10SN
P. 1 / 2 EM-0819 Rev.4
INSTRUCTION MANUAL
MODEL 10SN
INPUT LOOP POWERED ISOLATOR
COMPONENT IDENTIFICATION
INSTALLATION
Use Standard Rack (model: 10BX❑).
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the
connection diagram label on the unit side.
CHECKING
1) Terminal wiring: Check that all cables are correctly
connected according to the connection diagram.
2) Input: Check current with an ammeter. Be sure that the
connected transmitter allows the load shown in the follow-
ing table.
3) Output: Check that output load is within the permissible
limit shown in the following table.
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
package you received as below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner ................................................... (1)
■ MODEL NO.
Check that model No. described on specification label is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, installation, connection and basic mainte-
nance procedures.
POINTS OF CAUTION
■ GENERAL
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +55°C (23
to131°F)withrelativehumiditywithin30to90%RHinorder
to ensure adequate life span and operation.
■ WIRING
• Do not install cables (input and output) close to noise
sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
+
–
INPUT
1
2
7
8
+
–
OUTPUT
CONNECTOR
OUTPUT
Body
Specification Label
Connection Diagram
Label
(side)
Terminal Cover
MODEL EQUIVALENT INPUT IMPEDANCE
10SN-A60 250Ω
10SN-H60 100Ω
10SN-AA0 230Ωplus output load
10SN-HA0 90Ωplus output load ×0.16
MODEL LOAD RESISTANCE
10SN-A60 50kΩor more
10SN-H60 50kΩor more
10SN-AA0 50 – 350Ω