN100LSS0 / ARUN120LSS0
Model Name X
[mm]
Y
[mm]
Z
[mm]
ARUN100LSS0
ARUN120LSS0 522 750 256
X
Y
Z

13
MULTI V S Outdoor Unit Product Data
4. Electric Characteristics
■Wiring of Main Power Supply and Equipment Capacity
1. Use a separate power supply for the Outdoor Unit and Indoor Unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain liquid,etc.) when proceeding with the
wiring and connections
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking
into account the line voltage drops. Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed
flexible cord (design 60245 IEC57).
6. Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power
supply.
WARNING
•Follow ordinance of local regulation for technical standard related to electrical equipment, wiring
regulations and guidance of each electric power company.
•Make sure to use specified wires for connections so that no external force is imparted to terminal
connections. If connections are not fixed firmly, it may cause heating or fire.
•Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent
may include some amount of direct current.
•All Installation site must require attachment of an earth leakage breaker. If no earth leakage breaker is
installed, it may cause an electric shock.
CAUTION
•Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper
wire with too large capacity may cause a malfunction of unit or fire.

MULTI V S Outdoor Unit
4. Electric Characteristics
14
Product Data
4.1 1 Phase / Heat Pump
■50Hz
■60Hz
Model Unit Power Supply COMP OFM
Hz Volts Voltage-range MCA TOCA MFA MSC RLA(Cooling) RLA(Heating) kW FLA
4 HP 50 220-240 Min.:198, Max.:264 25.0 26.0 30 - 17.8 13.5 0.12 1.0
5 HP
(1Fan) 50 220-240 Min.:198, Max.:264 27.5 26.0 30 - 24.0 17.6 0.12 1.0
5 HP
(2Fan) 50 220-240 Min.:198, Max.:264 27.5 26.0 30 - 20.5 18.5 0.35 1.0
6 HP 50 220-240 Min.:198, Max.:264 29.4 26.0 40 - 23.2 22.4 0.35 1.0
Model Unit Power Supply COMP OFM
Hz Volts Voltage-range MCA TOCA MFA MSC RLA(Cooling) RLA(Heating) kW FLA
4 HP 60 220 Min.:198, Max.:242 25.0 26.0 30 - 17.8 13.5 0.12 1.0
5 HP
(1Fan) 60 220 Min.:198, Max.:242 27.5 26.0 30 - 24.0 17.6 0.12 1.0
5 HP
(2Fan) 60 220 Min.:198, Max.:242 27.5 26.0 30 - 20.5 18.5 0.35 1.0
6 HP 60 220 Min.:198, Max.:242 29.4 26.0 40 - 23.2 22.4 0.35 1.0
Note
1. Voltage supplied to the unit terminals should be within the minimum and maximum
range.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MSC means the Max. current during the starting of compressor.
4. MSC and RLA are measured as the compressor only test condition.
5. OFM are measured as the outdoor unit test condition.
6. TOCA means the total over current value of each outdoor unit.
7. Select the wire size based on the larger value among MCA or TOCA.
8. MFA is recommended fuse amps.
9. TOCA is minimum required amperes for selecting the circuit breaker and ground fault
circuit interrupter. Please select the circuit breaker size equal or greater than TOCA.
All installation site must require attachment of an earth leakage breaker.[Circuit
breaker type is ELCB (Earth Leakage Circuit Breaker)].
10.Select the electrical equipment of combination unit according to the electrical
characteristics of individual unit.
Symbols
MCA : Minimum Circuit Amperes (A)
TOCA : Total Over Current Amperes (A)
MFA : Maximum Fuse Amperes (A)
MSC : Maximum Starting Current (A)
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)

4. Electric Characteristics
15
MULTI V S Outdoor Unit Product Data
4.2 3 Phase / Heat Pump
■50Hz
■60Hz
Model Unit Power Supply COMP OFM
Hz Volts Voltage-range MCA TOCA MFA MSC RLA(Cooling) RLA(Heating) kW FLA
4 HP 50 380-415 Min.:342, Max.:456 12.5 17.0 20 - 4.3 3.3 0.35 1.0
5 HP 50 380-415 Min.:342, Max.:456 14.4 17.0 20 - 6.1 5.5 0.35 1.0
6 HP 50 380-415 Min.:342, Max.:456 16.1 17.0 20 - 7.0 6.8 0.35 1.0
8 HP 50 380-415 Min.:342, Max.:456 21.3 24.0 30 4.0 12.1 9.8 0.35 1.0
10 HP 50 380-415 Min.:342, Max.:456 26.3 35.0 30 4.5 16.5 10.4 0.50 2.8
12 HP 50 380-415 Min.:342, Max.:456 32.5 35.0 35 4.5 20.9 16.2 0.50 2.8
Model Unit Power Supply COMP OFM
Hz Volts Voltage-range MCA TOCA MFA MSC RLA(Cooling) RLA(Heating) kW FLA
4 HP 60 380 Min.:342, Max.:418 12.5 17.0 20 - 4.3 3.3 0.35 1.0
5 HP 60 380 Min.:342, Max.:418 14.4 17.0 20 - 6.1 5.5 0.35 1.0
6 HP 60 380 Min.:342, Max.:418 16.1 17.0 20 - 7.0 6.8 0.35 1.0
8 HP 60 380 Min.:342, Max.:418 21.3 24.0 30 4.0 12.1 9.8 0.35 1.0
10 HP 60 380 Min.:342, Max.:418 26.3 35.0 30 4.5 16.5 10.4 0.50 2.8
12 HP 60 380 Min.:342, Max.:418 32.5 35.0 35 4.5 20.9 16.2 0.50 2.8
Note
1. Voltage supplied to the unit terminals should be within the minimum and maximum
range.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MSC means the Max. current during the starting of compressor.
4. MSC and RLA are measured as the compressor only test condition.
5. OFM are measured as the outdoor unit test condition.
6. TOCA means the total over current value of each outdoor unit.
7. Select the wire size based on the larger value among MCA or TOCA.
8. MFA is recommended fuse amps.
9. TOCA is minimum required amperes for selecting the circuit breaker and ground fault
circuit interrupter. Please select the circuit breaker size equal or greater than TOCA.
All installation site must require attachment of an earth leakage breaker.[Circuit
breaker type is ELCB (Earth Leakage Circuit Breaker)].
10.Select the electrical equipment of combination unit according to the electrical
characteristics of individual unit.
Symbols
MCA : Minimum Circuit Amperes (A)
TOCA : Total Over Current Amperes (A)
MFA : Maximum Fuse Amperes (A)
MSC : Maximum Starting Current (A)
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
Other manuals for ARUN040GSS0
1
This manual suits for next models
9
Table of contents
Other LG Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Frigidaire
Frigidaire GHWQ103WC1 use & care

Mitsubishi Electric
Mitsubishi Electric CITY MULTI PKFY-P-VBM-E installation manual

GE
GE ASQ12AL Dimensions and installation information

Dometic
Dometic Blizzard NXT H540315 installation instructions

Hitachi
Hitachi airHome 400 DJ Series Operation manual

Fujitsu
Fujitsu AUXG18KVLA Design & technical manual