- 2 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes LGE Internal Use Only
1. Specification
Cooling Capacity kW
(Min~Rating~Max) Btu/h.
Heating Capacity kW
(Min~Rating~Max) Btu/h.
Power Input Cooling/Heating W
Running Current Cooling/Heating A
Starting Current Cooling/Heating A
EER W/W
Btu/h.W
COP W/W
Power Supply Ø / V / Hz
Power Factor %
Air Flow Rate Indoor,Max m
3
/min(CFM)
Outdoor,Max m
3
/min(CFM)
Moisture Removal l/h.
Sound Level Indoor,H/M/L dB(A)±3
Outdoor,Max dB(A)±3
Refrigerant & Charge(at 7.5 m) g(oz)
Additional Refrigerant charge g/m(oz/ft)
Compressor Type
Model
Motor Type
Oil Type
Oil Charge cc
O.L.P. name
Fan(Indoor) Type
Motor Output W
Fan(Outdoor) Type
Motor Type
Motor Output W
Circuit Breaker* A
Power Supply Cable No.*mm
2
Power and Transmission Cable No.*mm
2
+No.*mm
2
Piping Liquid Side mm(in)
Connections Gas Side mm(in)
Drain Hose O.D., I.D. mm(in)
Dimensions Indoor (W*H*D) mm
inch
Outdoor (W*H*D) mm
inch
Net Weight Indoor kg(lbs)
Outdoor kg(lbs)
Operation Range Cooling(Outdoor) °C(°F)
Heating(Outdoor) °C(°F)
Max. Piping Length m(ft)
Max. Elevation Difference m(ft)
Tool Code(Chassis) Indoor + Outdoor
Models ASNW30GDGM0
AUUW306D
8
27297
9.6
32756
2,690/3,250
12.0/14.5
12.0/14.5
2.97
10.13
2.95
1 / 220 ~ 240 / 50
97
21(742)
58(2048)
3.5
48 /44/ 39
58
R410A, 1,800(63.3)(at 10m)
30(0.323)
Twin Rotary
5KD240XAE21
Brushless DC motor
FV50S
900
CS-7L 115
Cross Flow Fan
70
Propeller
Brushless DC motor
80
25
3*2.5
4*0.75
6.35(1/4)
15.88(5/8)
21.5, 16 (0.85, 0.63)
1,209*346*205
47.6*13.6*8.1
870*800*320
34.3*31.5*12.6
18(39.7)
60(132.3)
-10 ~ 43 (14 ~ 109.4)
-15 ~ 24 (5 ~ 75.2)
50(164)
30(98.4)
SD + UE1
Note:
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national
code.
3. The specification may be subject to change without notic for purpose