ABuilding Safety. Building Security.
F ire Detection Control Panel
BC016-1
• For application in small and
mid-sized systems
• Addressable conventional technology
with up to 16 detector zones
• Menu-driven operation
• Free parameter setup via PC
software or operating fi eld
• Factory settings allow for easy
commissioning
• EN 54/VdS-certifi ed
Fire is a permanent threat to life and property. There-
fore, immediate response to a fi re is imperative. The
main objective of the fi re detection control panel Series
BC016 is to alarm and to react in time and, conse-
quently, save lives and protect property. For decades
LST have focused their aims to undertaking unrivaled
efforts in order to realize new innovations in the security
area. Research, development and production are loca-
ted within LST premises, thus guaranteeing fl exible and
reliable individual solutions.
Using a powerful processor system, display texts, and a
large number of integrated functions, the fi re detection
control panels Series BC016 ensure topmost effi ciency
and speed – prerequisites for saving lives and minimi-
zing damage to property.
Description
Already in the basic version the fi re detection control
panel BC016-1 is equipped with eight detector lines in
conventional technology and, owing to its sophisticated
factory settings, is immediately ready for operation.
This allows for quick and effi cient application of the
product. The control panel can be expanded from 8 to
16 detector zones by means of the Detector Zone Ex-
tension MGE8-1.
The addressable conventional technology allows for the
connection of automatic and non-automatic fi re detec-
tors as well as special detectors with contact output.
Unambiguous identifi cation of the activated detector in
the event of an alarm facilitates the indication of the
detector number on the control panel‘s display. Auxiliary
outputs whose parameters can be freely set allow also
for the realization and clear display of challenging tasks
in the fi eld of fi re alarm technology.
In addition, one slot each is available for a Fire Brigade
Interface and for a Serial Interface Module, respectively.
The Fire Brigade Interface FWI016-1 allows for the con-
nection of country-specifi c standardized fi re brigade
control units or for the expansion of the control panel
with additional inputs and outputs for general control
tasks.
Via the Serial Interface Module SIM216-1 you can
address either a PC for the effi cient and clearly laid out
parameterisation of the fi re detection control panel, or
a printer. The Serial Interface Module SIM016-3 serves
for the connection of INFO-bus devices such as fi re bri-
gade control units, remote display and operating pa-
nels, remote indication units, etc.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
BC016-1_DBL_LST_EN_0804.PDF • PAGE 2
ABuilding Safety. Building Security.
Clear Concept
The fi re detection control panel BC016-1 has been desi-
gned for use in small and mid-sized systems and alrea-
dy in its basic version provides the following features:
• 8 conventional detector lines permit the connection
of automatic detectors and manual call points in con-
ventional technology as well as special detectors with
contact output. Individual detector identifi cation can
be achieved by means of an optional address modu-
le.
• A slot for connecting the Detector Zone Extension
MGE8-1 is available for the extension to 16 conventi-
onal detector lines.
• Dry relay outputs indicate the alarm and fault condi-
tions on the control panel. In addition, 16 open-coll-
ector outputs, two auxiliary inputs, and an additional
relay output are available for general applications.
• The optional Fire Brigade Interface FWI016-1 allows
for the connection of two independent transmitting
devices for a direct interconnection to a designated
alarm respondent (e.g., the fi re brigade) as well as
for the connection of a country-specifi c fi re brigade
control unit.
• Outputs with open parameters and logical combina-
tions of detector zones for the activation of external
controls and alarming devices allow for a maximum
of fl exibility. Thus, no additional expenses arise for
external relays, logic gates or timers. Thanks to the
wide range of parameterisation possibilities, individu-
al requirements even under the most diffi cult ambient
conditions can be combined into a reasonable fi re
protection strategy.
• The LC text display shows all present events with
date and time. This allows for quick and targeted
reaction in the event of a fi re as well as for easy main-
tenance.
• An event memory allows for the display of the latest
200 events at any time, including all required informa-
tion. Thus, all system conditions and user operations
that occurred are documented in a clearly laid out
way.
• A possible breakdown of the central processing board
is securely detected and displayed by the system.
• The processor-monitored power supply ensures per-
manent surveillance and charging of the batteries.
This way, even during a power failure the untroubled
and uninterrupted operation (for more than 72 hours
depending on the design) is guaranteed.
• Three hierarchized authorization levels for operation
and parameterisation facilitate a high degree of secu-
rity against unauthorized access.
• The control panel is easily operated menu-driven via
the display and operating fi eld. Clear instructions on
the display guide the user during commissioning,
operation and maintenance.
• The parameter data can be entered either via the
display and operating fi eld or, in a more comfortable
way, created by means of the PC software PARSOFT-1
and loaded into the control panel. Thus, a quick and
effi cient transfer of the system confi guration into the
control panel is guaranteed.
• After activation, the control panel is immediately rea-
dy for operation due to the practical factory setting.
This guarantees easy and time-saving commissio-
ning.
The extremely fl at wall mount cabinet allows for an easy
mounting in virtually any place of the building. Thanks to
its modern, ageless design, architectural requirements
and demands of the respective regulations are ideally
combined. The compact design allows for the accom-
modation of the optional Detector Zone Extension, the
Fire Brigade Interface, the Serial Interface Module, up
to 3 auxiliary modules (e.g., relay module, siren connec-
tion module) and batteries up to 22Ah apart from the
central processing board in the standard case. Series
BC016 thus stands for modularity and easy expansion.
This product complies with all relevant standards of
EN 54 and is VdS-certifi ed. In addition, the product also
holds several country-specifi c approvals and certifi ca-
tes. LST‘s high quality level is secured by a permanent-
ly monitored quality management system certifi ed by
ISO 9001.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
BC016-1_DBL_LST_EN_0804.PDF • PAGE 3
ABuilding Safety. Building Security.
Permanent Connection
Specifi cations
Mains voltage 230VAC +10/-15%, 50Hz
Output/nominal voltage typ. 28VDC
Output peak current max. 1.8A
Own current consumption at 24V typ. 70mA (without optional componentries)
Ambient temperature -5°C to +50°C
Relative humidity 95% (no condensation)
Dimensions W × H × D 380 × 480 × 83 (mm)
Colour gray-white, RAL 9002
Weight without accumulator approx. 5kg
Approvals (EN 54-2, EN 54-4) VdS G205023
FT 14/439/04 (Austria),
Part No. 210102
Order name Fire Detection Control Panel BC016-1/INT1
A variety of peripheral devices can be connected to the
fi re detection control panel BC016-1:
• Fire brigade key safe
• Fire brigade control unit
• Acoustic and optical signaling devices
• External protocol printer
• Remote indication unit
• Actuations
• Modules for remote parameterisation and remote
maintenance via computer newtork, modem or GSM
connection
– and much more.

Other LST Control Panel manuals

LST ABF216-1 User manual

LST

LST ABF216-1 User manual

LST 130 User manual

LST

LST 130 User manual

LST BCE216 BC216-2 User manual

LST

LST BCE216 BC216-2 User manual

LST BC216-1S User manual

LST

LST BC216-1S User manual

LST BC06 Series User manual

LST

LST BC06 Series User manual

LST Extinguishing Control Panel BC06-2EXT User manual

LST

LST Extinguishing Control Panel BC06-2EXT User manual

LST Series BC216 User manual

LST

LST Series BC216 User manual

LST Vds EN 12094-1 User manual

LST

LST Vds EN 12094-1 User manual

LST Vds BC216-1 User manual

LST

LST Vds BC216-1 User manual

LST BC016-2 User manual

LST

LST BC016-2 User manual

LST LC216 Series User manual

LST

LST LC216 Series User manual

Popular Control Panel manuals by other brands

Siemens FC361-ZZ Installation

Siemens

Siemens FC361-ZZ Installation

LeCroy CrossSync user manual

LeCroy

LeCroy CrossSync user manual

ensto Enervent eAir User instructions

ensto

ensto Enervent eAir User instructions

tau K590M installation guide

tau

tau K590M installation guide

Hanil Combi 508 quick guide

Hanil

Hanil Combi 508 quick guide

Crow PowerWave-8 Installation and programming guide

Crow

Crow PowerWave-8 Installation and programming guide

Helo OK 33 PUi Instructions for installation and use

Helo

Helo OK 33 PUi Instructions for installation and use

Pego ECP 200 Base 2 quick guide

Pego

Pego ECP 200 Base 2 quick guide

Bosch BE 300 LSN installation instructions

Bosch

Bosch BE 300 LSN installation instructions

Grundfos SLC Series Installation and operating instructions

Grundfos

Grundfos SLC Series Installation and operating instructions

FGMatic EURO230M1 instruction manual

FGMatic

FGMatic EURO230M1 instruction manual

technoswitch ORYX200 Series Installation & operation manual

technoswitch

technoswitch ORYX200 Series Installation & operation manual

elsner elektronik KNX WS1000 Color Brief Instruction

elsner elektronik

elsner elektronik KNX WS1000 Color Brief Instruction

Pego ECP202 EXPERT Use and maintenance manual

Pego

Pego ECP202 EXPERT Use and maintenance manual

Carrier Touch Pilot 30XW-V manual

Carrier

Carrier Touch Pilot 30XW-V manual

Biamp Vocia WR-1 Operation manual

Biamp

Biamp Vocia WR-1 Operation manual

Honeywell GX-Series Installation and setup guide

Honeywell

Honeywell GX-Series Installation and setup guide

Visonic POWERART installation instructions

Visonic

Visonic POWERART installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.