Lightolier LyteMode User manual


Lightolier Controls
2828 Trade Center Dr. Ste. 130B
Carrollton, TX 75007
+1-800-526-2731 (In the United States and Canada)
214-647-7880
Fax: 214-647-8032
www.lolcontrols.com
This manual is for informational use only and is subject to change without notice.
Lightolier Controls assumes no responsibility or liability for any claims resulting
from errors or inaccuracies that may appear in this manual.
Version as of: July 16, 2008
Document: P/N: 85-6353A0
Lytemode Classic Digital Keypad User’s Guide
©2008 Philips Group. All Rights Reserved.
Lightolier Controls is a Philips group brand.

Classic Digital Keypad User’s Guide 1
Table of Contents
Customer Service .....................................................................2
Classic Digital Keypads Overview ..........................................3
Quick Start ...............................................................................4
Classic Digital Keypad Configurations ...................................5
Installation ...............................................................................6
Setting ILS Network ID ...........................................................7
Basic Setup ..............................................................................9
Mode .................................................................................9
ID Address ......................................................................11
LED Intensity .................................................................12
Operation ...............................................................................13
Selecting a Scene ............................................................13
Factory Defaults and Troubleshooting ..................................14
Resetting Factory Defaults .............................................14
Troubleshooting ..............................................................15
Specifications ........................................................................16

2Customer Service
Customer Service
Technical and Sales assistance for Lytemode products is available
worldwide.
Phone: +1-800-526-2731 (In the United States and Canada)
+1-214-647-7880 (Worldwide)

Classic Digital Keypad User’s Guide 3
Classic Digital Keypads Overview
Lightolier Controls Classic Digital Keypads offer intuitive user
control of lighting circuits in a broad range of applications.
Classic Digital Keypads are compatible with IntelliSight
Occupancy Sensors, Photocells, and Power Packs, Lyteswitch
Low-Voltage Lighting Control Panels, and Lytemode
Architectural Dimming Systems including Optio and Capio
Plus.
The architecturally neutral appearance and robust construction
provide years of trouble-free service. Field applied labels allow
button descriptions to be easily changed to match the most common
control functions.
Programming of keypads is both fast and simple. Walk-Around-
Programming allows complete setup of a keypad within minutes
without having to remove the device from the wall, or configure
DIP switches or dials.
Backlit buttons feature variable intensity and an audible alert to
provide confirmation and warn occupants of changes to the lighting
levels.
Classic Digital Keypads are available in a variety of button counts,
and are provided white White buttons and a white screwless
faceplate, or with black buttons and a stainless-steel faceplate.

4Quick Start
Quick Start
To get a Classic Digital Keypad up and running quickly, use the
following checklist:
Step 1. Install unit (refer to “Installation” on page 6).
Step 2. Connect to Lytemode ILS Network or ITS Network (refer
to “Setting ILS Network ID” on page 7).
Step 3. Set the mode (refer to “Mode” on page 9).
The unit should now be ready for operation.

Classic Digital Keypad User’s Guide 5
Classic Digital Keypad Configurations
The Classic Digital Keypad is available in the following button
configurations, and may be ordered as either White with a white
screwless faceplate, or Black with a stainless-steel faceplate:
* Standard keypad labeling shown. Each Classic Digital Keypad includes a
sheet of labels featuring common descriptions that may be installed easily
in the field.
ON A
BC
DE
ON
OFF
ON A
BC
DE
FOFF
ON A ON A
BOFF
AB
CD
OFF
ON
OFF OFF
2 BUTTON 3 BUTTON 4 BUTTON
6 BUTTON 7 BUTTON 8 BUTTON

6Installation
Installation
The Lytemode ILS Network consists of a single CAT5e cable
connecting all ILS modules in a daisy chain manner. All units
connect to the network using a 9-pin connector (included).
To install:
Step 1. Unpack unit and inspect for any signs of shipping damage.
Ensure that two mounting screws are included.
Step 2. Connect ILS Network Cable to 9-pin connector at back of
Classic Digital Keypad.
Step 3. Insert unit into single-gang, standard deep box (not
included). Secure with two supplied mounting screws.
1WH/OR(+Data)
2 OR (- Data)
3SHIELD
4WH/GN(+Volts)
5 GN (Ground)
6WH/BL(+Volts)
7 BL (Ground)
8WH/BR(+Volts)
9 BR (Ground)
9-Pin Connector Wiring
PIN SIGNAL
9-Pin
Faceplate
Connector
Classic
Digital Keypad
Single-Gang, Standard
Deep Box (not included)

Classic Digital Keypad User’s Guide 7
Step 4. For white screwless faceplates, snap faceplate into place.
For stainless-steel faceplates, mount using two supplied
screws.
Setting ILS Network ID
Lytemode products are controlled by the Intelligent Lytemode
System (ILS) protocol. All Lytemode ILS devices must be given an
ID (or address), which identifies the device on the network and
allows it to avoid network collisions when transmitting data.
Standard IDs are in the range of 1 to 255. An ID of 0 will disable
the unit and prevent it from transmitting on the network.
IDs are typically unique. For example, an ILS Master will require a
unique ID to allow dimmers to track its channel levels. However,
ILS Remotes should be given the same ID as the ILS Master it
controls. ILS Remotes rely on the fact that they are manually
triggered to avoid network collisions with other ILS Remotes
having the same ID.
The table on the following page provides guidelines for addressing.

8Setting ILS Network ID
ILS Network Addressing:
* Notes:
1 – Matches ILS Master ID.
2 – ILS Masters must be programmed to accept.
3 – Will respond to Remote Polls, Status Requests and Commands.
Note: Refer to the instructions included with your particular
device(s) in order to set corresponding control IDs.
Device ID Sub-ID Devices / ID Remotely
Polled? Notes *
Remote 1-255 0 Multiple No 1
Global Remote 1-255 0 Multiple No 2
Remote Keypad 1-255 0-7 1 Yes 3
IntelliSight (ITS) 1-255 0-7 1 Yes 3
Channel Master 1-255 0-7 1 Yes 3

Classic Digital Keypad User’s Guide 9
Basic Setup
This section describes how to program the unit’s Mode, Address,
and LED Brightness.
Mode
The unit can be set to function in one of several Modes as follows:
Step 1. Press and hold Hand Ifor 3 or more
seconds. (ELED will blink rapidly.)
Step 2. Enter Mode by setting J,K and L buttons
as either Off or On as shown in the
following table. (LEDs will blink for any
Mode not supported.)
Step 3. Press Eto save and exit.
Mode J K L
0 – Remote Off Off Off
1 – Global Remote Off Off On
2 – Remote Keypad Off On Off
3 – IntelliSight (ITS) Off On On
L
G
H
I
J
K
F
E
L
G
H
I
J
K
F
E
G
H
F
E
Example:
Mode 3

10 Basic Setup
Mode Function
0 – Remote Used to trigger Scenes and perform
Master Raise/Lower on ILS Masters.
1 – Global Remote Same as Remote, but transmits a Global
command used to link several ILS
Masters. ILS Masters must be
programmed to respond to the Global
ID.
2 – Remote Keypad Transmits key presses and releases.
LEDs are controlled by Remote
Commands.
3 – IntelliSight (ITS) Controls a connected IntelliSight
Power Pack.

Classic Digital Keypad User’s Guide 11
ID Address
Because there are not enough buttons/LEDs to address the full 0-
255 ID range, the ID must be entered in two stages. The three most
significant ID bits are entered first, followed by the five least
significant ID bits.
Step 1. Press and hold Gand Jfor 3 or more
seconds. (ELED will blink On 75% and
Off 25%.)
Step 2. Enter three most significant ID bits in J-K-
L. Use F/G to increment/decrement value.
Step 3. Press E.(ELED will blink On 25% and
Off 75%.)
Step 4. Enter five least significant ID bits in H-I-
J-K-L. Use F/G to increment/decrement
value.
Step 5. Press Eto save and exit.
ID Values:
J = 128 (most significant ID)
K = 64 (most significant ID)
L = 32 (most significant ID)
H = 16 (least significant ID)
I = 8 (least significant ID)
J = 4 (least significant ID)
K = 2 (least significant ID)
L = 1 (least significant ID)
L
G
H
I
J
K
F
E
L
G
H
I
J
K
F
E
L
G
H
I
J
K
F
E

12 Basic Setup
While in the Addressing Mode, the device will transmit a Network
Test Command every 2 seconds (Ewill blink). All devices on the
network will blink an LED to indicate their reception of this
command. If a receiving device matches the transmitted ID, it will
blink all of its LEDs. Those devices that are capable of being polled
will return a Network Test Response if the transmitted ID matches
their own ID. If the transmitting device sees a Network Test
Response, it will double blink its ELED. This is useful for network
testing and to determine if the ID is unique.
Note: When programming the ID of a unit set to Remote (Mode 0),
tapping the Raise or Lower button on a Master, Mini-Master, or
another Remote unit will capture the ID and exit the Set ID mode.
LED Intensity
The intensity (brightness) of the LEDs can be set as follows:
Step 1. Press and hold Hand Jfor 3 or more
seconds. G-H-I-J LEDs will display four
intensity choices. (Current intensity setting
button will blink.)
Step 2. Press desired intensity button.
Step 3. Press Eto save and exit.
L
G
H
I
J
K
F
E
F
E

Classic Digital Keypad User’s Guide 13
Operation
Selecting a Scene
An 8-button keypad provides access to eight Scenes (E-L). To
select a Scene, press the appropriate button on the keypad.
L
G
H
I
J
K
F
E

14 Factory Defaults and Troubleshooting
Factory Defaults and Troubleshooting
Resetting Factory Defaults
To set the unit back to its Factory Defaults, do the following:
Step 1. Remove unit from wall and unplug ILS
Network connector (if equipped) and ITS
Network connector (if equipped).
Step 2. Press and hold Eand L.
Step 3. While still holding E/L buttons, apply
power to unit while re-connecting either
the ILS Network connector or the ITS
Network connector.
Factory Defaults are as follows:
• Unit Mode = 5 (Lyteswitch)
• Unit ID = 1
• LED intensity = 100%
L
G
H
I
J
K
F
E
L
G
H
I
J
K
F
E

Classic Digital Keypad User’s Guide 15
Troubleshooting
In order to determine if all Lytemode ILS Network devices are
communicating, a network test signal can be sent by initiating the
Walk-Around-Programming mode from any Lyteswitch Lighting
Control Panel. While in this mode, the the Lyteswitch relay panel
will transmit a Network Test Command every 2 seconds. All
devices on the network will blink an LED and beep to indicate their
reception of this command.

16 Specifications
Specifications
Electrical:
• Input Power: +18-26 VDC
(powered from Lytemode ILS Network or IntelliSight ITS Network)
• Current: 20mA
• Temperature
- Storage: -25° to 85° C
- Operating: 0° to 40° C
- Relative Humidity: 30-90% (non-condensing)

Classic Digital Keypad User’s Guide 17
Notes

18 Notes
Notes
Table of contents
Popular Keypad manuals by other brands

DSC
DSC RF5501-433 installation manual

teko
teko ASTRA-Z-8145 Pro operating manual

Toshiba
Toshiba RKP004Z-0 instruction manual

DMP Electronics
DMP Electronics 7800 Series Installation and programming guide

Elkron
Elkron KP500L quick start guide

IntelliControl ICS
IntelliControl ICS Contact-TT Quick install guide