LST Extinguishing Control Panel BC06-2EXT User manual

0786–CPD–20300
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 1
ABuilding Safety. Building Security.
Extinguishing Control Panel
BC06-1EXT, BC06-2EXT
• For application in single-zone
extinguishing systems
• 4 detector zones in conventional
technology
• Differentiation between the activation
of automatic detectors and manual
call points on the same detector line
• Clear display and operation on the
panel front
• Tested to EN 54-2, -4, EN 12094-1 by
VdS
Already in the basic version the combined Fire/Extingu-
ishing Control Panels BC06-1EXT and BC06-2EXT are
equipped with four detector lines and the Extinguishing
Board EXB1-1 and, owing to its sophisticated factory
settings, are immediately ready for operation. This al-
lows for quick and effi cient application of the product.
The conventional technology allows for the connection
of automatic and non-automatic fi re detectors as well
as a wide range of special detectors with contact out-
put. Alarms from manual call points and from automatic
detectors that are connected together to one detector
line can be differentiated and thus evaluated differently
by the fi re/extinguishing control panel, by means of an
optional coding module.
Thanks to the two auxiliary inputs whose parameters
can be freely set as well as the eight open-collector out-
puts, manifold tasks in the fi eld of fi re alarm technology
can be realised.
The optional evacuation function serves for the actu-
ation of alarming devices independent from activated
alarms.
Thanks to the integrated extinguishing module, the
BC06 can be used as an extinguishing control panel
according to EN 12094-1 with one fl ooding zone. The
module provides appropriate inputs and outputs for con-
trolling and monitoring a fl ooding zone. The display and
operating elements that are necessary for the status
indication and the operation of the extinguishing module
are integrated into the keypad.
A printer for the event log can be connected via the
optional Serial Interface Modul SIM06-1.
The Fire/Extinguishing Control Panel BC06-2EXT dif-
fers from the BC06-1EXT by the additionally integrated
4-digit electronic alarm counter.
Fire is a permanent threat to life and property. There-
fore, immediate response to a fi re is imperative. The
main objective of the Fire Detection Control Panel
Series BC06 is to alarm and to react in time and, con-
sequently, save lives and protect property. For decades
LST have focused their aims to undertaking unrivaled
efforts in order to realise new innovations in the security
area. Research, development and production are loca-
ted within LST premises, thus guaranteeing fl exible and
reliable individual solutions.
Using a powerful processor system and a large number
of integrated functions, the Fire/Extinguishing Control
Panels Series BC06 ensure topmost effi ciency and
speed – prerequisites for saving lives and minimising
damage to property.
Description
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 2
ABuilding Safety. Building Security.
Clear concept
The combined Fire/Extinguishing Control Panels
BC06-1EXT and BC06-2EXT have been designed for
use in small fi re detection and extinguishing control sys-
tems with one fl ooding zone, and already in the basic
version they provide the following features:
• 4 conventional detector lines permit the connection
of automatic detectors and manual call points in con-
ventional technology as well as special detectors with
contact output. Each detector line can be individually
parameterised as detector zone for fi re alarms, as
detector zone for fault messages or as input for a
disable device or a fl ooding switch.
• If automatic detectors and manual call points are con-
nected together on one detector line, their activati-
ons can be differentiated and evaluated differently by
the control panel. To this aim, the manual call points
must be equipped with a special coding module.
• Two individually monitored, separately actuated siren
outputs with an output current of 1A and 0.5A respec-
tively, allow for the connection of acoustic or optical
signalling devices.
• Dry relay outputs indicate the alarm and fault conditi-
ons of the control panel. In addition, 8 open-collector
outputs whose parameters can be freely set as well
as two auxiliary inputs are available for general cont-
rol tasks.
• The Extinguishing Board EXB1-1, which is already in-
stalled in the control panel, allows for the actuation
of an extinguishing system according to EN 12094-1
with one fl ooding zone. In the course of commissio-
ning the control panel, the required functions and de-
lay times are parameterised according to the used
extinguishing agent as well as the country specifi c
regulations.
The extinguishing board provides 8 further open-coll-
ector outputs with fi xed preset functions.
• Logical combinations of detector zones for the ac-
tivation of external alarming devices and for the ac-
tuation of the extinguishing system allow for a high
degree of fl exibility. Thus, no additional expenses
arise for external relays or logic gates. Thanks to the
wide range of parameterisation possibilities, individu-
al requirements even under the most diffi cult ambient
conditions can be combined into a reasonable fi re
protection strategy.
• All events that occur can be output in English via a
connected printer or PC. Thus, all system conditions
and user operations that occurred are documented in
a clearly laid out way.
• The Fire/Extinguishing Control Panel BC06-2EXT in-
cludes a 4-digit, non-resettable alarm counter which
indicates the total number of alarms by means of an
LC display in the operating fi eld.
• A possible breakdown of the central processing board
is securely detected and displayed by the system.
• The processor-monitored power supply ensures per-
manent supervision and charging of the batteries.
This way, even during a power failure the untroubled
and uninterrupted operation (for more than 72 hours
depending on the design of the batteries) is guaran-
teed.
• Three hierarchised authorization levels for operation
and parameterisation provide a high degree of secu-
rity against unauthorized access.
• The control panel is easily operated and the parame-
ters are set via the display and operating fi eld. LEDs
indicate the current menu and the selected parame-
ter. This facilitates user guidance during commissio-
ning, operation and maintenance.
• The initial commissioning of the control panel is sig-
nifi cantly facilitated by the practical factory settings.
This guarantees easy and time-saving commissio-
ning.
The extremely fl at wall-mount cabinet allows for an easy
mounting in virtually any place of the building. Thanks to
its modern, ageless design, architectural requirements
and demands of the respective regulations are ideally
combined. Thanks to the compact design, the standard
case can accommodate batteries with up to 7Ah also
in the event of full extension (central processing board,
extinguishing board and an auxiliary module) of the con-
trol panel. Series BC06 thus stands for modularity and
easy expansion.
This product complies with all relevant standards of
EN 54 and EN 12094-1 and is tested by the VdS. LST‘s
high quality level is secured by a permanently monitored
quality management system certifi ed to ISO 9001.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 3
ABuilding Safety. Building Security.
By means of the Extinguishing Board EXB1-1, the
Fire/Extinguishing Control Panels BC06-1EXT and
BC06-2EXT provide numerous inputs and outputs with
fi xed or parameterisable function. With that, the follo-
wing components of an extinguishing system can be ac-
tuated and monitored in accordance with EN 12094-1:
• Activation devices for the manual activation of the
fl ooding process
• Emergency hold devices for the manual delay of the
fl ooding process
• Emergency abort devices for aborting the fl ooding
process
• Fault detection devices for monitoring the compon-
ents of the extinguishing system
• A disable device for the indication of the mechanical
blocking of the extinguishing agent‘s network
• A fl ooding switch that indicates the fl ow of the extin-
guishing agent
• A device for switching to the manual mode – for ex-
ample, a key switch
• Signalling devices for indicating the activated conditi-
on and the released condition
• The control device for activating the fl ooding – for
example, a solenoid valve
• Auxiliary outputs for actuating fl aps or for turning off
devices and systems
Extinguishing control
The operating fi eld of the Fire/Extinguishing Control Pa-
nels BC06-1EXT and BC06-2EXT provides 13 LEDs for
displaying the operating conditions and 4 buttons for
the operation of the extinguishing system.
The LEDs indicate the following operating conditions:
• Pre-activation/activation of the extinguishing module
• Released condition of the extinguishing output
• Extinguishing output fault
• Extinguishing module fault/disablement
• Extinguishing medium fault/fault of the fault input
• Emergency hold/emergency hold device fault
• Activation device fault/disablement
• Signal output activated/signal output faulty/disabled
• Manual mode of the extinguishing module
• Fault of the activated condition output
The buttons on the operating fi eld have the following
functions:
• Disable/enable the extinguishing module
• Start/terminate the manual mode
• Disable/enable the activation devices
• Disable/enable the signal output
Display and operating elements
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 4
ABuilding Safety. Building Security.
Specifi cations
Mains voltage 230VAC +10/-20%, 47...63Hz
Output/nominal voltage typ. 27.6VDC
Output current max. 2.2A
Output current siren outputs
output 1 max. 1A
output 2 max. 0.5A
(the sum of the currents of the signalling devices that are connected to the two outputs must not exceed 1A!)
Output current, extinguishing output max. 1A
Output current, activated condition output/signal output max. 500mA per output
Own current consumption (incl. extinguishing board) at 24V typ. 80mA (without optional componentries, line termination 5.6kΩ)
typ. 65mA (without optional componentries, line termination 47µF)
Line voltage typ. 20V (line termination 5.6kΩ)
typ. 23V (line termination 47µF)
Line current without fi re detectors typ. 3.7mA (line termination 5.6kΩ)
typ. 0mA (line termination 47µF)
Line termination 5.6kΩ or 47µF
Line resistance max. 50Ω per core
Ambient temperature -5°C to +50°C
Relative humidity max. 95% (no condensation)
Dimensions W × H × D 330 × 330 × 90 (mm)
Colour grey-white, RAL 9002
Weight without batteries approx. 3kg
Approvals 0786-CPD-20300
VdS pending
Fire Detection Control Panel BC06-1EXT
Order number 210223
Order name Fire Detection Control Panel BC06-1EXT/INT1
Fire Detection Control Panel BC06-2EXT
Order number 210224
Order name Fire Detection Control Panel BC06-2EXT/INT1
Functions of EN 12094-1
All mandatory functions of EN 12094-1 are integrated
into the Fire/Extinguishing Control Panels BC06-1EXT
and BC06-2EXT. Furthermore, the most important opti-
onal functions of this standard are supported:
• Parameterisable pre-discharge-warning time for the
delay of the activation
• Detector zone „extinguishing medium active“ se-
lectable for detecting the fl ow of the extinguishing
medium
• Monitoring of components of the extinguishing sys-
tem
• Input for connection of an emergency hold device
• Monitoring of a disable device
• Parameterisable fl ooding time
• Possibility to switch to the „manual only mode“
• Transmission of the triggering signal to further actu-
ations within the extinguishing system – for example,
warning devices
• Transmission of the triggering signal to further actua-
tions outside the extinguishing system – for example,
for turning off the air conditioning system
• Emergency abort device can be connected
• Activation of alarming devices with different alarm
signals

This manual suits for next models

1

Other LST Control Panel manuals

LST BCE216 BC216-2 User manual

LST

LST BCE216 BC216-2 User manual

LST Vds BC216-1 User manual

LST

LST Vds BC216-1 User manual

LST BC016-1 User manual

LST

LST BC016-1 User manual

LST BC216-1S User manual

LST

LST BC216-1S User manual

LST ABF216-1 User manual

LST

LST ABF216-1 User manual

LST Series BC216 User manual

LST

LST Series BC216 User manual

LST BC06 Series User manual

LST

LST BC06 Series User manual

LST BC016-2 User manual

LST

LST BC016-2 User manual

LST Vds EN 12094-1 User manual

LST

LST Vds EN 12094-1 User manual

LST LC216 Series User manual

LST

LST LC216 Series User manual

LST 130 User manual

LST

LST 130 User manual

Popular Control Panel manuals by other brands

Siemens FC361-ZZ Installation

Siemens

Siemens FC361-ZZ Installation

LeCroy CrossSync user manual

LeCroy

LeCroy CrossSync user manual

ensto Enervent eAir User instructions

ensto

ensto Enervent eAir User instructions

tau K590M installation guide

tau

tau K590M installation guide

Hanil Combi 508 quick guide

Hanil

Hanil Combi 508 quick guide

Crow PowerWave-8 Installation and programming guide

Crow

Crow PowerWave-8 Installation and programming guide

Helo OK 33 PUi Instructions for installation and use

Helo

Helo OK 33 PUi Instructions for installation and use

Pego ECP 200 Base 2 quick guide

Pego

Pego ECP 200 Base 2 quick guide

Bosch BE 300 LSN installation instructions

Bosch

Bosch BE 300 LSN installation instructions

Grundfos SLC Series Installation and operating instructions

Grundfos

Grundfos SLC Series Installation and operating instructions

FGMatic EURO230M1 instruction manual

FGMatic

FGMatic EURO230M1 instruction manual

technoswitch ORYX200 Series Installation & operation manual

technoswitch

technoswitch ORYX200 Series Installation & operation manual

elsner elektronik KNX WS1000 Color Brief Instruction

elsner elektronik

elsner elektronik KNX WS1000 Color Brief Instruction

Pego ECP202 EXPERT Use and maintenance manual

Pego

Pego ECP202 EXPERT Use and maintenance manual

Carrier Touch Pilot 30XW-V manual

Carrier

Carrier Touch Pilot 30XW-V manual

Biamp Vocia WR-1 Operation manual

Biamp

Biamp Vocia WR-1 Operation manual

Honeywell GX-Series Installation and setup guide

Honeywell

Honeywell GX-Series Installation and setup guide

Visonic POWERART installation instructions

Visonic

Visonic POWERART installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.